General
The Liebert NX UPS uses intelligent and reliable
decentralized technology to achieve parallel opera-
tion of two modules of the same rating.
The 1+1 system is used to:
• Increase the reliability of the system to ensure
adequate power supply to the critical load con-
nected.
• Increase serviceability and allow the execution of
maintenance operations and reparations without
affecting the ordinary operating conditions of the
system (depending on the redundancy level).
Conditions for Parallel System
1. Each UPS module should have the same rating,
the same firmware and hardware version.
2. Each UPS module must have the same bypass
source.
3. The outputs of all UPS modules are connected
altogether.
4. The main inputs can be from different sources, but
the phase rotation sequence of main inputs,
bypass inputs and outputs must be correct and the
same.
5. The parallel logic cable and load sharing cable
must be connected in a ring correctly (See
)
Features of Parallel System
1. The hardware and firmware for parallel UPS
module operation is standard in the Liebert NX,
and the configuration can be set up by changing
the settings in configuration software.
2. It is easy to install the parallel cables in a ring,
providing high reliability and redundancy. And
the intelligent paralleling logic provides the user
with maximum flexibility. For example, shutting
down or starting up the UPS modules in the
parallel system can be done in any sequence. If an
overload transfer occurs, the whole system can
recover automatically from bypass mode after the
overload is cleared.
3. The total load of the parallel system can be
queried from each module’s liquid crystal display
screen.
4. Optional monitoring background software can
treat the entire parallel system as a big
single-module UPS, and provide corresponding
management. It can also get the information for all
modules by connecting to just one of the modules.
+
!
CAUTION
An external maintenance cabinet is strongly
recommended to maintain the power supply to
load in case of complete maintenance.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
2 Figure 1 '1+1' System block diagram Operating Principles Redundancy Paralleling The redundancy parallel system can noticeably improve system reliability. In normal condition, nei- ther UPS module works at full load. That means that even if the load is increased, the system will not transfer to byp...
3 Installation The basic installation procedure of parallel system is the same as that of single module system. The fol- lowing sections only introduce the installation proce- dures specific to the parallel system. Cabinet Installation Parallel system composed of two UPS modules The two UPS modules ...
4 Liebert Corporation 1050 Dearborn DriveP.O. Box 29186Columbus, OH 43229 Telephone: 1-800-877-9222Facsimile: 1-614-841-6022www.liebert.com © 2004 Liebert CorporationAll rights reserved throughout the world. Specifications sub- ject to change without notice. ® Liebert and the Liebert logo are regist...