Page 3 - TABLE OF CONTENTS; UPS
i TABLE OF CONTENTS I MPORTANT S AFETY I NSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.0 I NTRODUCTION AND S YSTEM D ESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.1 Device Overview . . . . . ...
Page 4 - ii; Liebert IntelliSlot; FIGURES
ii 5.0 M AINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 5.1 Test, Replacement and Disposal of Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 5.2 Storage . . . . . . . . . . . . . ...
Page 5 - SAVE THESE INSTRUCTIONS; halfwave rectification.; WARNING; son representative immediately.
1 I MPORTANT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important safety instructions. Read all safety and operating instructions before operating the uninterruptible power system (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user inst...
Page 6 - not
2 ! WARNING Although the Liebert ® GXT3 ™ has been designed and manufactured to ensure safety, improper use can result in electrical shock or fire. To ensure safety, observe the following precautions:• Turn Off and isolate the Liebert GXT3 before cleaning it. Use only a soft cloth; never use liquid ...
Page 7 - Leakage Current; ELECTROMAGNETIC COMPATIBILITY; —The Liebert; NOTICE; must to correct at his own expense.; Information for the Protection of the Environment; UPS SERVICING
3 Leakage Current ELECTROMAGNETIC COMPATIBILITY —The Liebert ® GXT3 ™ complies with the limits for a Class A Digital Device, Pursuant to Part 15 of FCC rules. Operation is subject to the following conditions: • This device may not cause harmful interference• This device must accept any interference ...
Page 8 - Introduction and System Description; NTRODUCTION; Congratulations on your choice of the Liebert; Figure 1; CAUTION
Introduction and System Description 4 1.0 I NTRODUCTION AND S YSTEM D ESCRIPTION Congratulations on your choice of the Liebert ® GXT3 ™ -10000T220 UPS. It provides conditioned power to microcomputers and other sensitive electronic equipment.When generated, AC power is clean and stable. However, duri...
Page 9 - Device Overview; Figure 2; UPS with Integrated Battery
Introduction and System Description 5 1.1 Device Overview The following table provides an overview of the various versions of the device: Figure 2 Liebert ® GXT3-10000T220 ™ front and rear views Table 1 Overview of UPS devices and batteries Type Model # Nominal power UPS with Integrated Battery Lieb...
Page 10 - Unpacking the UPS and Site Preparation; NPACKING; AND; Inspection; Upon receiving your Liebert; Required Setup Equipment; Figure 3; Storage; conditions. Refer to; Table 9; for permissible environmental conditions for storage.; Handling; dropped or subjected to severe impact.
Unpacking the UPS and Site Preparation 6 2.0 U NPACKING THE UPS AND S ITE P REPARATION 2.1 Inspection Upon receiving your Liebert ® GXT3-10000T220 ™ , examine the packaging for any signs of mishandling or damage. While removing shipping materials, inspect the UPS for damage. If any damage is noted, ...
Page 11 - Environmental Conditions; Install the Liebert; Access to Area; for; Inventory List; • Liebert MultiLink; NOTE
Unpacking the UPS and Site Preparation 7 2.4 Environmental Conditions Install the Liebert ® GXT3 ™ indoors in a controlled environment where it cannot be accidentally turned off. Place it on a level, even surface in an area with unrestricted airflow around the unit. The installation location must be...
Page 12 - Installation; NSTALLATION; Electrical preparations; and provide a means of isolating the UPS from utility.; applicable safety standards.; performed inside the UPS.; immediately upon application of AC input.; Table 2; Description; ENSURE THAT THE UNINTERRUPTIBLE POWER SYSTEM IS ISOLATED BEFORE; rating in accordance with the National Electric Code, ANSI/NFPA 70.
Installation 8 3.0 I NSTALLATION 3.1 Electrical preparations Before beginning installation, the input source must be isolated and locked out to prevent connection during installation. The input circuit breaker on the rear of the UPS must be in the Off position. 3.2 Suggested Cable Sizes 3.3 External...
Page 13 - External Electrical Connections; your cabling, based on local electrical codes.; Figure 4; Connecting Utility and Load; is; Terminal Blocks for UPS; Figure 5; Rear Panel; GET; Single Feed
Installation 9 3.4 External Electrical Connections The external electrical connections may be accessed by removing the protective panel on the rear of the UPS (see Figure 2 ) (panel ships loose from factory). Select a conduit knockout appropriate for your cabling, based on local electrical codes. Fi...
Page 14 - Figure 6; Input and Output Connection Requirements; additional ground screw terminals are supplied for use as needed.; UPS Feed; Jumper
Installation 10 Figure 6 Dual source input supply—input and output connections Figure 7 Hardwire terminals 3.6.1 Input and Output Connection Requirements • Any 120V loads must be distributed evenly between X1-X2, X1-X4 and X4-X2. Do not connect loads between X3-X2 or between X3-X4—these are not stan...
Page 15 - Connecting Power Cables; Connect the utility to the corresponding input terminals (see; Figure 7; External Battery Cabinets; Figure 8
Installation 11 3.7 Connecting Power Cables 1. Open the UPS input breaker.2. Open the UPS bypass breaker.3. Set the maintenance breaker to the Bypass position.4. Remove the electrical connection protective panel, if installed, from the rear UPS panel.5. Connect loads to the output terminals as illus...
Page 16 - Operation; PERATION; Block Diagram; The Liebert; Figure 9
Operation 12 4.0 O PERATION 4.1 Block Diagram The Liebert ® GXT3-10000T220 ™ consists of the following main components: • 2 utility inputs with separate breakers—utility and bypass• rectifier/booster, inverter and charger• electronic bypass• 2-position Maintenance Bypass Breaker—UPS and BYPASS• inte...
Page 17 - Control Panel; and; Figure 10 Control Panel; Lighted LEDs; When the BYPASS LED is flashing, the utility is out of tolerance.; would no longer be supplied.
Operation 13 4.2 Control Panel The Control Panel’s LCD and buttons are used to initiate various UPS operations, tests and commands and to view the status of the UPS.By pressing the Menu Up or Menu Down and Enter keys , it is possible to scroll through the various menus. For details, see 4.2.1 - Cont...
Page 18 - Figure 11 Menu tree
Operation 14 Figure 11 Menu tree Start Window System Status Main Setup Control Contrast Set Battery Test Alarm Control Turn UPS On/Off Status Log About Version Language Tag Number UPS Address DC Start Battery Test Interval Battery Pack Audible Alarm Output Voltage Clear Event Log IP Types Battery Te...
Page 19 - Table 3
Operation 15 Table 3 Displayed text—system block and main menu Item # and Name Description Status Menu Measure value Unit Output Volt V Output Freq 0.1Hz Output Current A Output Watt W Output VA VA Output Load % Input Volt V L2 Input Volt N/A L3 Input Volt N/A Input Freq 0.1Hz Back Voltage V Batt Ca...
Page 21 - Buzzer alarm operation; —The buzzer alarm can be switched On or Off.; Clear fault—; Fault
Operation 17 4.2.4 Fault Indicators If a fault occurs, the UPS automatically switches to BYPASS mode, ONLY in case of a battery disconnect fault will the original operating mode be maintained. The fault message alternates with UPS mode once a second, the red Fault LED illuminates on the control pane...
Page 22 - Initial UPS Startup Procedure; Turn UPS to BYPASS; Carrying out this procedure will interrupt the supply to the load.
Operation 18 4.3 Initial UPS Startup Procedure 1. Inspect all power connections to ensure they are correct and secure.2. Open external circuit breakers/fused disconnects to the connected loads.3. Close all upstream circuit breakers and fused disconnects.4. Use a voltmeter to verify proper input volt...
Page 23 - Return from Maintenance Bypass; The load now is supplied via electronic bypass.; Maintenance Breaker, Off Position; could be supplied immediately when the output is enabled. (; This test involves putting the Liebert
Operation 19 4.6 Return from Maintenance Bypass 1. Ensure all switches and circuit breakers upstream of the UPS are closed.2. Ensure that both input circuit breakers are in the On position.3. Turn the Maintenance breaker from BYPASS to UPS and replace the cover. The load now is supplied via electron...
Page 24 - Maintenance; AINTENANCE; Test, Replacement and Disposal of Batteries; connections in accordance with; Cleaning; Table 7; Unit Type and Model #; Liebert External Battery Cabinet
Maintenance 20 5.0 M AINTENANCE 5.1 Test, Replacement and Disposal of Batteries The Liebert ® GXT3 ™ is designed to allow the user to replace the internal battery pack safely. Refer to Table 7 for internal battery pack part numbers for Liebert GXT3 UPS and Liebert External Battery Cabinets: Read all...
Page 25 - Communication; OMMUNICATION; Communication Interface Port; Dry Contact; The Dry Contact includes eight pins, as shown and defined in; Figure 12 Dry contact pin layout; mounted at a remote location.; connection of the pins in Set 3 is changed.
Communication 21 6.0 C OMMUNICATION 6.1 Communication Interface Port The Liebert ® GXT3 ™ UPS has a terminal block on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows. 6.2 Dry Contact The Dry Contact includes eight pins, as shown and defined in Figure 1...
Page 26 - and mounted at remote location.; The Liebert IntelliSlot port accepts three optional cards:; for remote connection will be via terminal block
Communication 22 6.2.2 Battery Mode Shutdown Battery Mode Shutdown permits shutting down the UPS by turning off the rectifier, inverter and static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active.Battery Mode Shutdown can b...
Page 27 - MultiLink; and delivers support for built-in shutdown for AS/400 systems.; Remote Emergency Power Off; with national and local wiring codes and regulations.; REPO switch connection diagram; be shielded and run separately from power cables.
Communication 23 6.3.1 Liebert ® MultiLink ® Liebert MultiLink continually monitors the UPS and can shut down your computer or server in the event of an extended power failure.Liebert MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot ® SNMP/Web card is insta...
Page 28 - Troubleshooting; ROUBLESHOOTING; technical; Messages
Troubleshooting 24 7.0 T ROUBLESHOOTING If any technical problems should occur, check the following before contacting Liebert ® technical support: • Is the utility voltage present at the UPS input?• Has the input fuse blown or have the circuit breakers tripped?• Has the UPS startup procedure been fo...
Page 29 - Specifications; PECIFICATIONS
Specifications 25 8.0 S PECIFICATIONS Table 9 Liebert ® GXT3 ™ specifications Model Rating, VA (W) 10,000 (9000) Dimensions, in. (mm) Unit, W x D x H 31.5 x 11.81 x 26.57 (800 x 300 x 675) Shipping, W x D x H 41.8 x 16.7 x 34 (1062 x 426 x 866) Weight, lb (kg) Unit 308 (140) Shipping 428 (194) Input...
Page 30 - Battery cabinet specifications; Model Number; Typical battery run times for the Liebert; Battery Cabinets
Specifications 26 Table 10 Battery cabinet specifications Model Number GXT3-240TBATTCE Dimensions, W x D x H, in. (mm) Unit 31.5 x 11.81 x 26.57 (800 x 300 x 675) Shipping 41.8 x 16.7 x 34 (1062 x 426 x 866) Weight, lb (kg) Unit 243 (110) Shipping 309 (140) Internal Battery Parameters Type Valve-reg...
Page 31 - RODUCT; To register for warranty protection:; Product Warranty Registration; and fill in the form.
Product Warranty Registration 27 9.0 P RODUCT W ARRANTY R EGISTRATION To register for warranty protection: • Visit the Quick Links section of Liebert’s Web site at: http://www.liebert.com • Click on Product Warranty Registration and fill in the form. If you have any questions, please contact us at: ...
Page 32 - by helping customers optimize their data center; Business-Critical Continuity
Ensuring The High AvailabilityOf Mission-Critical Data And Applications. Emerson Network Power, a business of Emerson (NYSE:EMR),is the global leader in enabling Business-Critical Continuity ™ from grid to chip for telecommunication networks, data centers,health care and industrial facilities. Emers...