CSU3000 Chiller For CTI PETNet Cyclotron w/100% Redundancy 1

Keeping Business in Business

CSU3000 Chiller

For CTI PETNet Cyclotron w/100% Redundancy

• Dedicated cooling supplies the proper temperature and water flow year round.
• Factory-tested, piped, wired and charged for hassle-free startup and operation.
• Local service and parts for quick and knowledgeable maintenance and service.
• Optional switch-over to alternate water source provides redundant, continuous operation.
• Optional remote monitoring systems keep you informed of chiller operation.
• Standard product ETL/CSA certified.
• ISO 9001 certified company.

PETNet Cyclotron Specifications

Fluid Specified

Water / Glycol

Max Heat Dissipation—BTUH (kW)

60,000 (17.6)

Fluid Temperature Range—°F (°C)

40-50 (4.4-10)

Fluid Flow Rate—GPM (l/m)

10 (38)

Fluid Pressure Drop—PSI (kPa)

5 (34)

CSU Chiller Specifications

Model Number

CS109A

Fluid Circulated

Water

Net Cooling Capacity—BTUH (kW)

121,900 (35.7)

Leaving Fluid Temperature—°F (°C)

45 (7.2)

Fluid Flow Rate—GPM (l/m)

24 (91)

PETNet Cyclotron Pressure Drop—PSI (kPa)

5 (34)

Chiller Pressure Drop—PSI (kPa)

8.4 (58.1)

Pump Total Head—PSI (kPa)

35.9 (247.7)

Pump HP (kW)

1.5 (1.1)