Liebert CSU 3000 - Manual
Liebert CSU 3000 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
CSU3000 Chiller Designed For Siemens Magnetom Harmony / Symphony 1
Keeping Business in Business
CSU3000 Chiller Designed
For Siemens Magnetom Harmony / Symphony
• Dedicated, equipment-matched cooling supplies the proper temperature and water flow, year round.
• Factory-tested, piped, wired, and charged for hassle-free start-up and operation.
• Local service and parts for quick and knowledgeable maintenance and service
• Optional switch-over to alternate water source provides redundant continuous operation.
• Optional remote monitoring systems keep you informed of chiller operation.
• Standard product ETL/CSA Certified.
• ISO 9000 Certified Company.
Magnetom Harmony/Symphony Specifications
Fluid Specified
Water/Glycol
Max Heat Dissipation—BTUH (kW)
102,390
Fluid Temperature Range—°F (°C)
43-54 (6-12)
Fluid Flow Rate—GPM (l/m)
13 (50)
Fluid Pressure Drop—PSI (kPa)
21.8 (150)
Process Fluid Chiller Specifications
Model Number
CS135A
Fluid Circulated
Water
Net Cooling Capacity—BTUH (kW)
116,000 (34)
Leaving Fluid Temperature—°F (°C)
45 (7.2)
Fluid Flow Rate—GPM (l/m)
24 (91)
Harmony / Symphony Pressure Drop—PSI (kPa)
21.8 (150)
Chiller Pressure Drop—PSI (kPa)
11.7 (81)
Pump Total Head—PSI (kPa)
56.3 (388)
Pump HP (kW)
3 (2.2)
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.