CSU3000 Chiller Designed For Siemens Magnetom Harmony / Symphony 1

Keeping Business in Business

CSU3000 Chiller Designed

For Siemens Magnetom Harmony / Symphony

• Dedicated, equipment-matched cooling supplies the proper temperature and water flow, year round.
• Factory-tested, piped, wired, and charged for hassle-free start-up and operation.
• Local service and parts for quick and knowledgeable maintenance and service
• Optional switch-over to alternate water source provides redundant continuous operation.
• Optional remote monitoring systems keep you informed of chiller operation.
• Standard product ETL/CSA Certified.
• ISO 9000 Certified Company.

Magnetom Harmony/Symphony Specifications

Fluid Specified

Water/Glycol

Max Heat Dissipation—BTUH (kW)

102,390

Fluid Temperature Range—°F (°C)

43-54 (6-12)

Fluid Flow Rate—GPM (l/m)

13 (50)

Fluid Pressure Drop—PSI (kPa)

21.8 (150)

Process Fluid Chiller Specifications

Model Number

CS135A

Fluid Circulated

Water

Net Cooling Capacity—BTUH (kW)

116,000 (34)

Leaving Fluid Temperature—°F (°C)

45 (7.2)

Fluid Flow Rate—GPM (l/m)

24 (91)

Harmony / Symphony Pressure Drop—PSI (kPa)

21.8 (150)

Chiller Pressure Drop—PSI (kPa)

11.7 (81)

Pump Total Head—PSI (kPa)

56.3 (388)

Pump HP (kW)

3 (2.2)