Liebert OpenComms™ 485

Quick Start Guide

I

NSTALL

• Locate the Intellislot option for your Liebert equipment.
• You might need to remove a plastic Intellislot cover.
• Insert the OpenComms 485 Card into the Intellislot bay.
• Secure the card with the supplied screws.
• Connect RS-485 cable.

IGM

: The card ships with IGM service enabled. (No configuration

is required for IGM communications.)

Modbus

: To assign a server ID address, use the Service Terminal

to configure the card. Proceed to Steps 2 & 3.

C

ONNECT

THE

C

ABLE

• Locate the blue serial configuration cable (null modem) that shipped

with the card.

• Connect the configuration cable to the DB-9 port on the card and to a

COM port on your PC.

C

ONFIGURE

THE

C

ARD

• Use terminal emulation software,

such as HyperTerminal™, to

open a direct connection to the

card.

• Press

ENTER

for the Main

Menu, above right.

• Select option

1

and press

enter

to access the communications

settings, shown at right.

• Enter

1

and press

enter

to

enable the Modbus application.

• At the next screen, enter

3

to

access the screen to set the

server ID for the OC-485 card

(the ID default is 1, but may be

any number up to 255). In the

example below right, the server

ID is “2.”

• Press

Esc

to return to the Main

Menu.

• Enter

X

and press

Enter

to exit

HyperTerminal, save your

changes and reboot the card.

Baud Rate:

9600

Data Bits:

8

Parity:

None

Stop Bits:

1

Flow Control: None