Liebert 350VA to 1000VA - Manual

Liebert 350VA to 1000VA

Liebert 350VA to 1000VA – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
Page: / 8

Table of Contents:

  • Page 2 – During input power source abnormalities (sags and swells), the AC; Design Requirements; Maximum specified output load capacity of the UPS, regardless of; Performance Requirements; The UPS operates at these values without drawing power from the
  • Page 3 – 0 Hz Applications; AC Output; Overload Warning (visual and audible alarms) occurs
  • Page 4 – level
  • Page 5 – The UPS is convection cooled.; Criteria A
  • Page 6 – Bi-Directional Converter; The following DC shutdown levels protect the UPS:
  • Page 7 – Display and Controls; C) for a minimum of 5; Output Distribution
  • Page 8 – Communications; The pin out configuration of the DB9 connector is:
Loading the manual

PowerSure PSA

Guide Specification

350 – 1000VA

SL-23271 8/03

1

Liebert PowerSure PSA UPS

GUIDE SPECIFICATIONS

350VA to 1000VA

Single - Phase Uninterruptible Power Supply Systems

1.0

GENERAL

1.1

SUMMARY

This specification defines the electrical and mechanical characteristics and requirements for a continuous-
duty single-phase, solid-state, uninterruptible power system. The uninterruptible power system, hereafter
referred to as the UPS, will provide high-quality AC power for sensitive electronic equipment loads.

1.2

STANDARDS

The UPS is designed in accordance with the applicable sections of the current revision of the following
documents. Where a conflict arises between these documents and statements made herein, the statements
in this specification will govern.

120V Units

UL 1778, c-UL listed (to CSA 22.2 No. 107.1)
FCC Part 15, Subpart B, Class B
ANSI C62.41, Category A, Level 3 (IEEE 587, Category A);
EN61000-4-5, Level 3, Criteria A
EN61000-4-2, Level 3, Criteria A
EN61000-4-3, Level 3, Criteria A
EN61000-4-4, Level 4, Criteria A
EN61000-4-6, Level 3, Criteria A
EN61000-3-2
EN61000-3-3
ISTA Procedure 1A

230V Units

EN50091-1-1, TUV/GS listed, CE compliance mark
EN50091-2, Class B
EN61000-4-2, Level 3, Criteria A
EN61000-4-3, Level 3, Criteria A
EN61000-4-6
EN61000-4-4, Level 4, Criteria A
EN61000-4-5, Level 3, Criteria A
EN61000-3-2
EN61000-3-3
ISTA Procedure 1 A

1.3.

SYSTEM DESCRIPTION

1.3.1

Modes of Operation

The UPS is designed to operate as a line-interactive system in the following modes:

A.

Normal -

The critical AC load is continuously supplied with filtered power. The battery

charger maintains a float-charge on the battery.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - During input power source abnormalities (sags and swells), the AC; Design Requirements; Maximum specified output load capacity of the UPS, regardless of; Performance Requirements; The UPS operates at these values without drawing power from the

PowerSure PSA Guide Specification 350 – 1000VA SL-23271 8/03 2 B. Voltage Boost/Buck - During input power source abnormalities (sags and swells), the AC output power is corrected by means of boost (sag correction) or buck (swell correction)compensation taps. Operation of the compensation taps automa...

Page 3 - 0 Hz Applications; AC Output; Overload Warning (visual and audible alarms) occurs

PowerSure PSA Guide Specification 350 – 1000VA SL-23271 8/03 3 127 VAC nominal: single phase, 2-wire-plus-ground: 90 ─ 150 VAC (±3VAC), Buck compensation: 141VAC (±3VAC)Boost1 compensation: 113VAC (±3VAC)Boost2 compensation: 100VAC (±3VAC) 220 VAC nominal: single phase, 2-wire-plus-earth: 155 ─ 270 ...

Page 4 - level

PowerSure PSA Guide Specification 350 – 1000VA SL-23271 8/03 4 F. Voltage Transient Response: ±15% in Normal mode for 0-100-0% loading of the UPS rating, ±5% in Battery mode for 20-100-20% loading of the UPS rating. G. Transient Recovery Time: To within ±8% of nominal voltage in < 2 cycles. H. Ef...