Kohler 8.5/12RES - Manual

Kohler 8.5/12RES

Kohler 8.5/12RES – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
Page: / 4

Table of Contents:

  • Page 2 – Application Data
  • Page 3 – Alternator; Alternator Features; Sound Data
  • Page 4 – Dimensions and Weights; Standard Features; Model RDT Automatic Transfer Switch
Loading the manual

Model:

8.5/12

RES

Multi-Fuel

LP Vapor/Natural Gas

Standard Features

D

ADC-RES Advanced Digital Control

d

Designed for today’s most sophisticated electronics

d

Electronic speed control responds quickly to varying

household demand

d

Digital voltage regulation protects your sensitive

electronics from harmonic distortion and unstable power

quality

d

LED display shows system status and setup information

D

Engine Features

d

Kohler Command PRO

r

OHV engine with hydraulic

valve lifters for reliable performance without routine

valve adjustment or lengthy break-in requirements

d

Digital Spark Advance Ignition (DSAI) optimizes engine

performance for natural gas and LP vapor fuels (12RES

only)

d

Simple field conversion between natural gas and LP

vapor fuels while maintaining emission certification

D

Designed for Easy Installation

d

Polymer base eliminates the need for a concrete

mounting pad, reducing installation time and cost

d

Fuel and electrical connections through the enclosure

wall eliminate the need for stub-ups through the bottom

d

Load connection terminal block allows easy field wiring

d

Designed for outdoor installation only

D

Certifications

d

Meets emission regulations for U.S. Environmental

Protection Agency (EPA) with both natural gas and

LPG.

Note:

CARB does not regulate emergency standby

generators outputting less than 50 HP. Only the EPA

standards apply.

d

UL 2200 listed (60 Hz models)

d

CSA certification available (60 Hz models)

d

Accepted by the Massachusetts Board of Registration of

Plumbers and Gas Fitters

D

Warranty

d

5-year / 2000 hour warranty for on-grid (standby)

applications in locations served by a reliable utility

source

d

18 month / 1000 hour warranty for off-grid (non-standby)

applications

The Kohler

r

Advantage

D

The Smart Choice

Known for its reliability, the Kohler 12 kW generator set

was named a “Best Buy” as well as the highest-rated

generator in a leading consumer magazine in October,

2006

D

Powerful

Exclusive Powerboost

t

technology allows the Kohler

12 kW generator to start and run a typical 4 ton

(48,000 BTU) central air conditioner, while still running

other home appliances and electronics *

D

Clean Power for Sensitive Electronics

Protects sophisticated electronics with clean, stable power

that exceeds strict utility requirements and IEEE standards

for total harmonic distortion (THD)

D

Fast Response

Kohler generator sets restore power in as little as 10

seconds

D

Quiet

Quiet operation: 65 dB(A) at 7 m maintains neighborhood

solitude

D

Premium Five-Year Limited Warranty

G4-97 (8.5/12RES) 4/14n

Generator Ratings

Model

Voltage

Phase

Hz

Alternator

Standby Ratings

Natural Gas

LP Gas

kW/kVA

Amps

kW/kVA

Amps

8.5RES

120/240

1

60

2F4

7.0/7.0

29

8.5/8.5

35

8.5RES

115/230

1

50

2F4

6.3/6.3

27

7.5/7.5

33

12RES

120/240

1

60

2F4

10.4/10.4

43

12.0/12.0

50

12RES

115/230

1

50

2F4

9.3/9.3

40

10.5/10.5

46

RATINGS: Standby ratings apply to installations served by a reliable utility source. All single-phase units are rated at 1.0 power factor. The standby rating is applicable to variable loads with an average

load factor of 80% for the duration of the power outage. No overload capacity is specified at this rating. Ratings are in accordance with ISO--3046/1, BS5514, AS2789, and DIN 6271. GENERAL

GUIDELINES FOR DERATING:

ALTITUDE

: Derate 4% per 305 m (1000 ft.) elevation above 153 m (500 ft.).

TEMPERATURE

: Derate 1.5% per 5.5

_

C (10

_

F) temperature increase above 16

_

C

(60

_

F). Availability is subject to change without notice. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability

whatsoever. Contact your local Kohler Co. generator distributor for availability.
* Due to the cycling operation of many electrical appliances, the generator set may not run all appliances simultaneously. Check the appliance manufacturer’s specifications for actual power

requirements. Consult a Kohler

r

Power Systems professional for your exact residential power system requirements.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Application Data

G4-97 (8.5/12RES) 4/14n Application Data Engine Engine Specifications 60 Hz 50 Hz Manufacturer Kohler Engine: model, type 8.5RES CH640 4-Cycle 12RES CH740 4-Cycle Cylinder arrangement V-2 Displacement, L (cu. in.) 8.5RES 0.624 (38) 12RES 0.725 (44) Bore and stroke, mm (in.) 8.5RES 77 x 67 (3.03 x 2....

Page 3 - Alternator; Alternator Features; Sound Data

G4-97 (8.5/12RES) 4/14n Alternator Alternator Features D Compliance with NEMA, IEEE, and ANSI standards for temperature rise D Self-ventilated and dripproof construction D Windings are vacuum-impregnated with epoxy varnish for dependability and long life D Superior voltage waveform and minimum harmo...

Page 4 - Dimensions and Weights; Standard Features; Model RDT Automatic Transfer Switch

W L H  2005, 2006, 2007, 2008, 2009, 2012, 2013, 2014 by Kohler Co. All rights reserved. DISTRIBUTED BY: Dimensions and Weights Overall Size, L x W x H: 1123 x 726 x 804 mm (44.2 x 28.6 x 31.6 in.) Weight: 182 kg (400 lb.) Shipping weight: 195 kg (430 lb.) NOTE: These drawings are provided for refe...

Other Kohler Models