Series

165

Automatic Transfer Switch

for use on Standby Systems

Cat No 165A2200F3C

Ser No 123456

200 A BOM 999999

240 V 60 Hz

381333–163 C

50 Hanover Road, Florham Park, New Jersey 07932–1591 USA

1 800 937–2726 (ASCO), for service call 1 800 800–2726 (ASCO) www.asco.com

ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3

telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca

Series 165 Automatic Transfer Switches

rated 100, 200, & 230 amps, single phase, 240 V ac

Owner’s

Manual

for automatic 2–wire start generators

DANGER is used in this manual

to warn of risk of electrical shock

from high voltages capable of

causing shock, burns, or death.

WARNING is used in this

manual to warn of possible

personal injury.

!

CAUTION is used in this manual to warn

of possible equipment damage.

!

Installation should be performed by a licensed electrician

and in accordance with the National Electrical Code (NEC)

and all local electrical code requirements. Read and

understand all instructions before installing, servicing, or

operating.

Failure to do so could result in serious

personal injuries or property damage.

ASCO Series 165 Automatic Transfer Switches are Listed

under the Underwriter’s Laboratories Standard for Transfer

Switch Equipment, UL–1008. They are intended for use

only in optional standby systems in accordance with the

National Electrical Code, NEC/NFPA 70, Article 702. This

ATS is for use with 2–wire automatic start generators only.
Refer to

Application Information 381339–219

to confirm

that you have selected the appropriate product for the

intended installation.

Rating Label

Each Automatic Transfer Switch (ATS) has rating labels to

define the loads and fault current withstand/ closing ratings.

Refer to those label on the Transfer Switch for specific values.

INJURY or SWITCH DAMAGE

Do not exceed the rating label

values; it can cause personal in-

jury or serious switch damage.

!

Nameplate

The

Transfer

Switch

nameplate includes data

for each specific ASCO

Series 165 ATS. Use the

switch only within the

limits shown on this

nameplate.

A

typical

Catalog Number is also

shown below with its

elements explained:

165

A

2

200

F

3

C

control group code

3 = automatic

product

designation

poles

2 = 2 lines

ampere rating

100, 200, or 230 amps

voltage code

F = 240 V AC

Catalog number

neutral

A = solid neutral

enclosure

C = Type 1

F = Type 3R

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - TABLE OF CONTENTS; DANGER

2 TABLE OF CONTENTS Specifications 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Introduction 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Elect...

Page 3 - The Series 165 Automatic Transfer

3 SPECIFICATIONS ENCLOSED AUTOMATIC TRANSFER SWITCH Enclosure Size Type 1 24” H x 14¼” W x 8” D . . . . . . . . . . . . . . . . . . (610 mm H x 362 mm W x 203 mm D) Type 3R 25” H x 14¾” W x 8½” D . . . . . . . . . . . . . . . (635 mm H x 375 mm W x 216 mm D) Weight Type 1 enclosure 67 lb . . . . . ....

Page 4 - INSTALLATION; ELECTRICAL LINE CONNECTIONS

4 INSTALLATION Installation of the ASCO Series 165 automatic transfer switch must be performed by a licensed electrician. It must be installed according to the National Electrical Code and all local electrical code requirements. Refer to the installation drawing and wiring diagram. MALFUNCTION or SH...