ICP NXH548GKA100 - Installation Manual
ICP NXH548GKA100 – Installation Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Unpack Unit; CAUTION
- Page 3 – FEEDER TUBE; Fig. 3 – Defrost Thermostat Location; Make Piping Connections; WARNING; PERSONAL INJURY AND ENVIRONMENTAL; UNIT DAMAGE HAZARD; Residential Piping and Long Line; Outdoor Unit Connected To Factory Approved Indoor
- Page 4 – VALVE CORE; Brazing Connections; Installing with Indoor Piston
- Page 5 – Install Liquid Line Filter Drier Indoor; Evacuate Refrigerant Tubing and Indoor Coil; Deep Vacuum Method; Final Tubing Check; Make Electrical Connections; Route Ground and Power Wires
- Page 6 – Connect Control Wiring; LEGEND; Final Wiring Check; Compressor Crankcase Heater
- Page 7 – ENVIRONMENTAL HAZARD; UNIT OPERATION AND SAFETY HAZARD; Follow these steps to properly start up system:; Cooling; Heating; NOTE
- Page 8 – Fig. 12 – Defrost Control; Check Charge; Units with Cooling Mode TXV
- Page 9 – Units with Indoor Pistons; Table 5 – Additional Subcooling Required -
- Page 10 – Table 6 – Additional Subcooling Required -
- Page 11 – Table 7 – Additional Subcooling Required -
- Page 12 – Table 8 – Required Liquid Line Temperatures; Table 9 – Superheat Charging (Heat Pump Only); Table 10 – Required Suction–Line Temperature
- Page 13 – FINAL CHECKS; IMPORTANT; CARE AND MAINTENANCE; R- 410A REFRIGERANT QUICK REFERENCE GUIDE
428 01 5107 05
07/25/18
INSTALLATION INSTRUCTIONS
R- 410A Split System Heat Pumps
N4H4 / R4H4 / WCH4 / NXH5
These instructions must be read and understood completely before attempting installation.
NOTE
: Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory–authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.
Recognize safety information. This is the safety–alert symbol
!
!
.
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words; DANGER, WARNING, and
CAUTION. These words are used with the safety–alert symbol.
DANGER identifies the most serious hazards which
will
result in
severe personal injury or death.
WARNING signifies hazards
which
could
result in personal injury or death. CAUTION is used
to identify unsafe practices which
may
result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which
will
result in enhanced installation, reliability, or
operation.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors.
Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.
!
WARNING
INSTALLATION RECOMMENDATIONS
NOTE
: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where
unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate
for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding un-
necessary turns and bends.
4. Leave some slack between structure and unit to absorb vi-
bration.
5. When passing refrigerant tubes through the wall, seal open-
ing with RTV or other pliable silicon–based caulk (see Fig.
1).
6. Avoid direct tubing contact with water pipes, duct work,
floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap which comes in direct contact with
tubing (see Fig. 1).
8. Ensure that tubing insulation is pliable and completely sur-
rounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation (see Fig. 1).
10. Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
INSULATION
SUCTION TUBE
LIQUID TUBE
OUTDOOR WALL
INDOOR WALL
LIQUID TUBE
SUCTION TUBE
INSULATION
CAULK
HANGER STRAP
(AROUND SUCTION
TUBE ONLY)
JOIST
1” (25.4 mm)
MIN
THROUGH THE WALL
SUSPENSION
A07588
Fig. 1 – Connecting Tubing Installation
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for ICP NXH548GKA100
Summary
2 428 01 5107 05 Specifications subject to change without notice. When outdoor unit is connected to factory–approved indoor unit,outdoor unit contains system refrigerant charge for operation with AHRI rated indoor unit when connected by 15 ft. (4.57 m) offield–supplied or factory accessory tubing. F...
428 01 5107 05 3 Specifications subject to change without notice. FEEDER TUBE DEFROST THERMOSTAT STUB TUBE A97517 Fig. 3 – Defrost Thermostat Location Table 1 – Accessory Usage Accessory REQUIRED FOR LOW–AMBIENT COOLING APPLICATIONS (Below 55 F / 12.8 C) REQUIRED FOR LONG LINE APPLICATIONS* REQU...
4 428 01 5107 05 Specifications subject to change without notice. 3. Find plastic bag taped to unit containing copper adapter tube, brass nut, and plastic washer. 4. Install plastic washer in the seat inside piston body.5. Fit brass nut onto adapter tube and install tube onto liquid service valve. T...