Page 3 - Contents
Contents iii Hitachi Universal Storage Platform VM Installation Planning Guide Contents Preface ................................................................................................... v Safety and Environmental Notices.........................................................................
Page 4 - Acronyms and Abbreviations
Power Specifications and Requirements............................................................ 2-13 Power Specifications and Power Supplies ................................................... 2-13 Breaker Configurations ................................................................................
Page 5 - Preface; This preface includes the following information:
Preface v Hitachi Universal Storage Platform VM Installation Planning Guide Preface This document provides installation and configuration planning information for the Hitachi Universal Storage Platform VM (USP VM) storage system. Please read this document carefully to understand the installation req...
Page 6 - Safety and Environmental Notices; Federal Communications Commission (FCC) Statement; “EINE LEICHT ZUGÄNGLICHE TRENN-VORRICHTUNG, MIT EINER KONTAKT-; CLASS 1 LASER PRODUCT; Beseitigung vom Benutzer geeignete Maßnahmen zu ergreifen sind.; Intended Audience; This document assumes the following:
Safety and Environmental Notices Federal Communications Commission (FCC) Statement This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interfe...
Page 7 - Changes in this Revision; Added information on the 750-GB hard disk drive (; Document Organization; chapter title; Referenced Documents; Hitachi Universal Storage Platform V/VM User and Reference Guide,
Product Version This document revision applies to Universal Storage Platform VM microcode 60-02-0x and higher. Document Revision Level Revision Date Description MK-97RD6679-00 November 2007 Initial release, supersedes and replaces MK-97RD6079 Changes in this Revision • Added information on the 750-G...
Page 8 - Document Conventions; Convention for Storage Capacity Values
Document Conventions The term “Universal Storage Platform VM” refers to all models of the Universal Storage Platform VM storage system, unless otherwise noted. This document uses the following icons to draw attention to information: Icon Meaning Description Note Calls attention to important and/or a...
Page 9 - Getting Help; The circumstances surrounding the error or failure.; Comments
Getting Help If you need to call the Hitachi Data Systems Support Center, make sure to provide as much information about the problem as possible, including: • The circumstances surrounding the error or failure. • The exact content of any error message(s) displayed on the host system(s). • The servic...
Page 11 - the Universal Storage Platform VM.
1 Planning for Installation 1-1 Hitachi Universal Storage Platform VM Installation Planning Guide Planning for Installation This chapter describes the requirements and procedures for planning to install the Universal Storage Platform VM.
Responsibilities
Installation Planning Tasks
Installatio...
Page 12 - Responsibilities; Customer Responsibilities; You are responsible for:; Hitachi Data Systems Responsibilities; The Hitachi Data Systems account team is responsible for:
Responsibilities The responsibilities for installation planning are shared by the customer and the Hitachi Data Systems account team. The required installation planning tasks must be scheduled and completed to ensure successful and efficient installation of the Universal Storage Platform VM. Custome...
Page 13 - Installation Planning Tasks; Review the User and Reference Guide (MK-96RD635) to familiarize; Provide the customer-supplied hardware that is required for
Installation Planning Tasks The customer is responsible for performing the following tasks, with assistance as needed from the Hitachi Data Systems account team, to prepare for installation of the Universal Storage Platform VM storage system: 1. Read this document carefully to understand the install...
Page 14 - Installation Planning Checklist; Definition of terms:; Data center: The room at the customer site in which the Universal
Installation Planning Checklist Complete the checklist below (online or hardcopy) to verify that all installation requirements for the Universal Storage Platform VM have been met. Successful completion of this checklist (Yes is checked for all entries) will ensure smooth and efficient installation o...
Page 15 - I n s t a l l a t i o n P l a n n i n g C h e c k l i s t
I n s t a l l a t i o n P l a n n i n g C h e c k l i s t Yes No Safety Is the data center equipped to protect equipment from fire? Is the data center free of hazards (e.g., cables that obstruct access)? Delivery Is the receiving area adequate for equipment delivery and unloading? (overall height: 8...
Page 17 - Installation Requirements; Platform VM storage system.; verified to meet the applicable local regulations.
2 Installation Requirements 2-1 Hitachi Universal Storage Platform VM Installation Planning Guide Installation Requirements This chapter provides the installation requirements for the Universal Storage Platform VM storage system.
Safety Requirements
Delivery Requirements
Storage Requirements
...
Page 18 - Safety Requirements; Observe the following general safety requirements:
Safety Requirements The safety requirements for Universal Storage Platform VM installation are: • Safety regulations: The data center must comply with all applicable safety regulations, standards, and requirements. • Fire protection: The data center must have an operational fire protection system. •...
Page 19 - Delivery Requirements; See
Delivery Requirements The customer site must accommodate the delivery and movement of the equipment to the installation location in the data center. The delivery requirements for Universal Storage Platform VM installation are: • Dimensions: The loading bay, hallways, doors, elevators, and stairs mus...
Page 20 - Storage Requirements; Environmental Specifications for Storage; * For storage, the equipment should be packed with factory packing.
Storage Requirements If the delivered equipment needs to be stored after delivery and prior to installation, the storage location must meet the environmental requirements for the Universal Storage Platform VM (see Table 2-1). Table 2-1 Environmental Specifications for Storage Shipping & Storage*...
Page 21 - Facilities Requirements; Floor: The data center must have a tiled raised floor.; operation of the Universal Storage Platform VM.
Facilities Requirements The customer site must meet the following facilities requirements: • General: The data center must be fully operational (e.g., power, air conditioning, cabling, fire protection system). • Floor: The data center must have a tiled raised floor. • ESD: The data center must provi...
Page 22 - Physical Specifications and Requirements; Dimensions and Weight; Physical Overview of the Universal Storage Platform VM
Physical Specifications and Requirements Figure 2-1 shows a physical overview of the Universal Storage Platform VM. The physical specifications and requirements for the USP VM include: • Dimensions and Weight • Service Clearance, Floor Cutout, and Floor Load Rating Disk Chassis (DKU-R3) Disk Chassis...
Page 23 - REAR VIEW; TOP VIEW; Physical Dimensions: Single-Rack Configuration
Dimensions and Weight Figure 2-2 shows the dimensions of the single-rack configuration. Figure 2-3 shows the dimensions of the twin-rack configuration. Table 2-2 lists the dimension and weight specifications for the Universal Storage Platform VM components. REAR VIEW FRONT VIEW 2001 mm TOP VIEW 601 ...
Page 24 - Physical Dimensions: Twin-Rack Configuration
FRONT VIEW TOP VIEW 2001 mm 601 mm 601 mm 1046 mm TBD Figure 2-3 Physical Dimensions: Twin-Rack Configuration 2-8 Installation Requirements Hitachi Universal Storage Platform VM Installation Planning Guide
Page 25 - Component Specifications: Weight and Dimension
Table 2-2 Component Specifications: Weight and Dimension Dimension (mm) Model Number Weight (kg) Width Depth Height DKC615I-5 70 445 800 438 DKC-F615I-B2 80.5 445 647 522 DKC-F615I-SBX 13 445 800 84 DKC-F615I-LGAB 11 — — — DKC-F615I-PLUC 2.0 — — — DKC-F615I-PHUC 4.0 — — — DKC-F615I-PLEC 1.5 — — — DK...
Page 26 - Service Clearance, Floor Cutout, and Floor Load Rating; Floor Load Rating and Clearances: Single Rack; Floor Load Rating and Clearances: Two Racks
Service Clearance, Floor Cutout, and Floor Load Rating This section specifies the service clearance requirements (a + b) for the Universal Storage Platform VM storage system, based on the floor load rating and the clearance (c), and the required floor cutouts for cabling. • Figure 2-4 shows the serv...
Page 27 - Service Clearance and Floor Cutouts: Single Rack
(Unit : mm) Floor cutout area for cables Caster Screw jack Service clearance G Grid panel (over 450mm x 450mm) 601 Front G DKC615 a *1 B *1 195 65 125 65 835 63 90 74 61.5 457 482 601 c *1 3250 1050 1100 Front 1050.00 575 601 Rear DKC615 125 200 or more 355 482 215 62 125 1100 Figure 2-4 Service Cle...
Page 28 - Service Clearance and Floor Cutouts: Two Racks
(Unit: mm) 1220 G DKC615 a *1 b 195 125 65 835 655 63 90 61.5 74 457 482 585 Floor cutout area for cables Caster Screw jack Service clearance G Grid panel (over 450mm x 450mm) *1 215 150 195 215 G 482 585 DKC615 457 74 61.5 65 125 1100 150 655 835 1050 3250 90 63 1100 c *1 10* 2 1050 575 601 Rear Fr...
Page 29 - Power Specifications and Requirements; Power Specifications and Power Supplies; Figure 2-6 shows the locations of the power supplies.; Current Specifications
Power Specifications and Requirements This section describes the power specifications and requirements for the Universal Storage Platform VM storage system: • Power Specifications and Power Supplies • Breaker Configurations • Power Connection • Input Voltage and Input Frequency • Circuit Breakers an...
Page 30 - Power Supply Locations
Primary Rack PDU PDU DKU PS Power Cable (AC Input 1) Power Cable (AC Input 2) DKC PS11 PS12 PS21 PS22 CL1 CL2 PS31 PS30 × 15 DKU-R0 PS21 PS20 × 15 PS11 PS10 × 15 PS01 PS00 × 15 PS31 PS30 × 15 DKU-R1 PS21 PS20 × 15 PS11 PS10 × 15 PS01 PS00 × 15 Plugs for 30A Breakers USA: NEMA L6-30P International: I...
Page 31 - Breaker Configurations; Figure 2-7 Breaker Configurations for the Primary Rack; Breaker Configurations for the Secondary Rack
Breaker Configurations For both racks, AC power is supplied to each power distribution unit (PDU) from the breaker. Figure 2-7 and Figure 2-8 show the breaker configurations for the primary and secondary racks, respectively. DKC DKU-R1 DKU-R0 DKC DKU-R0 Configuration with one disk chassis (DKC-F615I...
Page 32 - Power Connection; Power connection through UPS. Figure 2-10 shows the power; Direct Power Connection
Power Connection The AC power input for the Universal Storage Platform VM has a duplex PDU structure. This duplex structure enables the entire rack to remain powered on in the event that power is removed from one of the two power distribution panels (PDPs). • Direct connection to power. Figure 2-9 s...
Page 33 - Power Connection through UPS
DKU-R2 DKU-R3 DKC DKU-R1 DKU-R0 AC Input Line Branch Distribution Box To UPS For the AC input power, connect one of the duplexes PDUs to the UPS and the other one to the PDP. UPS1 PDP2 PDP: Power Distribution Panel UPS2 PDP1 PDU (1 φ /20A) PDU (1 φ /20A) PDU (1 φ /20A) PDU (1 φ /20A) PDU (1 φ /20A) ...
Page 34 - Input Voltage and Input Frequency; Universal Storage Platform VM.; Input Voltage and Input Frequency Requirements; Circuit Breakers and Plugs; 2A and 250V and have two 16A circuit breakers with 20A trip values.
Input Voltage and Input Frequency Table 2-6 lists the input voltage and input frequency requirements for the Universal Storage Platform VM. Table 2-6 Input Voltage and Input Frequency Requirements Frequency Input Voltages (AC) Conditions Tolerance(%) 60Hz ±2Hz 200V, 208V or 230V 1 Phase 2 Wire + Gro...
Page 35 - Environmental Specifications and Requirements; Heat Output, Power Consumption, and Air Flow; Environmental Specifications
Environmental Specifications and Requirements The environmental specifications and requirements for the Universal Storage Platform VM include: • Temperature, Humidity, and Altitude • Heat Output, Power Consumption, and Air Flow • Loudness • Vibration and Shock Temperature, Humidity, and Altitude Tab...
Page 36 - Hitachi TagmaStore
Heat Output, Power Consumption, and Air Flow Table 2-8 lists the power consumption and heat output specifications and the air flow requirements for the Universal Storage Platform VM. These data generally apply to both 60-Hz and 50-Hz storage systems. The Universal Storage Platform VM requires less p...
Page 37 - Loudness; Platform VM storage system are:; Vibration and Shock; Vibration and Shock Tolerances
Loudness The acoustic emission values [loudness in dB(A)] for the Universal Storage Platform VM storage system are: Front/rear = 65 dB(A) Both sides = 65 dB(A) Vibration and Shock Table 2-9 lists the vibration and shock tolerance data for the Universal Storage Platform VM. The USP VM can be subjecte...
Page 38 - Operational Requirements; Table 2-10 FED Cable Length Requirements
Operational Requirements The operational requirements for the Universal Storage Platform VM include: • LAN connection (or RJ-11 analog phone line) for Hi-Track ® The Hi-Track maintenance support tool monitors the operation of the Universal Storage Platform VM, collects hardware status and error data...
Page 39 - Units and Unit Conversions
A Units and Unit Conversions A-1 Hitachi Universal Storage Platform VM Installation Planning Guide Units and Unit Conversions Table A-1 provides conversions for metric and standard (U.S.) units of measure associated with the Hitachi Universal Storage Platform VM storage system. For information on ph...