Goodman RT6100004R13 - Manual

Goodman RT6100004R13

Goodman RT6100004R13 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
17 Page 17
18 Page 18
19 Page 19
20 Page 20
21 Page 21
22 Page 22
23 Page 23
24 Page 24
25 Page 25
26 Page 26
27 Page 27
28 Page 28
29 Page 29
30 Page 30
31 Page 31
32 Page 32
33 Page 33
34 Page 34
35 Page 35
36 Page 36
37 Page 37
38 Page 38
39 Page 39
40 Page 40
41 Page 41
42 Page 42
43 Page 43
44 Page 44
45 Page 45
46 Page 46
47 Page 47
48 Page 48
49 Page 49
50 Page 50
51 Page 51
52 Page 52
53 Page 53
54 Page 54
55 Page 55
56 Page 56
57 Page 57
58 Page 58
59 Page 59
60 Page 60
61 Page 61
62 Page 62
63 Page 63
64 Page 64
65 Page 65
66 Page 66
67 Page 67
68 Page 68
69 Page 69
Page: / 69

Table of Contents:

  • Page 2 – IMPORTANT INFORMATION; REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE; IMPORTANT NOTICES FOR CONSUMERS AND SERVICERS; RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS; TABLE OF CONTENTS; WARNING
  • Page 3 – SAFE REFRIGERANT HANDLING; See Service Section S-17 for proper servicing.; Never purge refrigerant into an enclosed room or
  • Page 4 – PRODUCT IDENTIFICATION; Descri ptio n; S plit S ystem Air C onditioners R-22
  • Page 5 – Split System Air C onditioners R-22
  • Page 6 – Descripti on; Split System H eat Pumps R -22
  • Page 7 – Split S ystem H eat P umps R -22
  • Page 8 – De scription; Single Piece Air Handlers
  • Page 9 – Descrip tion; Single Piece Air H andl ers
  • Page 10 – MB R/MBE Air Handlers
  • Page 11 – PKF; E: Comm ercial Air Conditioner; ELECTRICAL :; Amana; EL ECT RICAL:
  • Page 12 – KF; E: Comm ercial Air Conditioner; KL
  • Page 13 – THIS NOMENCLATURE IS TO BE USED TRHOUGH JULY 2006
  • Page 14 – THIS NOMENCLATURE IS TO BE USED AFTER JULY 2006; All Airhandlers use; DIRECT DRIVE MOTORS; C: Ceiling Mount PSC Motor; REF RI GERANT CHARGE:
  • Page 15 – MODEL; MB; AIRFLO W DEL IVERED; PRO DUCT
  • Page 16 – ACCESSORIES
  • Page 18 – For Applications requiring; For Applications not requiring; EXPANSION VALVE KITS
  • Page 19 – FREEZE THERMOSTAT
  • Page 20 – COIL ACCESSORIES; HKR SERIES ELECTRIC HEAT KITS; ELECTRIC HEAT KIT APPLICATIONS
  • Page 21 – PRODUCT DESIGN; CONDENSING UNIT; Suction and Liquid Line Connections; Compressor. There are a number of; COILS AND BLOWER COILS
  • Page 23 – SYSTEM OPERATION; COOLING; HEATING; COOLING CYCLE
  • Page 26 – COOLING CYCLE - CONDENSING UNIT; In the cooling mode, the orifice is pushed into its
  • Page 27 – DESCRIPTION; , it recognizes this as a
  • Page 28 – TROUBLESHOOTING CHART; COOLING/HP ANALYSIS CHART
  • Page 29 – MBE & AEPF with Single Speed
  • Page 30 – SERVICING; REMOTE CONDENSING UNITS; ANTICIPATOR; THERMOSTAT WIRE SIZING CHART; S-3A THERMOSTAT AND WIRING; Line Voltage now present.; Indoor Blower Motor; Line Voltage now present.
  • Page 31 – Resistance Heaters; S-3B COOLING ANTICIPATOR; Troubleshooting Encoded Two Stage Cooling Thermostats Options
  • Page 32 – S-4 CHECKING TRANSFORMER; Discon nect ALL p ower before servicing.; S-5 CHECKING CYCLE PROTECTOR; S-6 CHECKING TIME DELAY RELAY; W A RN ING; Discon nect ALL power before servicing.; OHMMETER; TESTING COIL CIRCUIT
  • Page 33 – Remove the leads from the holding coil.; S-8 CHECKING CONTACTOR CONTACTS; DISCONNECT ELECTRICAL POWER SUPPLY.; Disconnect Electrical Power Supply:; Disconnect the wire leads from the terminal (T) side of the; If a no voltage reading is obtained - replace the contactor.; TESTING COMPRESSOR CONTACTOR; S-9 CHECKING FAN RELAY CONTACTS; Disconnect wires leads from terminals 2 and 4 of Fan
  • Page 34 – S-10 COPELAND COMFORT ALERTTM; See Diagnostic Table on
  • Page 35 – DIAGNOSTICS TABLE
  • Page 36 – HARD START KIT WIRING; S-15A RESISTANCE CHECK; Discharge capacitor and remove wire leads.; OHM M ET ER; TESTING CAPACITOR RESISTANCE; Set an ohmmeter on its highest ohm scale and connect; S-11 CHECKING LOSS OF CHARGE PROTECTOR; SCROLL COMPRESSOR MODELS
  • Page 37 – S-15B CAPACITANCE CHECK; VOLT M ET ER; TESTING CAPACITANCE; S-16A CHECKING FAN AND BLOWER MOTOR; Electronically Commutated Motor
  • Page 38 – Gnd; 6-PIN ECM HARNESS CONNECTOR; S-16C CHECKING ECM MOTOR WINDINGS; MBE MOTOR; MOTOR SPEED ADJUSTMENT
  • Page 39 – CHART CONTINUED ON NEXT PAGE
  • Page 40 – CHART CONTINUED FROM PREVIOUS PAGE
  • Page 41 – DIPSWITCH FUNCTIONS; CFM DELIVERY; Model; THERMOSTAT “FAN ONLY” MODE; Table 4; O N
  • Page 42 – HUMIDITY CONTROL; MOTORS; C L G N; High Voltage; MOTOR CONNECTIONS; S-17 CHECKING COMPRESSOR; S-17A RESISTANCE TEST
  • Page 43 – TESTING COMPRESSOR WINDINGS
  • Page 44 – COPELAND COMPRESSOR; Y E A R; Disconnect ALL power before servicing.; S-21 CHECKING REVERSING VALVE
  • Page 45 – Refer to the installation instruc-; On most digital/electronic thermostats, “W2” will
  • Page 46 – Heating Operation; On most digital/electronic thermostats, “W3” will; DENSERS; AEP* & MBE ELECTRONIC BLOWER TIME DELAY RELAY; SEQUENCE OF OPERATION
  • Page 47 – P U M P S
  • Page 48 – For the 3; heater elements to operate on a third
  • Page 49 – If other than a 240V power supply is used, refer to the; BTUH; BTUH CAPACITY CORRECTION FACTOR; TEMPERATURE RISE; The temperature rise table is for sea level installa-
  • Page 50 – S-61B CHECKING HEATER FUSE LINK; S-62 CHECKING HEATER ELEMENTS; S-100 REFRIGERATION REPAIR PRACTICE; DANGER; BRAZING MATERIALS; Copper to Copper Joints
  • Page 51 – EVACUATION
  • Page 52 – CAUTION; SYSTEM SUPERHEAT; S-104 CHECKING COMPRESSOR EFFICIENCY
  • Page 53 – S-105B THERMOSTATIC EXPANSION VALVE
  • Page 54 – THERMOSTATIC EXPANSION VALVES; CHECKING SUPERHEAT
  • Page 55 – Gauge Pressure; S-109 CHECKING SUBCOOLING
  • Page 56 – S-111 CAPILLARY TUBES/RESTRICTOR ORIFICES; Capillary Tubes/Orifice Assembly; S-112 CHECKING RESTRICTED LIQUID LINE
  • Page 57 – NOTICE; Suction Line Drier Clean-Up Method; S-120 REFRIGERANT PIPING
  • Page 58 – Vibration and Noise:; TABLE 10. CAPACITY MULTIPLIERS AS A FUNCTION OF; TABLE 11. LOSSES FROM SUCTION LINE ELBOWS; Installation Requirements; Fig 6. Evaporator unit with inverted vapor loop
  • Page 59 – S-122 REVERSING VALVE REPLACEMENT
  • Page 60 – S-203 AIR HANDLER EXTERNAL STATIC; TOTAL EXTERNAL STATIC; S-204 COIL STATIC PRESSURE DROP; STATIC PRESSURE DROP
  • Page 61 – ACCESSORIES WIRING DIAGRAMS; ALL FUEL SYSTEM CONTROL BOARD - AFE18-60A
  • Page 62 – 0kw and Below, One Stage Electric Heat; 5kw and Above, Two Stage Electric Heat
  • Page 64 – Typical Wiring Schematic ADPF, ARPF, ARUF with Electric Heat.
  • Page 65 – Typical Wiring Schematic MBR Blower with Electric Heat.
  • Page 66 – Typical Wiring Schematic AEPF with Electric Heat.
  • Page 67 – Blower Section; HKR Heat Kit; Typical Wiring Schematic MBE Blower with Electric Heat.
Loading the manual

This manual is to be used by qualified, professionally trained HVAC
technicians only. Goodman does not assume any responsibility for
property damage or personal injury due to improper service
procedures or services performed by an unqualified person.

Split System Air Conditioners,

Split System Heat Pumps

with R-22 Refrigerant

Blowers, Coils, & Accessories

Service Instructions

Copyright

© 2005 - 2009 Goodman Manufac

turing Company, L.P.

RT6100004r13

May 2009

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - IMPORTANT INFORMATION; REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE; IMPORTANT NOTICES FOR CONSUMERS AND SERVICERS; RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS; TABLE OF CONTENTS; WARNING

IMPORTANT INFORMATION Pride and workmanship go into every product to provide our customers with quality products. It is possible, however,that during its lifetime a product may require service. Products should be serviced only by a qualified service technicianwho is familiar with the safety procedur...

Page 3 - SAFE REFRIGERANT HANDLING; See Service Section S-17 for proper servicing.; Never purge refrigerant into an enclosed room or

3 The successful development of hermetically sealed refrigera-tion compressors has completely sealed the compressor'smoving parts and electric motor inside a common housing,minimizing refrigerant leaks and the hazards sometimesassociated with moving belts, pulleys or couplings. Fundamental to the de...

Page 4 - PRODUCT IDENTIFICATION; Descri ptio n; S plit S ystem Air C onditioners R-22

PRODUCT IDENTIFICATION 4 M odel # Descri ptio n G SC13018-241AA G oodman® Brand S plit C ondenser 13 Seer c ondensing units. Initial release. 26" chassis G SC13036-481AA G oodman® Brand S plit C ondenser 13 Seer c ondensing units. Initial release. 29" chassis GSC13036,48*AA G oodman® Brand S...