Generac MPSG350 - Manual
Generac MPSG350 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Power Manager; Generator Controller; Power Manager System Control; Sequence of Operations; Each Generator will start on its own.; System Configuration
- Page 3 – Combinations; 08 Volt Parallel Wye Network; Rated Amps; TOTAL SYSTEM PARAMETERS; Alternator Models
- Page 4 – PMSC Power Manager System Control; GENERAC POWER SYSTEMS, INC.; MPSG350; GENERAC
Standby Power Rating Prime Power Rating
350 KW 60 Hz 280 KW 60 Hz
n
The Generac Modular Paralleling system utilizes
multiple small generators in a side by side parallel
arrangement to achieve a larger combined power
output.
n
The proven 13.3 liter Generac generators can be
combined up to 10 units to provide from 300 kW to 1
megawatts of reliable power.
n
Paralleling System Features. The paralleling function is
controlled by Generac’s field proven Power Manager
Control utilizing contractor switching technology
resulting in cost effective reliable paralleling. The MPS
control system provides automatic synchronization,
adjustable load sharing between generators, reverse
power protection and load shedding contacts.
n
The optional cable interconnect cabinet is furnished with
bus bar and lugs to allow easy cabling between the
multiple gensets. Recommended for 3 or more gensets.
n
The Generac “Power Manger Generator controller”
provides complete engine monitoring and control along
with alarm function and communication ability via a
RS232 with a modem link to Generac’s Genlink
software or Modbus control. A RS485 link is also
available.
n
Flexibility. The Modular Power systems flexibility allows
for a wide variety of configurations, including single or
multiple automatic transfer switch arrangements roof
application where better weight distribution is required
and areas with specific height or depth limitations.
Since MPS gensets need not be located together, space
can be utilized wherever it is available. Smaller units
are also easier to transport and place on the jobsite.
n
Redundancy. N+1 means greater reliability with MPS .
Backup power during scheduled maintenance.
Simplified service which reduces maintenance costs.
n
Single source service response from Generac’s dealer
network provides parts and service support for the entire
unit. You are never on your own when you own a
Generac Power System
GEN
Diesel Generator
Circuit
Breaker
Contactor
Contactor
Diesel Generator
Circuit
Breaker
GEN
Transfer Sw
W/ Integral
Control
UTILITY
Distribution
Cab
Contactor
Diesel Generator
Contactor
Circuit
Breaker
Circuit
Breaker
Diesel Generator
GEN
GEN
UTILITY
ATS
UTILITY
ATS
Distribution
C a b
Distribution
Cab
PMSC
Controller
Cabinet
Control Wires
Power Manager Integrated Controller Layout Power Manager System Controller Layout
FEATURES
Modular Power
System (MPS)
Powered with Generac’s 13.3 Natural Gas Engine
MPSG350
350 kW
®
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
Modular Paralleling SystemMPSG 350 System Description The Generac control system consists of the Power Manager™System Controller (PM-SC) or the Power Manager IntegratedController ()PM-IC) along with the Power Manager GeneratorController (PM- GC). For single transfer switch installations withthe Gene...
350 kW 437.5 kVA 15% 20% 25% 30% 35% % of Rated Load 1,209 2,329 3,429 4,467 Heat Rejection to Coolant( Full Load ) Coolant Capacity (total) Max air temp to radiator º F (derates apply) Max ambient temperature º F (derates apply) Flow at Rated Power ( cfm) 0.5 inches H2O Combinations 581 711 784 Ins...
INTERCONNECTION DIAGRAMPMIC Power Manager Integrated Control PMSC Power Manager System Control DISTRIBUTED BY: GENERAC POWER SYSTEMS, INC. MPSG350 The PM-SC can control 3 transfer switches and any number ofslave switches. The main connection box would be configured forthe size and number of wires fo...