Page 2 - Contents
3 2 Contents Important Notice 4 Warnings 4 What’s Included 5 Certifications 5 Description 6 Features Specifications 8 Safety Information 9 General Environmental Personal Protection Vacuum Pump Protection Setup Grounding Instructions Tech Tips 14 General Cold Weather Starts Setup Operation 16 RunQuic...
Page 3 - Important Notice; What’s Included; WARNINGS
5 4 Important Notice This is not a consumer machine Only qualified personnel trained in service and installation of A/C and/or refrigeration equipment shall use this vacuum pump This vacuum pump is used for evacuating (drying) refrigerant lines Fieldpiece model MR45 is available for recovering refri...
Page 4 - Features; Description
7 6 Features • 10CFM (VPX7), 8CFM (VP87), 6CFM (VP67) • A2L Certified • RunQuick® Oil Change System - Easy View Window and Oil Backlight - Change Oil Quickly, Even with the Pump Running - Extra Oil Bottle Storage - Elevated Oil Drain Ball Valve - Wide Mouth Fill Port - Oil Bottle Cap Storage - Preci...
Page 5 - Specifications; Safety Information; General
9 8 Specifications Flow Rate: 10CFM (VPX7), 8CFM (VP87), 6CFM (VP67) Oil Capacity: 8oz (237mL) Oil Compatibility: Fieldpiece Vacuum Pump Oil (Highly refined and optimized for proper sealing and lubrication) Fieldpiece part numbers: OIL8X3, OIL32, OIL128 Oil Backlight: Blue LED Oil Drain: Ball valve ...
Page 8 - Tech Tips
15 14 Tech Tips General 1. Vacuum pumps are not refrigerant recovery machines and should not be used for recovering refrigerant. 2. Purge the A/C system with a few psi of dry nitrogen before evacuation to pre-dry the system. This extra step actually saves time overall because it quickly removes a gr...
Page 9 - Operation
Remote Exhaust Cap Power Cord Storage Wrap 4 Input Ports Extra Oil Bottle Storage Gas Ballast Valve (Open) Motor Power Switch (OFF) IEC Power Cord Inlet and Lock Power Cord Storage Oil Tank Cap Oil Drain Valve (CLOSED) Backlit Oil Window and Tank Access (4 Screws) 17 16 Operation
Page 10 - RunQuick® Oil Change System
19 18 RunQuick® Oil Change System The only way to create a deep vacuum is to evacuate with fresh oil, especially at the end of the job The RunQuick® oil change system makes this old chore a breeze Easy View Window and Oil Backlight There are a few signs that remind you to change your oil. The visual...
Page 11 - Evacuation with a 4 Port Manifold
Vapor Schrader Valve Core Removal Tools (optional) 4 Port Manifold with Vacuum Gauge Liquid 21 20 Evacuation with a 4 Port Manifold This is the most common evacuation method Read the tech tips (page 12) for optimum gauge placement and variations to reduce recovery times 1. Always fill with fresh Fie...
Page 12 - Evacuation with a 3 Port Manifold
Vapor Schrader Valve Core Removal Tools (optional) 3 Port Manifold with Vacuum Gauge Hose with Shut-off Valve Liquid 23 22 Evacuation with a 3 Port Manifold This is a common, but less than ideal evacuation method Read the tech tips (page 12) for optimum gauge placement and variations to reduce recov...
Page 13 - Direct Evacuation
Vapor Schrader Valve Core Removal Tools Vacuum Gauge Liquid 25 24 Direct Evacuation This is usually the fastest evacuation method Read the tech tips (page 12) for optimum gauge placement and variations to reduce recovery times 1. Always fill with fresh Fieldpiece Vacuum Pump Oil (page 24). Running t...
Page 14 - Oil Change Procedure; Dynamic Vacuum Measurement; Remote Exhaust
27 26 Oil Change Procedure Changing oil is easy to perform Start each job with fresh oil Change as needed during the job It is recommended to drain the oil during storage Always dispose of oil according to local jurisdiction ADDING FRESH OIL 1. Ensure the drain valve is closed (horizontal).2. Unscre...
Page 15 - Gas Ballast Valve Switch; LED Indicators
29 28 Gas Ballast Valve Switch Much of the air and moisture in a system are removed before reaching 3000 microns For wet systems, you should open the gas ballast during this initial pull down Doing so helps the pump run smoothly and keeps the oil in good condition for when you need it most -- toward...
Page 16 - Maintenance; Oil Window Cleaning
31 30 Maintenance General Wipe with damp cloth to clean the exterior Do not use solvents Storage Empty or replace oil at the end of every job Don’t leave old oil in the machine Store the pump and oil in dry clean areas for longest life Oil can lose its sealing proper ties if lef t uncovered Keep oil...
Page 17 - Troubleshooting
33 32 Troubleshooting Appropriate vacuum is never reached. Ensure the gas ballast is closed (vertical position, yellow LED off ). Ensure oil is fresh. Ensure oil level is between MIN and MAX lines. Ensure all port caps are closed and have working seals. Limit amount of connections. Check for leaks a...
Page 18 - Limited Warranty; Supplier’s Declaration of Conformity
35 34 Limited Warranty This machine is warranted against defects in material or workmanship for one year from date of purchase from an authorized Fieldpiece dealer Fieldpiece will replace or repair the defective unit, at its option, subject to verification of the defect This warrant y does not apply...