www.fisherregulators.com

D101644XUS2

Installation Guide

English – June 2011

Type 1190

Installation

!

WARNING

Only qualified personnel should install or service

a regulator. Regulators should be installed,

operated, and maintained in accordance

with international and applicable codes and

regulations, and Emerson Process Management

Regulator Technologies, Inc. instructions.
If the regulator vents fluid or a leak develops in

the system, it indicates that service is required.

Failure to take the regulator out of service

immediately may create a hazardous condition.
Personal injury, equipment damage, or leakage

due to escaping fluid or bursting of pressure-

containing parts may result if this regulator

is overpressured or is installed where service

conditions could exceed the limits given in the

Specifications section, or where conditions

exceed any ratings of the adjacent piping or

piping connections.
To avoid such injury or damage, provide

pressure-relieving or pressure-limiting devices

(as required by the appropriate code, regulation,

or standard) to prevent service conditions from

exceeding limits.
Additionally, physical damage to the regulator

could result in personal injury and property

damage due to escaping fluid. To avoid such

injury and damage, install the regulator in a

safe location.

Clean out all pipelines before installation of the regulator and

check to be sure the regulator has not been damaged or has

collected foreign material during shipping. For NPT bodies,

apply pipe compound to the external pipe threads. For flanged

bodies, use suitable line gaskets and approved piping and bolting

practices. Install the regulator in any position desired, unless

otherwise specified, but be sure flow through the body is in the

direction indicated by the arrow on the body.

Note

It is important that the regulator be installed so that

the vent hole in the spring case is unobstructed at

all times. For outdoor installations, the regulator

should be located away from vehicular traffic and

positioned so that water, ice, and other foreign

materials cannot enter the spring case through the

vent. Avoid placing the regulator beneath eaves or

downspouts, and be sure it is above the probable

snow level.

Introduction

This installation guide provides instructions for installation, startup,

and adjustment. To receive a copy of the instruction manual, contact

your local Sales Office or view a copy at www.fisherregulators.

com. For further information refer to: Type 1190 Instruction Manual,
form 5307, D101644X012.

P.E.D. Categories

This product may be used as a safety accessory with pressure

equipment in the following Pressure Equipment Directive 97/23/

EC categories. It may also be used outside of the Pressure

Equipment Directive using sound engineering practice (SEP) per

table below.

PRODUCT SIZES

CATEGORIES

FLUID

TYPE

DN

NPS

25

1

SEP

1

50, 80, 100, 150

2, 3, 4, 6

II

Specifications

Body Size and End Connection Styles

See Table 1

Main Valve Maximum Inlet Pressure

(1)

27,6 bar / 400 psig or body rating limit whichever

is lower. DN 150 / NPS 6 main valve is limited to

19,0 bar / 275 psig and the DN 200 x 150 /

NPS 8 x 6 is limited to 16,0 bar / 232 psig for PED

Category II.

Maximum Operating Inlet Pressure

(1)

13,8 bar / 200 psig with cast iron construction

or 20,7 bar / 300 psig with a steel or stainless

steel construction.

Maximum Outlet (Casing) Pressure

(1)

5,2 bar / 75 psig

Outlet Pressure Ranges

(1)

See Table 2

Maximum and Minimum Differential Pressures

(1)

See Table 3

Proof Test Pressure

All Pressure Retaining Components have been

proof tested per Directive 97/23/EC - Annex 1,

Section 7.4.

Maximum Temperature Capabilities

(1)

Nitrile (NBR):

-29° to 82°C / -20° to 180°F

Fluorocarbon (FKM):

4° to 149°C / 40° to 300°F

Ethylenepropylene (EPDM):

-29° to 149°C / -20° to 300°F

Perfluoroelastomer (FFKM):

-29° to 149°C / -20° to 300°F

1. The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.

BODY SIZES

END CONNECTION STYLES

DN

NPS

Cast Iron

WCC Steel or CF8M Stainless Steel

25, 50

1, 2

NPT, CL125 FF, or CL250 RF flanged

NPT, SWE, BWE, CL150 RF, CL300 RF,

CL600 RF, or PN 16/25/40 flanged

80, 100, 150

3, 4, 6

CL125 FF, or CL250 RF flanged

BWE, CL150 RF, CL300 RF, CL600 RF, or PN 16 flanged

200 x 150,

300 x 150

8 x 6,

12 x 6

- - - -

BWE, CL150 RF, CL300 RF, CL600 RF, or PN 25 flanged

Table 1.

Body Sizes and End Connection Styles

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - To avoid personal injury resulting from sudden

2 167D Series Overpressure Protection The recommended pressure limitations are stamped on the regulator nameplate. Some type of overpressure protection is needed if the actual inlet pressure exceeds the maximum operating outlet pressure rating. Overpressure protection should also be provided if the ...

Page 3 - Parts List; Type EGR Parts List; Type Y191A Parts List

3 167D Series Parts List Type EGR Parts List Key Description 1 Valve Body 2 Body Flange 3 Cap Screw 4 Gasket 5 Lower Indicator Fitting 6 O-Ring Retainer 7 Indicator Stem O-Ring 8 Indicator Hex Nut 9 Spring 10 Travel Indicator Stem 11 Cage 12 Port Seal 13 Seat Ring 14 Piston Ring 15 Upper Seal 16 Val...

Page 4 - Type 95H Parts List; Type 95H Supply Pressure Regulator

The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls, Inc., a business of Emerson Process Management. The contents of this publication are presented for informational purposes ...