Installation Guide
English – June 2011
Type 1190
Installation
!
WARNING
Only qualified personnel should install or service
a regulator. Regulators should be installed,
operated, and maintained in accordance
with international and applicable codes and
regulations, and Emerson Process Management
Regulator Technologies, Inc. instructions.
If the regulator vents fluid or a leak develops in
the system, it indicates that service is required.
Failure to take the regulator out of service
immediately may create a hazardous condition.
Personal injury, equipment damage, or leakage
due to escaping fluid or bursting of pressure-
containing parts may result if this regulator
is overpressured or is installed where service
conditions could exceed the limits given in the
Specifications section, or where conditions
exceed any ratings of the adjacent piping or
piping connections.
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting devices
(as required by the appropriate code, regulation,
or standard) to prevent service conditions from
exceeding limits.
Additionally, physical damage to the regulator
could result in personal injury and property
damage due to escaping fluid. To avoid such
injury and damage, install the regulator in a
safe location.
Clean out all pipelines before installation of the regulator and
check to be sure the regulator has not been damaged or has
collected foreign material during shipping. For NPT bodies,
apply pipe compound to the external pipe threads. For flanged
bodies, use suitable line gaskets and approved piping and bolting
practices. Install the regulator in any position desired, unless
otherwise specified, but be sure flow through the body is in the
direction indicated by the arrow on the body.
Note
It is important that the regulator be installed so that
the vent hole in the spring case is unobstructed at
all times. For outdoor installations, the regulator
should be located away from vehicular traffic and
positioned so that water, ice, and other foreign
materials cannot enter the spring case through the
vent. Avoid placing the regulator beneath eaves or
downspouts, and be sure it is above the probable
snow level.
Introduction
This installation guide provides instructions for installation, startup,
and adjustment. To receive a copy of the instruction manual, contact
your local Sales Office or view a copy at www.fisherregulators.
com. For further information refer to: Type 1190 Instruction Manual,
form 5307, D101644X012.
P.E.D. Categories
This product may be used as a safety accessory with pressure
equipment in the following Pressure Equipment Directive 97/23/
EC categories. It may also be used outside of the Pressure
Equipment Directive using sound engineering practice (SEP) per
table below.
PRODUCT SIZES
CATEGORIES
FLUID
TYPE
DN
NPS
25
1
SEP
1
50, 80, 100, 150
2, 3, 4, 6
II
Specifications
Body Size and End Connection Styles
See Table 1
Main Valve Maximum Inlet Pressure
(1)
27,6 bar / 400 psig or body rating limit whichever
is lower. DN 150 / NPS 6 main valve is limited to
19,0 bar / 275 psig and the DN 200 x 150 /
NPS 8 x 6 is limited to 16,0 bar / 232 psig for PED
Category II.
Maximum Operating Inlet Pressure
(1)
13,8 bar / 200 psig with cast iron construction
or 20,7 bar / 300 psig with a steel or stainless
steel construction.
Maximum Outlet (Casing) Pressure
(1)
5,2 bar / 75 psig
Outlet Pressure Ranges
(1)
See Table 2
Maximum and Minimum Differential Pressures
(1)
See Table 3
Proof Test Pressure
All Pressure Retaining Components have been
proof tested per Directive 97/23/EC - Annex 1,
Section 7.4.
Maximum Temperature Capabilities
(1)
Nitrile (NBR):
-29° to 82°C / -20° to 180°F
Fluorocarbon (FKM):
4° to 149°C / 40° to 300°F
Ethylenepropylene (EPDM):
-29° to 149°C / -20° to 300°F
Perfluoroelastomer (FFKM):
-29° to 149°C / -20° to 300°F
1. The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.
BODY SIZES
END CONNECTION STYLES
DN
NPS
Cast Iron
WCC Steel or CF8M Stainless Steel
25, 50
1, 2
NPT, CL125 FF, or CL250 RF flanged
NPT, SWE, BWE, CL150 RF, CL300 RF,
CL600 RF, or PN 16/25/40 flanged
80, 100, 150
3, 4, 6
CL125 FF, or CL250 RF flanged
BWE, CL150 RF, CL300 RF, CL600 RF, or PN 16 flanged
200 x 150,
300 x 150
8 x 6,
12 x 6
- - - -
BWE, CL150 RF, CL300 RF, CL600 RF, or PN 25 flanged
Table 1.
Body Sizes and End Connection Styles
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
2 167D Series Overpressure Protection The recommended pressure limitations are stamped on the regulator nameplate. Some type of overpressure protection is needed if the actual inlet pressure exceeds the maximum operating outlet pressure rating. Overpressure protection should also be provided if the ...
3 167D Series Parts List Type EGR Parts List Key Description 1 Valve Body 2 Body Flange 3 Cap Screw 4 Gasket 5 Lower Indicator Fitting 6 O-Ring Retainer 7 Indicator Stem O-Ring 8 Indicator Hex Nut 9 Spring 10 Travel Indicator Stem 11 Cage 12 Port Seal 13 Seat Ring 14 Piston Ring 15 Upper Seal 16 Val...
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls, Inc., a business of Emerson Process Management. The contents of this publication are presented for informational purposes ...