SL-31080 Product Specification / Installation Sheet
page 1
6/03 (Rev. 0)
T
EMPERATURE
/ H
UMIDITY
T
RANSMITTER
- W
ALL
(4-20
M
A)
Description
The THW420 combination
temperature / humidity transmitter
is designed to meet applications
that require local indication of both
temperature and humidity in a
single, aesthetically pleasing
enclosure.
This device incorporates a 10K ohm
(
Ω
) platinum RTD. The transmitter
requires 24 VDC. The sensor provides an
accurate and predictable four-wire, 4-20 mA
output signal for temperature and a second
4-20 mA output signal for humidity.
Dimensions
Specifications
Termination
The THW420 transmitter must be powered from a
24 VDC supply. The combination temperature/
humidity sensor is terminated as follows:
• The
humidity transmitter
requires a three-wire
termination for the 4-20mA output using 24 VDC.
• The
temperature sensor
also requires a three-
wire termination. In most cases, it obtains power
from the analog input to which it is connected and
no external power is required.
Though interference from external sources is not a
major problem with current transmitters, Liebert
recommends separating the wiring from line voltage
wiring and from wiring used to supply highly induc-
tive loads such as motors, generators and coils. Lie-
bert also recommends making power connections
with twisted pair wire of at least 22 AWG and crimp-
type connectors.
Ordering Information
Output
4 to 20 mA
Sensor
10K
Ω
platinum RTD
Supply Voltage
24 VDC
Tolerance of Resistance
(Accuracy)
±1.5°F (±0.83°C)
±2% RH (from 15 to 95% RH)
Response Time
20 seconds for a 63% step
Environmental Operating
Range (Transmitter)
45°F to 96°F; 0 to 100% RH
(7°C to 35°C); 0 to 100% RH
4.5"
(1143mm)
2.25"
(572mm)
2.75"
(699mm)
0.95"
(241mm)
0.75"
(191mm)
FRONT
VIEW
SIDE
VIEW
TOP VIEW
Wall
!
CAUTION
Liebert recommends wiring the sensor
WITHOUT power applied because
accidental arcing may damage the product
and will void the warranty.
X
U3
Terminations
+24VDC should be
used at all times
SW2 OUTPUT SELECT
ON
0-5V
0-5V
0-5V
CAL
RUN
RESIST.
4-20ma
4-20ma
SW2
C9
Gn
d
V+
Ch1
Ch2
J2
J3
DISPLAY CYCLE
IN SECONDS
10
3
T
POT1
20
H
Ch
3
CA
L
Te
m
p
Te
m
p
R1
9
T&B
SWITCH
Short
Norm
Open
SW1
RTH1 RTH2
J1
%RH
Ch3
Ch2
Ch1
Building Automation
Products, Inc.
Copyright 2000
REV. 101600
XCOMBO T&B
4-20 mA
Input #1
Ground
4-20 mA
Input #2
+
-
+
-
Controller
To GND (common)
of controller*
From +24VDC
of controller or
power supply
To controller’s
analog input
(humidity signal,
4-20mA)
To controller’s
analog input
(temperature signal,
4-20mA)
* NOTE:
The GND (common)
terminal is common
between the Power
and Sensor
Quantity
Part #
Description
THW420
Combination Temperature / Humidity Transmitter Wall 4-20 mA @ 45°F to 96°F and 0 to 100% RH
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.