Specification for SiteI/O 10/0
DESCRIPTION:
The SiteI/O 10/0 is part of the SiteI/O-Line, which allows a complete SiteScan
monitoring/control system to be built a piece at a time. It is a 32 bit microprocessor-based device
designed to monitor up to ten analog, digital, and/or dry contact type signals. Individual hardware
jumpers set signal-type selections. Screw terminal blocks are provided to terminate power,
communication, and input signal wiring.
DIMENSIONS:
Module:
7.5” H x 11.3125” W x 2.75” D
19.05 cm H x 28.73 cm W x 7 cm D
Enclosure:
20" H x 18" W x 2.87" D
(Painted Steel)
508mm x 457.2mm x 72.89mm
See Enclosure Diagrams for mounting options
.
POWER:
24VAC
±
10%, 50-60 Hz., 20 VA power consumption
(120/24VAC 40VA Transformer available)
INPUTS:
Ten universal inputs, configurable for 0-5VDC, 0-20mA, or thermistor.
ENVIRONMENTAL
OPERATING RANGE:
0
°
to 130
°
F (-17.8
°
to 54.4
°
C), 10 to 90% relative humidity, non-condensing
COMMUNICATION:
One (1) CMnet EIA-485 Port - Control Module network screw terminals
Switch selectable baud rates ARC156 / 9600 or 38.4bps
Recommended wire is: MAGNUM Cable pn A3-ARC-156-2
(10) Analog and/or Digital - screw terminals
Jumper Selectable inputs
Thermistor - 10k ohm @ 77
°
F, 25
°
C
0 to 5 VDC - 10k ohm max source impedance
4 to 20mA - 24VDC loop power, 250 ohm input
Dry Contact - 0.5mA sense current
MEMORY:
1 MB Flash Memory, 1 MB Non-volatile battery backed RAM.
PROTECTION:
Voltage, current, and ESD protection on incoming power.
BATTERY:
Seven-year lithium battery provides a minimum of 10,000 hours of data
retention during power outages.
Liebert Corporation
Page 1 of 6 SL-28077 Rev.4; 7/03
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Emerson SiteI/O-Line
Summary
Specification for SiteI/O 10/0 DIAGNOSTIC LED's: Power: Indicates power on condition Tx: Indicates data transmitted on the CMnet Rx: In dicates data received on the CMnet Error: Indicates an error within the SiteI/O 10/0 Run: Indicates operating condition of the SiteI/O 10/0 LISTED BY: UL 916 (PAZX)...
Specification for SiteI/O 10/0 INPUT WIRING DIAGRAM P W R O U T G N D 0 - 5 V D C D R Y C O N T A C T 3 W I R E 4 - 2 0 m A 4 W I R E 4 - 2 0 m A I S O L A T E D D C P O W E R S U P P L Y P W R O U T G N D P W R O U T + G N D O U T - O U T + O U T - U n i v e r s a l I n p u t M o d e S e l e c t V ...
Specification for SiteI/O 10/0 COMMUNICATIONS WIRING DIAGRAM N e t - N e t + S h i e l d N e t - N e t + C M n e t 18-24 ga Twisted - Pair, Shielded, Low Impedance, Low CapacitanceRecommended wire is: Magnum Cable A3-ARC-156-2 ENLOSURE DIAGRAMS Liebert Corporation Page 4 of 6 SL-28077 Rev.4; 7/03