Page 3 - TABLE OF CONTENTS
i TABLE OF CONTENTS I MPORTANT S AFETY I NSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.0 G ENERAL S YSTEM I NFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.1 General Information ....
Page 4 - ii; YSTEM
ii 5.0 S YSTEM O VERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 5.1 Detailed System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 5.1.1 System Module Description...
Page 5 - iii; AINTENANCE
iii 6.4 Menu Tree and Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 6.4.1 Screen Tree Menu Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 6.4.2 Navigation and Ope...
Page 6 - iv; UPS I; Liebert FS Configuration - Single Liebert FS on Liebert
iv A PPENDIX A.0 UPS I NTERCONNECTION K ITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Appendix A.1 Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Appendix A.1.1 General Wiring Considerations ....
Page 7 - AC P
v Appendix B.3 DCM Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Appendix B.3.1 Logging into the DCM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 Appendix B.3.2 Status and...
Page 8 - FIGURES
vi FIGURES Figure 1 Liebert FS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Figure 2 Single Liebert FS unit or multiple Liebert FS units integrated into a UPS system. . . . . . . . . . . . 5 Figure 3 Lie...
Page 9 - vii
vii Figure 54 Control panel view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Figure 55 Main screen functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 10 - viii
viii Figure 109 Networks view, turn off DHCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102Figure 110 Networks view, edit settings (service level). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102Figure 1...
Page 11 - ix; TABLES
ix Figure 157 Multiple Liebert FS+DC units operating with a UPS in conjunction with batteries . . . . . . . . . 151Figure 158 A single Liebert FS unit operating with a UPS and without batteries attached to the DC bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 13 - SAVE THESE INSTRUCTIONS; WARNING
1 I MPORTANT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and mainte- nance of your Liebert FS. ! WARNING The installation of the Liebert FS must comply with applicable national, federal, state and local codes. ...
Page 14 - Safety Precautions
2 Safety Precautions Read this manual thoroughly, paying special attention to the sections that apply to you, before work- ing with the Liebert FS.Under typical operation and with all cabinet doors closed, only normal safety precautions are neces- sary. The area around the Liebert FS should be kept ...
Page 15 - General System Information; ENERAL; General Information; provided herein may void your warranty.; Table 1
General System Information 3 1.0 G ENERAL S YSTEM I NFORMATION 1.1 General Information 1.1.1 Safety Considerations Read and follow the instructions in this manual before interacting with the system. This document contains important information and instructions for your Liebert FS. All procedures def...
Page 16 - General System Description; Figure 1; and
General System Information 4 1.2 General System Description The Liebert FS is a flywheel energy storage system, a mechanical battery that stores energy in the form of a rotating mass. This energy is immediately convertible to useful electric power.The Liebert FS is available with a wide performance ...
Page 17 - Backup
General System Information 5 Figure 2 Single Liebert FS unit or multiple Liebert FS units integrated into a UPS system Figure 3 Liebert FS unit(s) integrated into UPS system for ride-through to backup generator EMERSO N Network Power Lieber t EMERSO N Net work Power Lieber t Loads UPS Block Diagram ...
Page 18 - Figure 4; summarizes the technical specifications of the Liebert FS.; Technical specifications on page 148; Rated Power Delivery; Dependent upon the duration required; Figure 5
General System Information 6 Figure 4 One or more Liebert FS units in parallel with one or more battery strings, battery cabinets or batteries in racks 1.2.1 General Specifications Table 2 summarizes the technical specifications of the Liebert FS. For more-detailed technical specifications, refer to...
Page 19 - age, until the stored energy is depleted. See; for a graphic representation of the performance; Key Technological Features
General System Information 7 1.2.2 Features and Benefits The Liebert FS provides clean constant DC output to the DC bus, at the user-selected, regulated volt- age, until the stored energy is depleted. See Figure 5 for a graphic representation of the performance power and duration curves of single an...
Page 20 - kWb = Refers to Kilowatts on the DC bus of the UPS system
General System Information 8 For distribution in Europe, the Liebert FS is CE-marked and meets the applicable requirements of the following European directives: “Low Voltage Directive” 73/23/EEC and its amendments by the directive 93/68/EEC;“Machinery Directive” 98/037/EEC and its amendments by the ...
Page 21 - through duration (see; Figure 7; ). One or more Liebert FS units may also be connected in parallel with
General System Information 9 Figure 6 Integrating a single Liebert FS unit into a UPS system Several Liebert FS units can be put in parallel to achieve higher power output and higher ride- through duration (see Figure 7 ). One or more Liebert FS units may also be connected in parallel with a UPS bat...
Page 22 - Site Preparation; ITE; ments are to properly:; System Location; Choose a location for the Liebert FS that offers:; Environmental Considerations; CAUTION; installing the Liebert FS.; NOTE; All drawings referred to in this section are in
Site Preparation 10 2.0 S ITE P REPARATION Site preparation for the Liebert FS is minimal. If a UPS system is already installed, the only require- ments are to properly: • Place the unit in relation to walls, ceiling and other equipment and• Fasten the unit to the floor. 2.1 System Location Choose a...
Page 23 - Flooring Requirements; contact load at; Electrical Considerations; include the required safety factors.
Site Preparation 11 2.3 Flooring Requirements 2.3.1 Floor Loading The Liebert FS should be mounted on a finished surface, such as concrete, block, brick or wood. The floor must be strong enough to support the equipment load and suitable for installation of an anchor- ing kit with vertical floor load...
Page 24 - Power Connections; Auxiliary Backup AC Power Supply; Remote Monitoring Connections—Optional
Site Preparation 12 2.4.2 Status/Control Connections Site preparation for Status/Control connections vary according to the type of UPS interconnection kit provided with your Liebert FS.Liebert recommends making Status/Control connections on the UPS system side.For details, refer to 4.2.3 - Status/Co...
Page 25 - Unloading and Unpacking; NLOADING; Inspection Before Removal From the Truck; While the Liebert FS shipping package is still on the truck:; Unloading; The FS as shipped (see; Figure 8; Do not attempt to install the system if damage is apparent.; Do not tilt the Liebert FS
Unloading and Unpacking 13 3.0 U NLOADING AND U NPACKING 3.1 Inspection Before Removal From the Truck While the Liebert FS shipping package is still on the truck: • Inspect the equipment and shipping container(s) for any signs of damage or mishandling. Check also if the shock and tilt gauges (instal...
Page 27 - Use a forklift to remove the cabinet from the shipping pallet.; Figure 10 Lifting the Liebert FS cabinet; the pocket inside the cabinet door (see; Table 1 - System information; Do not attempt to install the system if there is any damage.
Unloading and Unpacking 15 5. Use a forklift to remove the cabinet from the shipping pallet. To lift the Liebert FS, the forks should be inserted between the caster wheel assemblies (see Figure 10 ). Forks must be extended to the full depth of the cabinet—at least 6 ft. (2m) fork length—to properly ...
Page 28 - Positioning the Liebert FS; Figure 13 Liebert FS cabinet caster location; Storing the Liebert FS for Delayed Installation
Unloading and Unpacking 16 Figure 12 Location of serial and model number plate (cabinet side panel removed and open door) 3.3 Positioning the Liebert FS 3.3.1 Moving the Liebert FS When moving the unit a short distance, the Liebert FS may be rolled on its built-in casters (see Figure 13 ) to its loc...
Page 29 - Installation; NSTALLATION; floor preparations (see; Figure 14 Dimensions, general layout; Front
Installation 17 4.0 I NSTALLATION The Liebert FS system design and safety characteristics allow for a relatively simple and quick instal- lation. The system is designed to be rolled or lifted into place and bolted to the floor using Liebert's mounting kit, included with the system. The mounting kit ...
Page 30 - Figure 15 Internal layout; Fan
Installation 18 Figure 15 Internal layout NOTE The Liebert FS is designed for front-access-only for installation and maintenance. While the likelihood of repair is minimal, some repair procedures require side and/or rear access. Normally, the easiest way to handle this is to disconnect the power and...
Page 31 - Cabinet Floor Mounting; • For placement on concrete, masonry or stone floors, see; • For placement on wood floors, see; Figure 16 Floor mounting; loading specifications in; Floor Mounting
Installation 19 4.1 Cabinet Floor Mounting • For placement on concrete, masonry or stone floors, see 4.1.1 - Concrete, Masonry or Stone Floor Mounting . • For placement on wood floors, see 4.1.2 - Wood Floor Mounting . • For placement on raised floors, see 4.1.3 - Raised Floor Mounting . Figure 16 F...
Page 32 - Mounting Kit for Concrete, Masonry or Stone Floors; These tools are needed for the mounting the Liebert FS on the floor:; Concrete, Masonry or Stone Floor Mounting Instructions; places marked with an “X” on the template.; Figure 17 Floor mounting template layout; Front of Liebert FS
Installation 20 4.1.1 Concrete, Masonry or Stone Floor Mounting Mounting Kit for Concrete, Masonry or Stone Floors Liebert has included a complete anchoring kit with each Liebert FS for surface mounting. The kit is intended to securely fasten the Liebert FS to its intended location for operational s...
Page 33 - pattern described in; Figure 149 - Floor mounting template; . The setter rod should be used as a; Figure 18 Checking hole depth; mounting surface, use setter rod to expand and secure.; Figure 20 Expanding anchors
Installation 21 5. Drill 2" (51mm) deep holes in prepared surface using the drill bit included in the kit per bolt pattern described in Figure 149 - Floor mounting template . The setter rod should be used as a depth gauge to ensure proper depth. The setter rod is marked with two circles indicati...
Page 34 - hex bolts; Figure 21 Securing mounting brackets to the cabinet; Figure 22 Mounting rear bolts—rear side of cabinet; Bolt securing bracket
Installation 22 8. Match mounting brackets with the holes on the bottom of the cabinet (see Figure 21 ). Make sure that the bracket holes align with the mounting spots on the underside of the cabinet and secure the brackets with the four (4) 1/2" diameter x 3/4" long (12.7mm diameter x 20mm ...
Page 35 - Figure 23 Mounting front bolts—front side of cabinet; is within the outer circle.; Figure 24 Bubble level; Bubble
Installation 23 11. Insert and begin tightening two (2) hex head bolts with one washer each through bracket mounted at front of cabinet into anchor inserts in mounting surface (see Figure 23 ). Figure 23 Mounting front bolts—front side of cabinet 12. Check the bubble level on the floor of the cabine...
Page 36 - Wood Floor Mounting Parts
Installation 24 4.1.2 Wood Floor Mounting Determine which of these cases applies to your installation: • For wood flooring over concrete, follow the instructions in 4.1.1 - Concrete, Masonry or Stone Floor Mounting . • For wood flooring on joists, follow the instructions in this section. Wood Floor ...
Page 37 - Raised Floor Mounting Kit; • One floor mounting template,; Raised Floor Mounting Tools; Match mounting brackets with holes under base of cabinet (see; Figure 25 Raised floor mounting; Large diameter washer
Installation 25 4.1.3 Raised Floor Mounting Raised Floor Mounting Kit Liebert has included a complete anchoring kit with each Liebert FS for surface mounting. The kit is intended to securely fasten the Liebert FS to its location for operational safety and seismic requirements.The anchoring kit inclu...
Page 38 - Wiring Connections; The electrical connections to the Liebert FS are:; Figure 26 Liebert FS cabinet with UPS interconnection kit; Power and Status/Control wiring must be separated.; Fan Coil Module
Installation 26 6. Attach a large diameter washer, a lock washer and a nut to each hex flange bolts as described in Figure 25 and Figure 155 . 7. Check the bubble level on the floor of the cabinet on the right hand side of the Power Conversion Module (see Figure 24 ). The Liebert FS is sufficiently ...
Page 39 - connections; Liebert FS cabinet prior to cutting entry holes in them.; POS
Installation 27 Figure 27 Liebert FS with circuit breaker mounting plate and access panels for DC and control wiring connections Figure 28 Typical circuit breaker wiring for DC connections (view from rear of circuit breaker) ! CAUTION Do not cut entry holes for conduit while the access plates are st...
Page 40 - Appendix; Table 3
Installation 28 4.2.2 DC Power Connections The instructions for installation of DC power connections vary according to the type of UPS intercon- nection kit integrated into your Liebert FS unit. Follow the installation instructions in Appendix A.0 - UPS Interconnection Kits for the relevant UPS inte...
Page 41 - AC Auxiliary Control Power Supply Connections; Power Supply
Installation 29 4.2.5 AC Auxiliary Control Power Supply Connections The AC auxiliary power supply connections to the Liebert FS are made through the auxiliary power fused disconnect on the mounting plate above the inductor-capacitor module and to the right of the optional VIB and DCM modules (see Fi...
Page 42 - wire section) is recommended for this connection.; Figure 33 Top access panel
Installation 30 The AC wire is field-supplied. Wire size and installation must comply with all applicable local, regional and national regulations (e.g., National Electric Code for USA). An 18 AWG cable (approxi- mate metric equivalent: 0.82mm 2 wire section) is recommended for this connection. Figu...
Page 43 - Remote Monitoring Connections—Optional; capabilities are provided as an option see; Data Collection Module; Startup Considerations; AC Auxiliary
Installation 31 4.2.6 Remote Monitoring Connections—Optional The Liebert FS standard unit does not include remote monitoring connections. Remote monitoring capabilities are provided as an option see Figure 34 ). If your unit is equipped with the optional Data Collection Module (DCM), refer to the in...
Page 44 - System Overview; Detailed System Description; Figure 35 Liebert FS front view
System Overview 32 5.0 S YSTEM O VERVIEW 5.1 Detailed System Description Figure 35 Liebert FS front view UPS Interconnection Kit Power Conversion Module Built-In Casters, 4 Magnetic Levitation Module (above flywheel module) Versatile Interface Board (option) LCD Control Panel Motor Generator Filter ...
Page 45 - The Liebert FS is a modular system composed as follows:; Control Panel; The Flywheel Module houses several major components:
System Overview 33 5.1.1 System Module Description The Liebert FS is a modular system composed as follows: • Control Panel• UPS Interconnection Kit• Power Conversion Module• Main Control Module• Flywheel Module• E-Stop (optional-special order) Components are illustrated in Figure 35 . Control Panel ...
Page 46 - IGBT Power Conversion Module (PCM) on page 36; Magnetic Levitation; Remote Monitoring
System Overview 34 5.1.2 Power System The electrical system of the Liebert FS is shown in Figure 36 . The schematic shows the Magnetic Levitation Module [see 5.1.7 - Magnetic Levitation Module (MLM) ]. The pre-charge resistor and contactor which limit the inrush current into the DC bus capacitors. T...
Page 47 - or over the Internet, enabling a diagnostic reporting capability.; Monitored Information
System Overview 35 5.1.4 User interfaces Control Panel The Liebert FS uses a Control Panel as the primary means for an operator to interface with the sys- tem. Operating parameter values are displayed and updated in real time. Alarm states and system notices are also displayed when they occur. User ...
Page 48 - Power Conversion Module Controller (PCMC)
System Overview 36 5.1.6 Power Conversion Module Power Conversion Module Controller (PCMC) The Power Conversion Module Controller is located within the Power Conversion Module. The PCMC uses microprocessor-controlled logic to control the six pulse IGBT solid state switches and monitor the active mag...
Page 49 - tages over mechanical bearing systems:; Figure 37 Schematic of the levitation system; Active Magnetic Levitation Hardware; are located within the flywheel module. See; ROTOR
System Overview 37 5.1.7 Magnetic Levitation Module (MLM) The Magnetic Levitation Module provides control of the active magnetic levitation hardware.The Liebert FS has a unique active magnetic levitation system that fully levitates the flywheel-rotat- ing group, allowing the flywheel to rotate witho...
Page 50 - Figure 38 Liebert FS flywheel module
System Overview 38 5.1.8 Flywheel Module The Flywheel Module houses several major components: • The Rotating Group (high-speed carbon composite flywheel, high-speed shaft and rotor of the Motor-Generator) • The Motor-Generator (synchronous reluctance technology)• The Molecular Vacuum Pump• Flywheel ...
Page 51 - Figure 39 Rotating group; ply to the output DC bus up to the rated power. The illustration in
System Overview 39 5.1.9 Rotor/Flywheel—Rotating Group The flywheel is made of carbon/glass composite. This is mounted on a metal shaft with integral motor-rotor and together these components form the rotating group. The rotating group is magneti- cally levitated and centered so that it does not tou...
Page 52 - shaft to maintain a high-vacuum in the lower chamber, as shown in; Figure 41 Vacuum system operation; Air and Water Vapor
System Overview 40 5.1.11 Vacuum System During manufacture, the vacuum chambers are evacuated and baked to remove water vapor. The vac- uum system is then permanently sealed off to prevent any air entering the system and to remove the possibility of accidental loss of vacuum. The Liebert FS does not...
Page 53 - Speed; Type J thermocouple format.; Figure 42 Schematic for the speed and temperature sensors
System Overview 41 5.1.12 Flywheel Sensors Speed The speed detection system uses an infrared emitter and a sensor to detect the rotation of the shaft. A hole drilled through the shaft allows light to pass and is detected on the opposite side by an infrared detector. This signal is used to detect the...
Page 54 - Figure 43 Cutaway flywheel module; Outer Housing
System Overview 42 5.1.13 System Safety Every composite flywheel is inspected, spin balanced and tested to 110% over-speed in accordance with NEMA guidelines. A patented dual-wall safety system ensures that in the unlikely event a fly- wheel were to separate during operation, the inner housing would...
Page 55 - tinue to operate over the life of the unit.; List of System User-Configurable Parameters; ing operating parameters: See; Maximum Charge Current (Max Charge Current)
System Overview 43 5.1.15 Ventilation and Cooling The Liebert FS stator and power electronics are liquid cooled with a liquid-to-air radiator. The radia- tor within the Liebert FS package is designed for natural and forced air-cooling. Air inlets are pro- vided from the bottom front of the Liebert F...
Page 56 - Figure 44 Voltage and Inductance curve; ) shows the performance characteristics and; Regulation Voltage Delta During Discharge (Vreg Delta 1); to the Vreg Delta TSOC.; eh; Ch
System Overview 44 Figure 44 Voltage and Inductance curve The V-I (Voltage and Inductance) curve (see Figure 44 ) shows the performance characteristics and modes of operation of the Liebert FS system based on the seven user-configurable system parameters. Regulation Voltage Delta During Discharge (V...
Page 57 - Regulation Voltage Delta During Discharge (Vreg Delta 2); • Default setting—0VDC; Figure 45 Vreg delta help screen; Modes of Operation; various modes with no or minimal user intervention.; Control Panel see
System Overview 45 Regulation Voltage Delta During Discharge (Vreg Delta 2) Vreg Delta 2 is the programmed amount of voltage drop from the Transition State of Charge to the end of discharge (T SOC to the end of discharge (SOC = 0%) • Range—From 0 to (Vreg - Vreg Delta1) VDC (Ex: if Vreg = 500, and V...
Page 58 - TUP mode if all startup conditions are met.; Figure 46 STANDBY mode diagram; The Liebert FS will be in STANDBY Mode as long as:; Figure 47 Startup mode diagram; The Liebert FS will be in STARTUP mode as long as:; Vcharge and; UPS DC Bus Voltage = Vcharge
System Overview 46 5.3.1 OFF Mode When the Liebert FS is initially powered on, it enters the OFF mode and magnetically levitates its rotating group. A manual user command will make the system transition from OFF mode to STAR- TUP mode if all startup conditions are met. The Liebert FS also will enter...
Page 59 - Figure 48 CHARGE mode diagram; The Liebert FS will be in CHARGE mode as long as:; Figure 49 READY mode diagram; The Liebert FS will be in READY mode as long as:; supporting the UPS DC bus.
System Overview 47 5.3.4 CHARGE Mode To charge the Liebert FS, the Liebert FS will draw power from the UPS DC bus to accelerate the fly- wheel (as long as the UPS DC bus voltage is higher than Vcharge). In this mode, the Liebert FS State of Charge (SOC) will progressively increase from 0% to 100%. F...
Page 60 - Figure 50 DISCHARGE mode diagram; The Liebert FS will be in DISCHARGE mode as long as:; Following a Liebert FS Discharge Down to SOC = 0%; Figure 51 SHUTDOWN mode diagram - shutdown after full discharge
System Overview 48 5.3.6 DISCHARGE Mode Starting from either CHARGE or READY mode, the Liebert FS will enter the DISCHARGE mode if the UPS DC Bus Voltage goes below Vcharge. In DISCHARGE mode, the Liebert FS will regulate the DC bus at Vreg. Figure 50 DISCHARGE mode diagram The Liebert FS will be in...
Page 61 - Following a User Command; bus voltage is greater than Vcharge.; Figure 52 SHUTDOWN mode diagram - user-initiated shutdown; Liebert FS will automatically transition into SHUTDOWN Mode.; shooting; for more information.
System Overview 49 Following a User Command In any mode, except OFF mode, the user may command the Liebert FS to transition in SHUTDOWN. While in SHUTDOWN mode, the user will still be able to command the Liebert FS to transition into CHARGE mode (if SOC > 0%) or STARTUP mode (if SOC < 0%), pro...
Page 62 - Figure 53 Typical operation modes
System Overview 50 Figure 53 Typical operation modes KEY # MODE DESCRIPTION 1 READY Idle condition waiting for event 2 DISCHARGE 3 CHARGE FS supporting the critical load Charging to top speed A B C D E Grid Supply lost , FS supporting the load Generator Starts , A .T.S. transfers the load FS fully c...
Page 63 - Maintenance and Reliability
System Overview 51 5.4 Maintenance and Reliability The Liebert FS is designed to require minimal preventive servicing and maintenance. There are no user serviceable parts in the Liebert FS. Please contact a Liebert-Certified Technician before attempt- ing to remove or service any components of the s...
Page 64 - Operation; PERATION; Operator Controls; Initial setup and adjustments to Security Access functions; • Set pass codes and access levels; Execute operational procedures:; • Startup and shutdown of the Liebert FS.; Quick view of operational status:
Operation 52 6.0 O PERATION 6.1 Operator Controls The Liebert FS uses a Control Panel as the primary means for an operator to interface with the sys- tem. The Control Panel enables the operator to perform the following tasks: Initial setup and adjustments to programmable parameters (access limited b...
Page 65 - The Control Panel (see; Figure 54 Control panel view; numbers below, may vary from; screen at the same time during operation; Table 4
Operation 53 6.2 Control Panel The Control Panel (see Figure 54 ) below represents the Control Panel on the Liebert FS. The dia- gram is labeled as a reference for the various keys, functions and data found on the Control Panel. Figure 54 Control panel view Navigating the control panel is a simple p...
Page 66 - Figure 55 Main screen functions; Liebert FS; FAULT; FAULTS
Operation 54 6.2.1 Main screen function descriptions Figures 55 and 56 . provide descriptions and locations of the information and functions available from the Main screen and the Fault Screen. Figure 55 Main screen functions Figure 56 Fault screen functions Liebert FS 48020 RPM:SOC:SOC:BUS:PWR: 73....
Page 67 - panel as identified in; lists the system Modes along with the corresponding Con-; Table 6; See; Table 5
Operation 55 6.2.2 System MODE Indicators The Liebert FS has nine modes of operation: OFF, STARTUP, CHARGE, READY, DISCHARGE, SHUTDOWN, COAST, FAULT and STANDBY. These are displayed on the main screen of the control panel as identified in Figure 55 . Table 5 lists the system Modes along with the cor...
Page 68 - • Option Status DCM or VIB (example: V abbreviation for VIB enabled; Operative; Default setting; S O C
Operation 56 6.2.4 Other Status Indicators The Liebert FS system displays additional indicators during operation. • Option Status; DCM or VIB (example: V abbreviation for VIB enabled • Security Levels • PWM: Pulse Width Modulation Status (ON or OFF)• SOC: State of Charge (0-100%) SOC shows a relativ...
Page 69 - Security Access; , the display can be locked at any time to prevent use of; Menu Tree and Navigation; for more information on this subject.; Table 7
Operation 57 6.3 Security Access 6.3.1 Security Levels The Liebert FS software has two security levels: READ-ONLY and USER. Security levels restrict access to system resources, such as EEPROM parameters, terminal commands and display panel functions. From the Main Screen, Figure 55 , the display can...
Page 70 - Figure 57 Menu tree; units only; LEGEND
Operation 58 Figure 57 Menu tree User/ Adv Time/ Date Temperatures Voltages History Options Charge Electrical Network Vitals Password Input S/N Reboot Security About Tools View Menu Discharge Warning Fault Vitals Counters View/ Set Parameters RotorStator IGBTPCM/ PPMMLM/ MCMCabinet24V PS #1 24V PS #...
Page 71 - Navigation and Operation of Control Panel; pressed, the “Menu” key, will display the Main Menu screen as shown in; Figure 58 User level main menu screen
Operation 59 6.4.2 Navigation and Operation of Control Panel Navigation of the menu screens is simple and intuitive. From the Main Screen, also referred to as “Home”, menu functions and screens can be accessed by using the function keys and the numeric key- pad. The function keys, F1- F6, initiate c...
Page 72 - Figure 59 READ ONLY level parameter view screen; In the USER mode, below the 7 basic parameters can be modified, see; Figure 60 USER level or above parameter edit screen; Figure 61 HELP screen for User Setup Parameters; HELP; MORE; PREV
Operation 60 Figure 59 READ ONLY level parameter view screen In the USER mode, below the 7 basic parameters can be modified, see 6.3.2 - Password for access level and passwords. Pressing the corresponding number to the parameter to the left of the number will take you to the parameter setup screen f...
Page 73 - Figure 63 USER or higher level parameter selection for view/edit; rity level or higher is required to adjust the time or date, see; Figure 65 TIME/DATE set
Operation 61 Each EEPROM parameter has its own screen which contains parameter description, data range, cur- rent value and default value button. Default button shows the default value for the parameter. From this screen the UP/DOWN arrow keys can used to move between parameters. The UP/Down arrow w...
Page 74 - Figure 66 Temperature view; values are updated continuously.; Figure 68 History view; this software, it will display only the 24V power supply voltage.
Operation 62 6.4.6 Temperatures MENU>VIEW>TEMPERATURES shows the temperatures of various system parts. Figure 66 Temperature view 6.4.7 Voltages MENU>VIEW>VOLTAGES shows the major power supply voltages on the controller board. These values are updated continuously. Figure 67 Figure 5-14....
Page 75 - Figure 70 Discharge history; • A Discharge History event list screen,; Figure 71 Discharge History, Event list screen; tively. Seven warnings/faults are displayed in a single screen.; Figure 72 Warning history, Event list screen
Operation 63 • Discharge: The most recent discharge (LAST DISCHARGE) is displayed in time (sec.) and energy (kW) on this screen as are the accumulated discharge time/energy (TOTAL DISCHARGE) and the number of times system has discharged (DISCHARGE COUNT). (See Figure 70 .) Figure 70 Discharge histor...
Page 76 - Max/Min measurements along with the date recorded.; Figure 74 Vitals history view
Operation 64 • Vitals (USER or above): Key system efficiency and performance measurements are displayed in Max/Min measurements along with the date recorded. Figure 74 Vitals history view • Counters (USER or above) provide totals of run time hours; system and components, and numbers of startup and s...
Page 77 - assigning IP addresses.; Figure 78 Networks view; By entering a Password to access the User level mode (see; Figure 79 Networks view, Edit DHCP; tem will display the new screen.
Operation 65 6.4.10 Network—Requires DCM Option The Network view screen displays the addresses of the DCM. Static address settings can be entered using the keypad into this screen. If this option is installed, reference the Liebert Data Collection Module (DCM) Option Manual for more information on s...
Page 78 - ties are updated continuously.; Figure 81 Electrical view; Security levels can be changed in the MENU>SECURITY screen.; negative values for same indicate Charge mode.; HOME
Operation 66 6.4.11 Electrical The screen MENU>VIEW>ELECTRICAL shows the major electrical system variables. These quanti- ties are updated continuously. Figure 81 Electrical view 6.4.12 Vitals MENU>VIEW>VITALS shows the current vital system values. These quantities are updated continu- o...
Page 79 - Figure 83 Password screens; after 13th are ignored if more than 12 digits are entered.; Figure 84 Change password; INVALID PASSWORD
Operation 67 Figure 83 Password screens USER level password can be modified by pressing the CHG PW button. Current password is required to change the password. The USER level password should be between 3 - 12 digits length, hence digits after 13th are ignored if more than 12 digits are entered. Figu...
Page 80 - Figure 85 Change password; two DSPs and each DSP has bootloader and application firmware.; Figure 86 ABOUT screen; Tools menu has REBOOT function for USER to reboot system.; Figure 88 Tools for USER
Operation 68 Figure 85 Change password 6.4.14 About About screen shows the version of the firmware and company information. The controller board has two DSPs and each DSP has bootloader and application firmware. Figure 86 ABOUT screen Figure 87 Serial numbers 6.4.15 Tools Tools menu has REBOOT funct...
Page 81 - System Startup; Inspection before Initial System Startup; A Liebert technician will perform the following tasks:; • Visual Inspection; abide by instructions provided herein may void your warranty.
Operation 69 6.5 System Startup 6.5.1 Initial System Startup Procedure Initial System Startup is defined as the first or initial startup following installation of the system. Several additional steps are required prior to the normal startup procedure including the following Inspection before Initial...
Page 82 - Control Parameters Setup at Initial System Startup; ) and proceed to the Initial Startup Procedure.; Table 9; Control Parameter; Software versions; Software Application
Operation 70 6.5.3 Control Parameters Setup at Initial System Startup Please have the relevant UPS Interconnection Kit Handbook (Liebert UPS Interconnection Kit [IKIT] Handbook for specific Brand and Model UPS) available for the Liebert technician. The Control Parameters Setup values that need to be...
Page 83 - Powering Up the Liebert FS; A regular startup is any startup after the Initial System Startup.
Operation 71 6.5.5 Regular Startup Procedure 6.5.6 Inspection Before Regular Startup The following verifications must be done before performing a regular startup of the Liebert FS (see 6.5.7 - Starting up the System ): 1. Make sure the Liebert FS is properly secured to the floor with the Liebert-pro...
Page 84 - Validation of Control Parameters Setup; Shutdown Procedure; Startup procedures will vary for each UPS model.
Operation 72 Validation of Control Parameters Setup 1. Once the Control Panel has successfully booted up, the Control Panel will display the Main Screen (see Figure 55 ). 2. Verify the Control Parameters values are correct. (Consult Table 9 and the relevant UPS Interconnection Kit Handbook for choos...
Page 85 - Maintenance; Important Safety; familiar with the circuitry.; others approved for use in fighting electrical fires.
Maintenance 73 7.0 M AINTENANCE 7.1 Safety Precautions Observe all safety precautions in this manual, paying particular attention to Important Safety Instructions on page 1 . ONLY qualified service personnel should perform maintenance on the Liebert FS. Observe all of the warnings below before perfo...
Page 86 - Liebert Global Services; sales representative.; Professional Startup; Liebert FS Startup; Liebert FS startup agreement.; Maintenance Agreements: The Signature Program; Liebert FS Service Agreements; —Liebert Global Services (LGS) has a variety of available mainte-; Training; tive maintenance and some corrective maintenance.; Warranties; Routine Maintenance
Maintenance 74 7.2 Liebert Global Services Startup, maintenance and training programs for the Liebert FS are available through your Liebert sales representative. Professional Startup Liebert FS Startup —Liebert’s customer engineers perform a thorough, non-powered inspection of the units and will the...
Page 87 - Maintenance Schedule; ensure unit is disconnected and de-energized.; specifically noted, may void your warranty.; Maintenance schedule; for torque requirements.; technical bulletins to address any additions.
Maintenance 75 7.4 Maintenance Schedule The Liebert FS maintenance schedule consists of actions listed in Table 11 . 7.5 Record Log Set up a maintenance log to record scheduled checks and any abnormal conditions.The log should have space for all metered parameter indications including phase readings...
Page 88 - Optional Air Filters; Torque specifications (unless otherwise labeled)
Maintenance 76 7.6 Optional Air Filters The optional air filters must be inspected and serviced on a regular schedule. The period between inspections will depend upon environmental conditions. Under normal conditions, the air filters will require cleaning or replacement approximately every 12 months...
Page 89 - Reporting a Problem; action in; Recommended Test Equipment; audit and verification.; Limited Life Components; avoid interruptions in critical load operations.; Recommended test equipment and tools
Maintenance 77 7.9 Reporting a Problem If a problem occurs within the Liebert FS, review all alarm messages along with other pertinent data. This information should be given by telephone to the Liebert service representative’s office nearest you. This information can be downloaded to Liebert Global ...
Page 90 - Troubleshooting; ROUBLESHOOTING; General; for instructions on how to access this data via the DCM.; Figure 89 USER level menu; select the function by number.; Figure 90 VIEW menu
Troubleshooting 78 8.0 T ROUBLESHOOTING 8.1 General The Liebert FS is capable of detecting conditions outside of normal operating parameters and provid- ing notice at the Control Panel. This data is recorded as either Warnings or Faults and can be viewed in the software menu tree at the screen locat...
Page 91 - Figure 91 Warning history; may be used; Warnings; Figure 93 Warning screen; CHARGE; More information
Troubleshooting 79 Figure 91 Warning history Figure 92 Fault history The warnings, fault meanings and possible causes in the following text and in Table 15 may be used in troubleshooting the messages and may also aid in identifying conditions outside the flywheel sys- tem that may adversely affect i...
Page 92 - Warning
Troubleshooting 80 Table 15 lists the warnings and some troubleshooting steps that may be taken if any of the Warnings in appear. If Warnings persist, contact your local Liebert representative or contact Liebert Global Services at 800-543-2378. You may also visit the Liebert Web site for information...
Page 93 - Faults; shows the appearance of an active Fault on the main screen.; Figure 94 Fault screen descriptions; through
Troubleshooting 81 8.3 Faults A Fault is defined as an undesirable system operating condition that could cause further damage to the system or potentially drop the load. Once detected, Faults may trigger an appropriate emergency action such as shutting the unit down. Most Fault conditions are automa...
Page 94 - Table 17 - Troubleshooting; describes actions that may alleviate the condition or provide; Faults—causes and responses
Troubleshooting 82 Faults. Table 17 - Troubleshooting describes actions that may alleviate the condition or provide valuable information for technical support. Faults that initiate an AUTOSHUTDOWN include: MISER, RUNOUT, PWR SPLY VOLT (at high speed), and will require Service level and higher to res...
Page 95 - are troubleshooting steps for the Fault messages that can occur.
Troubleshooting 83 Fault messages displayed can, in some cases, be investigated for a solution. Listed below in Table 17 are troubleshooting steps for the Fault messages that can occur. Refer to the general drawings in Appendix D.0 - Installation Drawings for the location of system components.If a F...
Page 96 - UPS Interconnection Kits; PPENDIX; instructions and drawings in this manual.; Appendix A.1 Wiring Connections; Appendix A.1.1 General Wiring Considerations; to arrange for system startup.; designed for, as shown in; Key to UPS model interconnection; Use With Liebert UPS; Liebert Npower; are in
UPS Interconnection Kits 84 A PPENDIX A.0 UPS I NTERCONNECTION K ITS Your Liebert FS is equipped with a UPS interconnection kit to connect it to one of these Liebert UPS systems: • Liebert Series 610™, 600T™ or 600™• Liebert Npower™• Liebert Series 300™• Liebert HiPulse™ The Liebert FS system must b...
Page 97 - Power and status/control wiring must be separated; Liebert FS cabinet prior to cutting entry holes.
UPS Interconnection Kits 85 Power and status/control wiring must be run in separate conduits or cable trays. Refer to Appendix D.0 - Installation Drawings for locations of the various electrical connections between Liebert FS system(s) and UPS system. Figure 95 Top view of Liebert FS Cabinet with UP...
Page 98 - Figure 96 Circuit breaker; . Refer to this drawing to ensure that the adequate con-; Circuit Breaker Torque
UPS Interconnection Kits 86 Appendix A.1.2 DC Power Connections The DC power connections to the Liebert FS are made through the circuit breaker (see Figure 96 ) in the UPS interconnection kit installed in your Liebert FS. The maximum wire size for the circuit breaker terminals is 350MCM - 600VDC (ap...
Page 99 - DC Power Interface; UPS Output Rating
UPS Interconnection Kits 87 Appendix A.2 Installing the Liebert FS With a Liebert Series 610, Liebert Series 600T or Liebert Series 600 The Liebert Series 610/600T/600 UPS interconnection kit for the Liebert FS is compatible with the Liebert Series 610, Liebert Series 600T and Liebert Series 600 mod...
Page 100 - trol Terminal Block is described in; Figure 137 - Control wiring diagram—Liebert FS cabinet -; . Refer to this drawing to ensure that proper connections are; Figure; some parameters must be checked on the UPS system:
UPS Interconnection Kits 88 Appendix A.2.2 Status/Control Connections - Liebert Series 610/600T/600 UPS Interconnection Kit The status/control interface is the Status/Control Terminal Block. The connection of the Status/Con- trol Terminal Block is described in Figure 137 - Control wiring diagram—Lie...
Page 101 - Instructions to set these parameters on the Liebert FS are in; DC Bus; together at the same time to the task of supporting the UPS DC bus.; Liebert FS Software Control Parameter settings; Liebert FS Software Control Parameter; Liebert FS Software Control Parameters varying with UPS size; representative to arrange a review of the application.
UPS Interconnection Kits 89 Appendix A.2.4 Liebert FS Configuration - Single Liebert FS on Liebert Series 610/600T/600 DC Bus The following Software Control Parameters must be set when the Liebert FS is connected to the DC bus of the Liebert Series 610/600T/600 UPS system. Instructions to set these ...
Page 102 - Appendix A.3 Installing the Liebert FS With a Liebert Npower UPS; Npower models in; Figure 99 Liebert FS integrated into a Liebert Npower UPS system
UPS Interconnection Kits 90 Appendix A.3 Installing the Liebert FS With a Liebert Npower UPS The Liebert Npower UPS interconnection kit for the Liebert FS is compatible with the Liebert Npower models in Table 22 . Figure 99 Liebert FS integrated into a Liebert Npower UPS system Appendix A.3.1 Descri...
Page 103 - of the BIB is described in; Figure 140 - Control wiring diagram—Liebert FS - optional electri-; . Refer to this drawing to ensure that the; lel for capacity; Appendix A.3.3 UPS Configuration - Liebert FS and Liebert Npower; parameters must be checked on the UPS system:; Appendix A.3.4 Liebert FS Configuration - Single Liebert FS Unit; DC bus of the Liebert Npower UPS system.; parameters on the Liebert FS are in; Startup; Liebert FS Software
UPS Interconnection Kits 91 Appendix A.3.2 Status/Control Connections - Liebert Npower UPS Interconnection Kit The status/control interface is the Liebert Npower Battery Information Board (BIB). The connection of the BIB is described in Figure 140 - Control wiring diagram—Liebert FS - optional elect...
Page 104 - Initial System Startup
UPS Interconnection Kits 92 Appendix A.3.5 Liebert FS Configuration - Multiple Liebert FS Units on Liebert Npower DC Bus Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are connected in parallel on the DC bus of a Liebert Npower UPS system for proper operation wit...
Page 105 - Series 300 models in; Liebert FS and the Liebert Series 300.; List of Liebert Series 300 models ratings
UPS Interconnection Kits 93 Appendix A.4 Installing the Liebert FS With a Liebert Series 300 UPS The Liebert Series 300 UPS interconnection kit for the Liebert FS is compatible with the Liebert Series 300 models in Table 25 . Figure 100 Liebert Series 300 UPS Appendix A.4.1 Description - Liebert Ser...
Page 106 - Figure 137 - Control wiring diagram—Liebert FS cabi-; Appendix A.4.3 UPS Configuration - Liebert FS and Liebert Series 300
UPS Interconnection Kits 94 Appendix A.4.2 Status/Control Connections - Liebert Series 300 UPS Interconnection Kit The status/control interface is the Status/Control Terminal Block. The connection of the Status/Con- trol Terminal Block is described in the Figure 137 - Control wiring diagram—Liebert ...
Page 107 - Bus of the Liebert Series 300 UPS system.; Bus
UPS Interconnection Kits 95 Appendix A.4.4 Liebert FS Configuration - Single Liebert FS on Series 300 DC Bus The following Software Control Parameters must be reset when the Liebert FS is connected to the DC Bus of the Liebert Series 300 UPS system. Instructions to set these parameters on the Lieber...
Page 108 - Appendix A.5 Installing the Liebert FS With a Liebert HiPulse UPS; Appendix A.5.1 Description—HiPulse UPS Interconnection Kit
UPS Interconnection Kits 96 Appendix A.5 Installing the Liebert FS With a Liebert HiPulse UPS The Liebert HiPulse UPS interconnection kit for the Liebert FS is compatible with the Liebert HiPulse™ models in Table 28 . Appendix A.5.1 Description—HiPulse UPS Interconnection Kit HiPulse UPS interconnec...
Page 109 - Figure 135 - Elevation drawing—Liebert FS; . Refer to this drawing to ensure that the proper connec-; eters must be checked on the UPS system:
UPS Interconnection Kits 97 Appendix A.5.3 IKIT-A05 DC Power Connections The DC power connections to the Liebert FS are made through the circuit-breaker (see Figure 103 ) in the IKIT-A05. The minimum wire size to be used is 1/0 AWG - 600VDC wire (54 mm 2 wire section). The maximum wire size for the ...
Page 110 - Appendix A.5.5 Single Liebert FS on UPS DC Bus; nected alone on the DC bus of the Liebert HiPulse UPS system.; Setup at Initial System Startup; require adjustments due to the battery type.
UPS Interconnection Kits 98 Appendix A.5.5 Single Liebert FS on UPS DC Bus The following Liebert FS Software Control Parameters must be set when a single Liebert FS is con- nected alone on the DC bus of the Liebert HiPulse UPS system. Instructions on setting these parameters on the Liebert FS are fo...
Page 111 - Appendix A.5.7 Liebert FS Configuration – Multiple Liebert FS Units; Multiple Liebert FS Parallel Operation—Regular Configuration
UPS Interconnection Kits 99 Appendix A.5.7 Liebert FS Configuration – Multiple Liebert FS Units Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are connected in parallel on the DC bus of a Liebert HiPulse™ UPS system.Instructions to set these parameters on the Lie...
Page 112 - Appendix B.1 General Information; gration with an existing network.; Appendix B.2 DCM Installation and Configuration; communication cable have been connected at the factory as seen in; Figure 104 Data Collection Module location, features
Data Collection Module 100 A PPENDIX B.0 D ATA C OLLECTION M ODULE Appendix B.1 General Information Appendix B.1.1 Overview The Data Collection Module (DCM) is designed to provide real-time data monitoring and data storage for the Liebert FS. The DCM collects data on virtually every event that occur...
Page 113 - your Internet browser.; Figure 105 DCM LAN connection; From the Main Menu Screen, select number 2 “View” screen.; Figure 106 Options view; Power Connection
Data Collection Module 101 Appendix B.2.2 DCM Requirements The Data Collection Module requires a connection to an existing network via an Ethernet cable. An RJ-45 jack is built directly into the bottom of the faceplate of the DCM and located adjacent to the power supply connection. The DCM may also ...
Page 114 - Default Gateway, Subnet Mask and DNS Server.; Figure 108 Networks view; turn this function Off or On.; Figure 109 Networks view, turn off DHCP
Data Collection Module 102 To view the Network settings return to the View menu and press number 6 “Network”. The Network view screen displays the network addresses coming from the DCM. Static address settings can be entered using the keypad into this screen. The Network screen will show the assigne...
Page 115 - net browser to gain access to the DCM as seen in; Figure 111 DCM screen; browse the data recorded by the DCM.; Appendix B.2.4 Configuring DCM System Parameters; are seven fields on the Setup page as seen in; Figure 112 DCM setup screen; Enter IP
Data Collection Module 103 Appendix B.2.3 Accessing the DCM From a personal computer connected to the same network as the DCM, enter the IP Address of the DCM, assigned by the LAN network server or manually configured, into the address line of the Inter- net browser to gain access to the DCM as seen...
Page 116 - Appendix B.3 DCM Operation; and Configuration; Appendix B.3.2 Status and Detailed Status Screens; Figure 113 DCM status screen
Data Collection Module 104 • Software Version: The current version of the software running on the DCM. • Configuration Type: Select from the drop-down menu as to whether it is a Static IP Address or a DHCP server assigned. • IPAddress: The IP Address of the DCM • Subnet Mask: The Subnet mask of the ...
Page 117 - Figure 114 Datafiles screen
Data Collection Module 105 Appendix B.3.3 Datafiles Screen This screen lists the different files types for viewing and download. There are five files types: F, S, L, A and D. • F indicates a fast data packet, containing electrical information such as voltages, amps and watts. • S represents a slow p...
Page 118 - Appendix B.4 DCM Troubleshooting; Appendix B.4.1 DCM Troubleshooting Principles; shown in; Figure 115 Data Collection Module reset button; What You See...
Data Collection Module 106 Appendix B.4 DCM Troubleshooting Appendix B.4.1 DCM Troubleshooting Principles There are few circumstances in which the Liebert FS might operate in an unexpected manner. This section explains a few of these circumstances and offers some solutions to such issues. Appendix B...
Page 119 - Versatile Interface Board; Appendix C.1 General Information—Versatile Interface Board; Appendix C.1.1 Versatile Interface Board Overview; shows the two main electrical components of the VIB.; Figure 116 VIB components
Versatile Interface Board 107 A PPENDIX C.0 V ERSATILE I NTERFACE B OARD Appendix C.1 General Information—Versatile Interface Board Appendix C.1.1 Versatile Interface Board Overview The Versatile Interface Board (VIB) is designed to provide real-time status feedback and control of the Liebert FS. Th...
Page 120 - each I/O is listed below in; Interface
Versatile Interface Board 108 Appendix C.1.2 VIB Features The VIB provides fully isolated inputs and outputs that operate on a wide range of voltages for maxi- mum flexibility. Each I/O is programmed to perform a dedicated function. The specific function of each I/O is listed below in Table 34 . For...
Page 121 - Figure 117 I/O Designations
Versatile Interface Board 109 Figure 117 I/O Designations I/O Label (X20) ~ I /O 2 I/ O 3 I/ O 4 I/ O 5 I /O 6 I /O 7 I /O 8 I /O 9 I/O 10 COM N.C. W/ N .O . COM N.C. W/ N .O . COM N.C. W/ N .O . COM N.C. W/ N .O . COM N.C. W/ N .O . COM N.C. W/ N .O . COM N.C. W/ N .O . COM N.C. W/ N .O . COM N.C. ...
Page 122 - Appendix C.2 VIB Installation and Configuration; cable has been connected to the Main Control Module at the factory; Figure 118 Versatile Interface Board mounted in the Liebert FS; corner of the display. Press F6 when finished.; with the kit for the proper mounting procedure.)
Versatile Interface Board 110 Appendix C.2 VIB Installation and Configuration Appendix C.2.1 VIB Installation The VIB has been installed behind the service panel of the Liebert FS. The power/communications cable has been connected to the Main Control Module at the factory . Figure 118 Versatile Inte...
Page 123 - Figure 119 VIB screw terminal connections; Appendix C.3 VIB Operation; undesirable effects and may damage the equipment.; “Enabled” State
Versatile Interface Board 111 Appendix C.2.5 VIB Connections The VIB is supplied with removable screw-terminal connectors to allow for easy integration Figure 119 . The user must supply the wire as specified below to make the connections to the VIB connectors. • Wire gauge: 12-24 AWG• Stripped lengt...
Page 124 - Appendix C.4 Troubleshooting the VIB; Appendix C.4.1 UIB State Not Displayed on the Front Panel; • Attempt to enable the VIB by pressing
Versatile Interface Board 112 Appendix C.4 Troubleshooting the VIB Appendix C.4.1 UIB State Not Displayed on the Front Panel • Check that no other faults are present on the display panel.• Call Liebert for instructions on how to enable the VIB functionality. Appendix C.4.2 VIB in “Disabled” or “Not ...
Page 125 - Installation Drawings; Appendix D.1 Liebert FS Flywheel Submittal Document Matrix; factory. The documents are grouped by Liebert FS model number.; Submittal documents accompanying Liebert FS
Installation Drawings 113 A PPENDIX D.0 I NSTALLATION D RAWINGS Appendix D.1 Liebert FS Flywheel Submittal Document Matrix Following is a list of submittal documents that must accompany each Liebert FS that ships from the factory. The documents are grouped by Liebert FS model number. Table 35 Submit...
Page 126 - Appendix D.2 Other Liebert FS Drawings; Single Liebert FS Cabinets – Additional Elevation Drawings
Installation Drawings 114 Appendix D.2 Other Liebert FS Drawings Following is a list of additional Liebert FS drawings that are available for distribution. These draw- ings are not directly linked to any specific Liebert FS model number, because most of them are appli- cable to Liebert FS cabinets c...
Page 127 - Figure 121 Electrical connections
Installation Drawings 115 Figure 121 Electrical connections
Page 128 - Figure 122 Electrical system block diagram
Installation Drawings 116 Figure 122 Electrical system block diagram
Page 129 - Figure 123 24 UVR, circuit breaker to terminal block wiring
Installation Drawings 117 Figure 123 24 UVR, circuit breaker to terminal block wiring Figure 124 48 UVR, circuit breaker to terminal block wiring Note: PCM is UPS module. 12-100120-16 Rev. 0 Note: PCM is UPS module. 12-100120-16 Rev. 0
Page 130 - Figure 125 Outline drawing, Liebert FS cabinet; Rev
Installation Drawings 118 Figure 125 Outline drawing, Liebert FS cabinet 12-100120-00 Rev . 01
Page 131 - module; FUSED
Installation Drawings 119 Figure 126 Control wiring, external interconnect diagram—Liebert FS cabinet to Liebert Npower UPS module Figure 127Control wiring external interconnect—Liebert FS to Liebert Series 300 C.G. #17 C.G. #19 Liebert FS Liebert Npower UPS Module 12-100120-01Rev. 01 FUSED DISCONNE...
Page 134 - Shipping
Installation Drawings 122 Figure 130Elevation drawing, Liebert FS cabinet with shipping package 12-100120-08 Rev . 01 48" (1219mm) 4.4" (1 12mm) 45" (1 143mm) 24" (610mm) Shipping Support Bands (on either side) 54" (1372mm) 76.9" (1953mm) Front V iew Right Side V iew W e ight...
Page 135 - Figure 131Elevation drawing—Liebert FS cabinet
Installation Drawings 123 Figure 131Elevation drawing—Liebert FS cabinet 70.9" (1801mm) 25" (635mm) Front Top Bottom 32.5" (826mm) Right Side Standard Upgraded Interactive Display 12-100120 -09Rev. 1
Page 137 - Figure 133Liebert FS cabinet with optional power terminal block
Installation Drawings 125 Figure 133Liebert FS cabinet with optional power terminal block 12-100120-11Rev. 01 Optional PowerTerminal Block(shown withoutcover plate)
Page 138 - Figure 134Liebert FS cabinet mechanical installation
Installation Drawings 126 Figure 134Liebert FS cabinet mechanical installation Do N o t Ti ght e n H al f- S iz e V iew of Fl o o r A n c hor Re ar M o u n t 12- 10 012 0- 12 Re v. 0 1 32 -5 ” (8 25 .5 m m ) R ig h t- S id e V iew 36 ” ( 914 m m ) Mi n im u m Fr ont C le ar a nc e 12” ( 3 05m m ) O ...
Page 140 - Ou
Installation Drawings 128 Figure 136One-line drawing, three Liebert FS systems in parallel configuration B i-D ire ct ion al P ow er C onv er te r F LYW H E EL No rm al ly O pen Fa ct or y- In tegr at ed Ci rc ui t B re ak er 1 FL Y W H E E L No rm al ly O pen Fa ct or y- In te gr ate d Ci rc ui t B...
Page 141 - Contacts; Ye
Installation Drawings 129 Figure 137Control wiring diagram—Liebert FS cabinet - manually operated circuit breaker 1 3 3 4 5 6 7 8 9 10 (+ ) (- ) (+ ) (- ) (G N D ) To Li eb er t FS PC M D C O u tp u t NO T E 1. P C M – P o w e r C o nv er si on M o dul e TB 1 UV R Co n tr ol NC NO CO M T o Li eber t...
Page 143 - Liebert UPS module; Liebert UPS Module; Normally
Installation Drawings 131 Figure 139 One-line diagram—single Liebert FS system with factory-integrated circuit breaker supplying Liebert UPS module Battery/DC In Liebert FS System 12-100120 -18Rev. 0 Liebert UPS Module FLYWHEEL Normally Open Circuit Breaker Rectifier Inverter 3Out 3In Battery/Usage(...
Page 144 - Npower units; Contractor to
Installation Drawings 132 Figure 140Control wiring diagram—Liebert FS - optional electrically operated circuit breaker Liebert Npower units TB 3 T B 1 T B 2 TB 5 T B 9 P2 T B 8 40 0 40 1 113 Therm (In ) 114 (Therm (Out ) C o nt ra ct o r t o P ro vi de C a bl es to Li eb er t U P S M o du le Ye llo ...
Page 145 - Liebert UPS
Installation Drawings 133 Figure 141Two-eight paralleled Liebert FS units with factory-integrated circuit breaker in parallel with a Liebert UPS B i-D ire ct ion al P owe r Co nv e rte r NO T E S 1. S er ies 610/600 re qui re s the us e of M B D for mor e th an th ree u ni ts in par al le l. I t c a...
Page 146 - Liebert UPS—UPS DC terminal point of common connection; Rectifier; Circuit Breaker; VRLA Battery
Installation Drawings 134 Figure 142One-line diagram, single Liebert FS and battery with factory-integrated circuit breaker supplying Liebert UPS—UPS DC terminal point of common connection Liebert UPS Module Rectifier Inverter 3Out 3In Liebert FS System Bi-Directional Power Converter 12 -100120 -21R...
Page 147 - Liebert UPS—UPS battery point of common connection; Power Converter
Installation Drawings 135 Figure 143One-line diagram, single Liebert FS and battery with factory-integrated circuit breaker supplying Liebert UPS—UPS battery point of common connection Liebert UPS Module Rectifier Inverter 3Out 3In Liebert FS System 12 -100120 -22Rev. 0 FLYWHEEL Normally Open Circui...
Page 148 - Figure 144 Status/control wiring, multiple units; UV
Installation Drawings 136 Figure 144 Status/control wiring, multiple units 3 UV R 9 9 8 8 7 7 6 6 5 5 3 3 2 2 10 10 4 4 1 1 E nd (N ) L ieb er t F S C ab ine t F S S tatu s / C ontr ol T er m in al B loc k 3 5 4 In ter m ed ia te ( 1 th ro ug h N -1 ) Li eb er t F S C ab in et F S S tat us / C ont r...
Page 150 - Figure 146 Wiring specifications, Liebert FS and Liebert Npower
Installation Drawings 138 Figure 146 Wiring specifications, Liebert FS and Liebert Npower Wire No. Terminal Designation Signal Name Maximum Voltage Maximum Current Color Wire Size & Type Maximum Length Remarks From To Liebert N-Power UPS - Cable Group # 17 (Flywheel CB IFM) From TB69 in UPS Modu...
Page 152 - Figure 148 Wiring specifications, Liebert FS and Liebert HiPulse; WIRING SPECIFICATIONS FOR THE LIEBERT FS AND LIEBERT HIPULSE
Installation Drawings 140 Figure 148 Wiring specifications, Liebert FS and Liebert HiPulse WIRING SPECIFICATIONS FOR THE LIEBERT FS AND LIEBERT HIPULSE ARE AVAILABLE BY CONTACTING: Your local Liebert Sales Representative Your local Liebert Service Representative Liebert Corp. at 1-800-Liebert (1-800...
Page 153 - Figure 149 Floor mounting template
Installation Drawings 141 Figure 149 Floor mounting template 16 " (4 06m m ) N O T E : I f h ole is dr ill ed to o de ep , b a ck fill t o c o rr ec t to pr op er de pt h. 2. 25 ( 57m m ) m ax . 4X O 5/ 8" ( 1 6m m ) M as o n Dr ill x 2. 00 ( 5 1m m ) m in . 29- 1/ 2" (7 49m m )
Page 154 - Figure 150 System mounting kit
Installation Drawings 142 Figure 150 System mounting kit Dr ill T e m p la te Dw g 1 6 B o lts a nd W a sher s com e w ith c a bi net 3 7 4 5 2 8
Page 155 - Figure 151 Liebert FS block diagram
Installation Drawings 143 Figure 151 Liebert FS block diagram OP T IO N A L CA P A CI T O RS FI LT E R P R EC H A R G E B O AR D C A P A CI TO R B A N K F U SE BO A R D P O W E R I N T E R F AC E B O A R D PO W E R B L O C K P O W E R DI S T RI B U T IO N B O A R D 2 4VD C PO W E R SU PPL Y 2 4VD C ...
Page 156 - Figure 152 Power line diagram
Installation Drawings 144 Figure 152 Power line diagram
Page 157 - Figure 153 UPS cable entry—bottom; UP; INE
Installation Drawings 145 Figure 153 UPS cable entry—bottom ( + ) B us (- ) B us Gr ou nd B u s Li eb e rt F S C abi ne t U n it N Li eb e rt FS Ca b in e t Un it N Li e b er t F S Ca b in et Un it N 3- P has e Ou tp ut UP S CA B INE T 3- P ha se In p ut NOTES 1. All ca bl es sho u ld b e rou ted b ...
Page 158 - Figure 154 UPS cable entry—top
Installation Drawings 146 Figure 154 UPS cable entry—top ( + ) B us ( - ) B us Gr o un d B us Li eb e rt F S C abi ne t Un it 1 Li eb e rt FS Ca b in e t Un it 2 Li e b er t F S Ca b in et Un it N 3- P has e Ou tp ut UP S CA B INE T 3- P ha se In p ut NOTES 1. All cabl es shoul d be rou ted before b...
Page 159 - Figure 155 Raised floor mounting; TOP VIEW
Installation Drawings 147 Figure 155 Raised floor mounting 2" (50mm) dia. 1/2" (12.7mm) dia. steel bolt Large diameter washer Lockwasher Raisedfloor F NOTE: Combination of floor material of given thickness , plusproperties of large diameter washer and fastener , should result inlateral load ...
Page 160 - Specifications; Technical specifications; ENVIRONMENTAL
Specifications 148 A PPENDIX E.0 S PECIFICATIONS Table 36 Technical specifications INPUT, DC Float Voltage 350 through 600 VDC; > 520 VDC required for 190kW Charging Current 5 through 50 Amps per Liebert FS Rated Input Charging 350-600 VDC; > 520 VDC required for 190kW Maximum Idling Consumpti...
Page 161 - Appendix E.1 Ground Test Procedure; Items Required; • Handheld Multimeter - Ohmmeter; Connect tester cable to non-painted metal or screw for testing.
Specifications 149 Appendix E.1 Ground Test Procedure The purpose of the GTS is to confirm integrity of grounding path. This test is performed when the sys- tem is completely shutdown and isolated from all external powers. Use the checklist below. Items Required • Handheld Multimeter - Ohmmeter The ...
Page 162 - OWER; Appendix F.1 Overview; details on installation and operation.; Appendix F.2 Backup AC Power Supply Specification; If the Liebert FS
Auxiliary Backup AC Power Supply 150 A PPENDIX F.0 A UXILIARY B ACKUP AC P OWER S UPPLY Appendix F.1 Overview The Liebert FS must be operated with a backup AC power supply to protect the unit’s mechanical bearings if: • the external DC supply is lost and• the Liebert FS has developed a fault If thes...
Page 163 - Operating the Liebert FS+DC in Parallel With Batteries; power supply to the output of the UPS, as shown in; +DC unit operating with a UPS in conjunction with batteries; +DC units operating with a UPS in conjunction with batteries
Auxiliary Backup AC Power Supply 151 Appendix F.3.1 Operating the Liebert FS+DC in Parallel With Batteries If the Liebert FS is operating in parallel with batteries, Liebert recommends attaching the backup AC power supply to the output of the UPS, as shown in Figures 156 and 157 . Figure 156 A singl...
Page 164 - Operating the Liebert FS Without Batteries; separate feeder circuit (see
Auxiliary Backup AC Power Supply 152 Appendix F.3.2 Operating the Liebert FS Without Batteries If the Liebert FS is operating without batteries, Liebert recommends feeding the backup AC power supply from a separate, protected supply. This may be the output of another UPS or a supply from a separate ...
Page 165 - Appendix F.4 Scenarios; Loss of backup AC supply at 0 RPM
Auxiliary Backup AC Power Supply 153 Appendix F.4 Scenarios This section describes five scenarios that might occur. • Loss of backup AC supply at 0 RPM - This causes a fault message to appear on the control panel to indicate there is a problem with the backup supply. The unit will not start until th...
Page 168 - AC Power
EmersonNetworkPower.com Ensuring The High Availability0f Mission-Critical Data And Applications. Emerson Network Power, the global leader in enabling business-criticalcontinuity, ensures network resiliency and adaptability througha family of technologies—including Liebert power and coolingtechnologi...