Emerson PN 51A-404 - Manual

Emerson PN 51A-404

Emerson PN 51A-404 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
Page: / 8

Table of Contents:

  • Page 2 – WIRING DIAGRAMS; FIGURE 2. Model 54eC Wiring; WIRING; WIRE COLOR AND CONNECTIONS IN SENSOR; COLOR FUNCTION; RTD
  • Page 3 – WIRING THROUGH A JUNCTION BOX
  • Page 4 – CLEANING THE SENSOR
  • Page 5 – TROUBLESHOOTING; PROBLEM; FIGURE 9. Checking Temperature Element
  • Page 6 – NOTES
  • Page 8 – Specifications subject to change without notice.
Loading the manual

WARNING

Before removing the sensor, be absolutely certain
that the process pressure is reduced to 0 psig and
the process temperature is lowered to a safe level!

Model 404

ENDURANCE

Conductivity Sensor

Instruction Sheet

PN 51A-404/rev.M
December 2010

If the sensor is installed in a sidestream
with the sample draining to open atmos-
phere, bubbles may accumulate on the
electrodes. Trapped bubbles will cause
errors. Normally, as bubbles accumu-
late the conductivity reading drifts down.
To control bubble formation, apply a small
amount of back pressure to the sensor.

SENSOR SPECIFICATIONS

SPECIFICATIONS

MODEL 404-16 (PVC body)

MODEL 404-17 (stainless steel body)

Wetted Materials

Titanium, PEEK (glass filled), PVC,

Titanium, PEEK (glass filled),

EPDM, polyethylene

303 SST, EPDM

Temperature Range

32-140°F (0-60°C)

32-212°F (0-100°C)

Maximum Pressure

20 psig (239 kPa abs) at 60°C (140°F)

100 psig (791 kPa abs)

100 psig (791 kPa abs) at 25°C (77°F)
(use FNPT fittings only)

FIGURE 1. Installation of Model 404 Sensor

For additional information, please visit our website

at

www.emersonprocess.com/raihome/liquid/

.

INSTALLATION

The wetted sensor materials may not be compatible
with process com position and operating conditions.
Application compat ibility is entirely the responsi-
bility of the user.

CAUTION

SENSOR/PROCESS

APPLICATION COMPATIBILITY

WARNING

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - WIRING DIAGRAMS; FIGURE 2. Model 54eC Wiring; WIRING; WIRE COLOR AND CONNECTIONS IN SENSOR; COLOR FUNCTION; RTD

2 MODEL 404 WIRING WIRING DIAGRAMS FIGURE 2. Model 54eC Wiring FIGURE 3. Model 56 and 1056 Wiring WIRING WIRE COLOR AND CONNECTIONS IN SENSOR COLOR FUNCTION Gray Connects to outer electrode Clear Coaxial shield for gray wire Orange Connects to inner electrode Clear Coaxial shield for orange wire Red...

Page 3 - WIRING THROUGH A JUNCTION BOX

3 MODEL 404 INSTALLATION FIGURE 5. Model Xmt-C-10 Wiring (Panel) FIGURE 6. Model Xmt-C-11 Wiring (Pipe or Wall) FIGURE 7. Model 5081-C Wiring FIGURE 8. Model 6081-C Wiring WIRING THROUGH A JUNCTION BOX If wiring connections are made through a remote junction box (PN 23550-00), wire point-to-point. U...

Page 4 - CLEANING THE SENSOR

4 MODEL 404 WIRING CLEANING THE SENSOR The 404-17 (stainless steel body) sensor can be taken apart for cleaning. However, in some cases, disassembling andreassembling the sensor can cause the cell constant to change as much as 1%. For maximum accuracy, the cell con-stant should be rechecked after th...

Other Emerson Models