- Page 2 – Liebert Corporation; Page 2 of 4 Rev. 4 10/03; MODULE DIMENSIONS AND LAYOUT
- Page 3 – Page 3 of 4 Rev. 4 10/03; ENCLOSURE DIMENSIONS
- Page 4 – Page 4 of 4 Rev. 4 10/03; Enclosure Wall Mounting
Submittal for SiteI/O 10/0E
Liebert Corporation
Page 1 of 4 Rev. 4; 10/03
DESCRIPTION:
The SiteI/O 10/0E is part of the SiteI/O-Line and is intended to be used with
SiteScan Web systems specifically. It is a 32 bit microprocessor-based device designed to monitor up to
ten thermistors, and/or dry contact type signals. Logically the device, sits on the Ethernet network,
providing the interface to SiteScan Web. This effectively creates a device that is a router / gateway and
I/O module in one device. Screw terminal blocks are provided to terminate power, communication, and
input signal wiring.
DIMENSIONS:
Module:
7 1/8" H x 6 1/4" W X 1 5/8” D
18.10cm H x 15.88cm W X 4.13cm D
Enclosure:
12”H x 14.25" W x 2.85" D
(painted steel)
419.1mm x 301.3mm x 78.6mm
POWER:
24 VAC ±10%, 50-60 Hz, 7.2 VA.
ENVIRONMENTAL
OPERATING RANGE:
0 to 130°F (-17.8 to 54.4°C); 10 to 90% relative humidity, non-condensing.
For UUKL Smoke Control Systems, 32°-120.2°F (0°-49°C); 10 to 85% relative
humidity, non-condensing.
COMMUNICATIONS:
One (1) Ethernet 10BaseT RJ-45 port
MEMORY:
1 MB flash, 1 MB RAM.
BATTERY:
Seven-year lithium battery provides a minimum of 10,000 hours of data retention
during power outages.
FAULT DETECTION:
Hardware watchdog timer.
PROTECTION:
Built-in surge and transient protection circuitry.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Emerson Network Power
Summary
Submittal for SiteI/O 10/0E Liebert Corporation Page 2 of 4 Rev. 4; 10/03 MODULE DIMENSIONS AND LAYOUT POWER WIRING DIAGRAMS
Submittal for SiteI/O 10/0E Liebert Corporation Page 3 of 4 Rev. 4; 10/03 ENCLOSURE DIMENSIONS
Submittal for SiteI/O 10/0E Liebert Corporation Page 4 of 4 Rev. 4; 10/03 Enclosure Wall Mounting Enclosure Floor Mounting