Loading the manual

Each Mobrey ultrasonic control system requires a sensor to
suit the specific application, plus a control unit.

These installation instructions cover the Mobrey control units
in the MCU200 series.

1. Sensor installation
2. Control unit installation
3. Applications:

3.1Gain adjustment
3.2Liquid level alarm
3.3Pump control and latching arms
3.4Blanket or interface detection

4. Spare parts and fault finding

Contents

Specification

Power supply

MCU 201

110/120 ±10%

220/240±10%

50-60 Hz

Installation category

MCU 201

II-IEC664 for 230V ac supply III-IEC664 for 115V ac supply

Pollution degree

MCU 201

2-IEC664

Power consumption

MCU 201

6VA approx at 240 Vac

Power supply

MCU 203

24V dc (20V Min, 30V Max) Supply must be floating or negative earth

Current consumption

MCU 203

0.1A Max

Relay output

5A at 230V ac DPCO

Relay state

Normal state selectable energised/de-energised

Relay delay

0.5,2,8,30 seconds selectable. Operates for change of relay state in
one direction only. 50msecs in other direction. (Approx.)

LED indicators

Red for alarm, Green for normal, Yellow for cable fault

LED state

Green/Red indication selectable for either sensor state

Sensors compatible

Any Mobrey ultrasonic gap, Hisens or Interface sensor

Sensor frequency

Switch selects electronics operational at either l MHz or 3.7 MHz

Cable check

Option selectable for certain sensors

External input

Used to hold relay de-energised to provide pump control

Box size

200 x 120 x 75mm

Fixing centres

188 x 188

Box rating

IP65 Polycarbonate (clear lid)

Temperature

-40

o

C to 55

o

C ambient

Holes for glands

3 off 16mmØ

EMC

Emissions: EN50081-1

Immunity: EN50082-1

Safety

EN61010-1

WARNING:
If this equipment is used in a manner not specified by the
manufacturer, the protection provided may be impaired.
All installation and commissioning of this equipment must
be carried out by electrically competent persons

Mobrey ultrasonic liquid level control or sludge
blanket or interface detection systems using
control unit type MCU200

Installation Leaflet

IP227, Rev. AA
July 07

MCU200

MCU200 Installation, Operation &
Maintenance Instructions

www.mobrey.com