Page 2 - User Manual
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 1 V2.11 Emerson Network Power Liebert GXT-MT Series 1-3 kVA UPS User Manual Version: V2.11 Revision date: September 29, 2005 Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local...
Page 3 - Contents
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 2 V2.11 Emerson Network Power Table of Contents Contents Safety Instructions 1. Description of commonly used notations 5 2. Product Introduction 6 3. System Description 7 4. Installation 8-9 5. Connection and operation 10-13 6. Opera...
Page 4 - Safety Instructions; Transport
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 3 V2.11 Emerson Network Power Safety Instructions Safety Instructions As dangerous voltages are present within the UPS, only an Emerson technician or an Emerson-authorized technician is permitted to open it. Failure to observe this c...
Page 5 - Operation
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 4 V2.11 Emerson Network Power Safety Instructions Operation • Do not disconnect the mains cable on the UPS system or the building wiring socket outlet (shockproof socket outlet) during operations since this would cancel the protectiv...
Page 7 - . Product Introduction; is an uninterruptible power supply incorporating; Model Number; Run
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 6 V2.11 Emerson Network Power 2 . Product Introduction The Liebert GXT-MT On-Line-Series is an uninterruptible power supply incorporating double-conversion technology. It provides perfect protection specifically for Novell, Windows N...
Page 8 - System Description
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 7 V2.11 Emerson Network Power System Description 3. System Description Figure 1: Display Panel Switch Function ON - Switch Turn on UPS system: By pressing the ON-Switch “I” the UPS system is turned on. Deactivate acoustic alarm: By p...
Page 9 - Unpacking and Inspection; Notes for installation
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 8 V2.11 Emerson Network Power 4. Installation Unpacking and Inspection 1) Unpack the packaging and check the package contents. The shipping package contains: z A UPS z A user manual z A communication cable z A battery cable (for Long...
Page 10 - may be burned and destroyed.
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 9 V2.11 Emerson Network Power Installation Note: Do not use the wall receptacle as the input power source for the 2/3KVA UPS, as its rated current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned a...
Page 11 - Connection and Operation; switched back on again.; Terminal Block; Nil; accordance with applicable safety regulations
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 10 V2.11 Emerson Network Power Connection and Operation 5. Connection and Operation 1) Inspection: Inspect the packaging carton and its contents for damage. Please inform the transport agency immediately should you find signs of dama...
Page 13 - to turn off the output.; Audible Alarm Mute Function:
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 12 V2.11 Emerson Network Power Connection and Operation 4) Turn On the UPS : 4.1) With utility power connected: Press “I” button continuously for more than 1 second to turn on the UPS. Then the UPS will get into self-test status firs...
Page 14 - Note
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 13 V2.11 Emerson Network Power Connection and Operation • The battery connection procedure is very important. Any incompliance may result in the risk of electric shock. Therefore, the following steps must be strictly complied with. •...
Page 15 - Operating modes for all models; Utility power mode; Note: Please follow the following steps to connect the generator; the “ON” button on the front panel is pressed; Fig 15.1 The utility power mode
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 14 V2.11 Emerson Network Power 6. Operating modes for all models 1. Utility power mode The display panel in utility power mode is shown in the following diagram. The utility power LED and the INV LED are turned on. The load level LED...
Page 16 - by the load is supplied from the utility power via internal filter.; Fig 15.2 Battery mode diagram
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 15 V2.11 Emerson Network Power 2) When the battery capacity decreases, the number of the battery capacity LEDs turned on will be reduced. If the battery voltage descends to the alarm level, the buzzer will beep once every second to r...
Page 17 - communication protocol
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 16 V2.11 Emerson Network Power 7. Communication Port RS232 Interface The following is the pin assignment and description of DB-9 connector. Pin # Description I/O 2 TXD Output 3 RXD Input 5 GND Input AS400 Interface (Option) Except fo...
Page 18 - Free Software – WinPower; Insert the CD into CD ROM.
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 17 V2.11 Emerson Network Power 8. Software Free Software – WinPower WinPower is a brand new UPS monitoring software, which provides user-friendly interface to monitor and control your UPS. This unique software provides safely auto sh...
Page 19 - The standard charging time should be at least 12 hours.
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 18 V2.11 Emerson Network Power Maintenance 9. Maintenance Operation The UPS system contains no user-serviceable parts. If the battery service life has been exceeded, the batteries must be replaced. In this case please contact your de...
Page 20 - Notes for Battery Disposal and Battery Replacement
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 19 V2.11 Emerson Network Power Maintenance Notes for Battery Disposal and Battery Replacement 1) Before disposing of batteries, remove conductive jewelry such as necklace, wrist watches and rings. 2) If it is necessary to replace any...
Page 21 - Trouble Shooting; Problem Possible
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 20 V2.11 Emerson Network Power Trouble Shooting 10. Trouble Shooting If the UPS system does not operate correctly, please attempt to solve the problem using the table below. Problem Possible cause Remedy No indication, no warning ton...
Page 24 - Appendix
Liebert GXTMT Series Installation and User Manual 1-3 kVA UPS Page 23 V2.11 Emerson Network Power Appendix - Back Panel Back View of GXT1000-MT and GXT1000L-MT Figure 1: Back View of 1KVA & 1KVAS Back View of GXT2000-MT and GXT2000L-MT Appendix: Back Panel
Page 26 - Emerson Network Power.