Page 2 - NOTE; Tables i; GLYCOOL
P RODUCT N OMENCLATURE NOTE Tables i , ii and iii show nomenclature for the complete range of all available product options. Not all combinations are possible. For assistance, contact your local dealer, Liebert representative or call 1-800-543-2778. Table i Product model information B F 042 A — A A ...
Page 3 - TABLE OF CONTENTS
i TABLE OF CONTENTS P RODUCT N OMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I NSIDE F RONT C OVER 1.0 D EDICATED , P RECISE E NVIRONMENTAL C ONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 Temperature Control . . . . . . . . . ....
Page 4 - ii; GLYCOOL S
ii 5.2 Chilled Water System—Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5.2.1 Chilled Water Flow Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 5.2.2 High Pressure . . . . . . . ...
Page 5 - iii; Liebert SiteScan; W E
iii 10.3 SCR Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 10.4 High-Efficiency Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 10.5 H...
Page 6 - iv; FIGURES
iv FIGURES Figure 1 Unit configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Figure 2 Unit configurations, continued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 9 - Dedicated, Precise Environmental Control; EDICATED; ratios required by electronic computer equipment.
Dedicated, Precise Environmental Control 1 1.0 D EDICATED , P RECISE E NVIRONMENTAL C ONTROL For sensitive electronics, environmental control is more than simple cooling. “Comfort” air condition- ing systems are designed for the comfort of people and simply cannot provide the kind of environment req...
Page 10 - nated management of temperature, humidity and air filtration.; Liebert Challenger ITR; you to select temperature and humidity ranges.; Multiple Configurations to Fit a Variety of Spaces
Precision Environmental Control for Industrial, Telecommunications, Medical and Data Processing Equipment 2 2.0 P RECISION E NVIRONMENTAL C ONTROL FOR I NDUSTRIAL , T ELECOMMUNICATIONS , M EDICAL AND D ATA P ROCESSING E QUIPMENT Data processing power is moving from the specialized environment of the...
Page 13 - Local Monitoring Systems; OCAL; Control
Local Monitoring Systems 5 3.0 L OCAL M ONITORING S YSTEMS Two levels of microprocessor control systems are available providing precise control and monitoring of the critical space.The Advanced Microprocessor is standard, and the Advanced Microprocessor with Graphics is optional. The main control fu...
Page 14 - Logging; and date stamp for each event; Alarms; Figure 3; Graphical Displays—Advanced Graphic Control Only; Figure 4
Local Monitoring Systems 6 3.6 Logging • Alarm history log: The Advanced Microprocessor displays the 10 most recent alarms. The Advanced Microprocessor with Graphics displays the most recent 60 alarms. Both provide a time and date stamp for each event • Run time log: Displays run time and hours for ...
Page 15 - Standard Features—All Systems; TANDARD; changed quickly and easily through the front of the unit.
Standard Features—All Systems 7 4.0 S TANDARD F EATURES —A LL S YSTEMS 4.1 Cabinet and Frame The frame, 14 gauge, MIG welded tubular and formed steel, provides maximum support while 1" (25.4mm) deep steel panels with 1-1/2 lb. (.68 kg) insulation protect and quiet the system. The front door can ...
Page 16 - Table 1; Voltage
Standard Features—All Systems 8 4.6.1 Condensate Pump The condensate pump, mounted in the bottom of most units, is used for unit drain water only. The condensate pump is complete with sump, motor and pump assembly and automatic control.The standard model has single float. A dual-float condensate pum...
Page 17 - Chilled Water System—Standard and Optional Features; Chilled Water System—Standard Features; manufactured to the highest standards in the industry.; Chilled Water System—Optional Features; The valve is designed for 400 psig (2758 kPa) water pressure.
Chilled Water System—Standard and Optional Features 9 5.0 C HILLED W ATER S YSTEM —S TANDARD AND O PTIONAL F EATURES 5.1 Chilled Water System—Standard Features 5.1.1 Cooling Coil The chilled water cooling coil is designed for closed-loop applications using properly maintained water. It is constructe...
Page 18 - Refrigeration Systems; EFRIGERATION; Self-Contained Systems; Water, Glycol and GLYCOOL; Split Systems
Refrigeration Systems 10 6.0 R EFRIGERATION S YSTEMS Two versions are available: • Self-Contained Systems• Split Systems 6.1 Self-Contained Systems These systems feature a scroll compressor and controls, expansion valve, hot gas bypass and evapora- tor coil in the room unit. Air-Cooled models also i...
Page 19 - Air-Cooled System—Standard and Optional Features; tion with a low pressure switch.; traditional condensers with acoustical shielding.; Figure 5
Air-Cooled System—Standard and Optional Features 11 7.0 A IR -C OOLED S YSTEM —S TANDARD AND O PTIONAL F EATURES 7.1 Air-Cooled, Self-Contained Systems—Standard Features 7.1.1 Pump Down Control The compressor pump-down control is accomplished by a liquid-line solenoid valve used in conjunc- tion wit...
Page 20 - Air-Cooled Split Systems—Standard Features; Figure 6; Propeller Fan Condensing Unit Options; This unit is available in these optional configurations:; Air-Cooled Split Systems—Optional Features; allows turning off the Challenger ITR for main-
Air-Cooled System—Standard and Optional Features 12 7.3 Air-Cooled Split Systems—Standard Features 7.3.1 Centrifugal Fan, Condensing Unit The centrifugal condensing unit’s copper-tube, aluminum-fin coil is equipped with low-temperature controls to ensure year-round operation to -20°F (-29°C). The co...
Page 21 - Water/Glycol-Cooled Systems—Standard and Optional Features; Water/Glycol Self-Contained Systems—Standard Features; using a minimum of liquid and low total pressure drop.; Water/Glycol Split System—Standard Features
Water/Glycol-Cooled Systems—Standard and Optional Features 13 8.0 W ATER /G LYCOL -C OOLED S YSTEMS —S TANDARD AND O PTIONAL F EATURES 8.1 Water/Glycol Self-Contained Systems—Standard Features Liquid-Cooled Condensers A co-axial condenser provides ample capacity to handle the heat rejection needs of...
Page 22 - High Pressure; cations with large static heads.; Factory Installed Non-Fused Disconnect Switch; tower loop or other open water system.; Fan Speed Control Drycooler; tested control panel reduces installation time.; Glycol Pump; proof enclosure. Optional Equipment—See
Water/Glycol-Cooled Systems—Standard and Optional Features 14 8.4 Water/Glycol-Cooled, Split System—Optional Features High Pressure The high pressure option for the condenser circuit consists of a two-way or three-way water regulat- ing valve and condenser rated at 350 psig (2413 kPa) water pressure...
Page 23 - GLYCOOL Systems—Standard and Optional Features; YSTEMS; GLYCOOL—Self-Contained Models Only; microprocessor control that “free-cooling” is available.
GLYCOOL Systems—Standard and Optional Features 15 9.0 GLYCOOL S YSTEMS —S TANDARD AND O PTIONAL F EATURES 9.1 GLYCOOL—Self-Contained Models Only The Liebert GLYCOOL free-cooling system is integrated with a glycol-cooled Liebert Challenger ITR.At outdoor temperatures below 35°F (1.6°C), the Econ-O-Co...
Page 24 - Figure 7; Glycol and GLYCOOL-Cooled—Optional Equipment; Dual Pump Package; Quiet-Line Drycoolers; traditional drycoolers with acoustical shielding.
GLYCOOL Systems—Standard and Optional Features 16 9.2.5 Drycooler The Liebert manufactured drycooler is constructed of aluminum with a copper tube aluminum fin coil. The low profile design features multiple direct drive propeller type fans, balanced to the heat rejection load. An integral, factory w...
Page 25 - Optional Equipment—All Systems; PTIONAL; Steam Generating Humidifier; canister should be changed.; Figure 8; Steam generating humidifier; Figure 9
Optional Equipment—All Systems 17 10.0 O PTIONAL E QUIPMENT —A LL S YSTEMS 10.1 Steam Generating Humidifier Clean, pure steam is generated in a disposable canister that is complete with supply and drain valves, electronic controls and steam distributor. The humidifier is provided with an automatic f...
Page 26 - High External Static Blowers; charge styles available.
Optional Equipment—All Systems 18 10.3 SCR Reheat This reheat uses stainless steel elements and also includes the necessary sensors and controls to pro- vide variable heat output to help maintain tighter control of room conditions, especially in lightly loaded applications. (Contact factory for avai...
Page 27 - Firestat
Optional Equipment—All Systems 19 10.9 Smoke Detector The smoke detector senses the return air, shuts down the unit upon detection, and sends visual and audible alarm. Dry contacts are available for a remote customer alarm. This smoke detector is not intended to function as or replace any room smoke...
Page 28 - Comprehensive Monitoring Systems—Optional; OMPREHENSIVE; toring, control and leak detection devices.; Enterprise Monitoring Systems; users easy access from anywhere at anytime.; Network Monitoring Systems; The Liebert IntelliSlot; Stand-Alone Monitoring and Leak Detection Solutions; • Sequence the operation of multiple environmental units.
Comprehensive Monitoring Systems—Optional 20 11.0 C OMPREHENSIVE M ONITORING S YSTEMS —O PTIONAL You will find a full range of monitoring and control systems, communications modules designed to interface Liebert equipment with a variety of building management systems, plus stand-alone moni- toring, ...
Page 29 - Leak Detection Modules; • Provide quick detection and location of hazardous fluid leaks.; Discrete Output Interface Card; Enterprise Monitoring
Comprehensive Monitoring Systems—Optional 21 Leak Detection Modules • Provide quick detection and location of hazardous fluid leaks. Discrete Output Interface Card • Straightforward way to tie environmental units to a building management system or alarm panel. Figure 10 Monitoring configurations Ent...
Page 30 - Comprehensive Monitoring Solutions—Optional; Liebert SiteScan; management system and up to 12 Liebert units via Modbus or BACnet.; Adapter; alarm notification to pagers.
Comprehensive Monitoring Solutions—Optional 22 12.0 C OMPREHENSIVE M ONITORING S OLUTIONS —O PTIONAL 12.1 Liebert SiteScan ® Web Liebert SiteScan Web is a monitoring solution for critical environments that utilize a facility-view approach. The system enables communications from Liebert environmental...
Page 31 - Universal Monitor; log, an event log and a trend log. The Universal Monitor has a local
Comprehensive Monitoring Solutions—Optional 23 12.8 Universal Monitor The Universal Monitor keeps personnel on-site and at remote locations apprised of the status of equipment through local alarming and remote paging services. The panel will interface with anything that closes an electrical contact ...
Page 32 - System Data; YSTEM; Table 2; System Type; Indoor Unit
System Data 24 13.0 S YSTEM D ATA Table 2 Liebert Challenger ITR air-cooled data—60 Hz System Type BR = Horizontal Flow Self-Contained Split Systems w/Outdoor Prop-Fan Condensing Unit w/Indoor Centrifugal Condensing Unit Indoor Unit BR 067A BR 060E BR 060E Net Capacity Data BTU/H kW BTU/H kW BTU/H k...
Page 33 - Table 3
System Data 25 Table 3 Liebert Challenger ITR air-cooled data—60 Hz (continued) System Type Self-Contained Split Systems w/Outdoor Prop-Fan Condensing Unit w/Indoor Centrifugal Condensing Unit Indoor Unit BR 067A BR 060E BR 060E Infrared Humidifier - Standard Capacity - lb/hr (kg/hr) 11 (5) 11 (5) 1...
Page 34 - Table 4; BR = Horizontal Flow
System Data 26 Table 4 Liebert Challenger ITR air-cooled data—50 Hz System Type BR = Horizontal Flow Self-Contained Split Systems w/Outdoor Prop-Fan Condensing Unit w/Indoor Centrifugal Condensing Unit Indoor Unit BR 065A BR 059E BR 059E Net Capacity Data kW BTU/H kW BTU/H kW BTU/H 37.8°C DB, 21.1°C...
Page 35 - Table 5
System Data 27 Table 5 Liebert Challenger ITR air-cooled data—50Hz (continued) System Type Self-Contained Split Systems w/Outdoor Prop-Fan Condensing Unit w/Indoor Centrifugal Condensing Unit Indoor Unit BR 065A BR 059E BR 059E Infrared Humidifier - Standard Capacity - kg/hr (lb/hr) 5 (11) 5 (11) 5 ...
Page 36 - Table 6
System Data 28 Table 6 Liebert Challenger ITR water cooled data, 60 Hz System Type BR = Horizontal Flow Self-Contained Split Systems Indoor Unit BR 071WG BR 060E Net Capacity Data BTU/H kW BTU/H kW 100°F DB, 70°F WB (37.8°C DB, 21.1°C WB) 20% RH Total 82,900 24.3 79,000 23.1 Sensible 82,900 24.3 79,...
Page 37 - Table 7
System Data 29 Table 7 Liebert Challenger ITR water cooled data, 60 Hz (continued) System Type Self-Contained Split Systems Indoor Unit BR 071WG BR 060E Infrared Humidifier - Standard Capacity, lb/hr (kg/hr) 11 (5) 11 (5) kW 4.8 4.8 Steam Generating Humidifier - Optional Capacity, lb/hr (kg/hr) 11 (...
Page 38 - Table 8
System Data 30 Table 8 Liebert Challenger ITR water cooled data, 50 Hz System Type BR = Horizontal Flow Self-Contained Split Systems Indoor Unit BR 070WG BR 059E Net Capacity Data kW BTU/H kW BTU/H 37.8ºC DB, 21.1ºC WB (100ºF DB, 70ºF WB) 20% RH Total 24.0 81,800 23.1 78,800 Sensible 24.0 81,800 23....
Page 39 - Table 9
System Data 31 Table 9 Liebert Challenger ITR water cooled data, 50 Hz (continued) System Type Self-Contained Split Systems Indoor Unit BR 070WG BR 059E Infrared Humidifier - Standard Capacity - kg/hr (lb/hr) 5 (11) 5 (11) kW 4.8 4.8 Steam Generating Humidifier - Optional Capacity, kg/hr (lb/hr) 5 (...
Page 40 - Liebert Challenger ITR glycol cooled data, 60 Hz
System Data 32 Table 10 Liebert Challenger ITR glycol cooled data, 60 Hz System Type BR = Horizontal Flow BM = Horizontal Flow with Econ-O-Coil Glycol Cooled GLYCOOL Self-Contained Split Systems Self Contained Indoor Unit BR 071WG BR 060E BM 061G Net Capacity Data BTU/H kW BTU/H kW BTU/H kW 100°F DB...
Page 42 - Liebert Challenger ITR glycol cooled data, 50 Hz
System Data 34 Table 12 Liebert Challenger ITR glycol cooled data, 50 Hz System Type BR = Horizontal Flow BM = Horizontal Flow with Econ-O-Coil Glycol Cooled GLYCOOL Self-Contained Split Systems Self Contained Indoor Unit BR 070WG BR 059E BM 058G Net Capacity Data kW BTU/H kW BTU/H kW BTU/H 37.8ºC D...
Page 44 - Liebert Challenger ITR chilled water data, 60 Hz
System Data 36 Table 14 Liebert Challenger ITR chilled water data, 60 Hz Capacity Data BTU/H (kW) @ 45°F (7.2°C) EWT, 10°F (5.6°C) Water Rise; Net Capacity DataIndoor Unit BR = Horizontal Flow BR 102C Indoor Unit BR 102C 100ºF DB, 70ºF WB (37.8ºC DB, 21.1ºC WB) 20% RH, 12°F (6.7°C) Water Rise Fan Da...
Page 45 - Liebert Challenger ITR chilled water data, 50 Hz
System Data 37 Table 15 Liebert Challenger ITR chilled water data, 50 Hz Capacity Data kW (BTU/H) @ 7.2°C (45°F ) EWT, 5.6°C (10°F) Water Rise; Net Capacity DataIndoor Unit BR = Horizontal Flow BR 101C Indoor Unit BR 101C 37.8ºC DB, 21.1ºC WB (100ºF DB, 70ºF WB) 20% RH, 6.7°C (12°F) Water Rise Fan D...
Page 46 - Dimensional Drawings; IMENSIONAL; UNIT TOP VIEW
Dimensional Drawings 38 14.0 D IMENSIONAL D RAWINGS Figure 11 Cabinet and floor planning dimensional data—Horizontal flow models DPN001523Pg. 2, Rev. 1 Filter Accessby Opening Door UNITTOP VIEW 32-1/2"(826mm) 5/8" (16mm) 9-5/8" (244mm) 8-1/2" (216mm) 31-1/2" (800mm) 1-7/8" (4...
Page 47 - Figure 12 Cabinet and floor planning dimensional data; OPTIONAL FLOOR STAND; Air Intake
Dimensional Drawings 39 Figure 12 Cabinet and floor planning dimensional data Figure 13 Cabinet and floor planning dimensional data—Split system—5-ton centrifugal fan condensing unit See SpecificationSheet for floor standheight ordered OPTIONAL FLOOR STAND DIMENSIONAL DATA 1" (25mm) 30-1/2" ...
Page 48 - condensing unit; Model
Dimensional Drawings 40 Figure 14 Cabinet and floor planning dimensional data—Split system—5-ton water/glycol-cooled condensing unit Model Net Weight lbs (kg) 60 Hz 50 Hz MC_69W MC_68W 282 (128)
Page 49 - Outdoor Propeller Fan Condensing Unit
Dimensional Drawings 41 Figure 15 Cabinet and floor planning dimensional data—Split System—Propeller fan condensing unit A B C Fan Rotation CCW (left side) SL-11081 Pg 4 Left Air Intake Shaded area indicates a minimum clearance of 18" (457mm) for proper air flow Removable (front) panel foraccess...
Page 50 - discharge; Model Numbers
Dimensional Drawings 42 Figure 16 Cabinet and floor planning dimensional data—Propeller fan condensing modules—Vertical air discharge Figure 17 Cabinet and floor planning dimensional data—Self-contained system—Air-cooled condenser or drycooler Shaded area indicatesa recommended clearanceof 24" (...
Page 51 - Electrical Data; LECTRICAL; Liebert Challenger ITR electrical data
Electrical Data 43 15.0 E LECTRICAL D ATA Table 16 Liebert Challenger ITR electrical data 1 —60 Hz Model Type Self-Contained Split System Evaporator or Chilled Water BR067A, BR071WG, BM061G BR060E, BR102C Voltage All Voltages Are 3 Phase Unless Noted Otherwise 208 230 460 575 208 230 460 575 With El...
Page 52 - Electric Reheat and Humidifier (Infrared or Steam
Electrical Data 44 Table 17 Self-contained with SCR reheat * Voltage (3, 60 Hz) 208 230 460 575 Electric Reheat and Humidifier (Infrared or Steam Generating)Motor 1.5 hp (1.1 kW) FLA 81.3 76.1 38.1 N/A WSA 96.9 91.1 45.5 N/A OPD 100 100 50 N/A Motor 2.0 hp (1.5 kW) FLA 83.1 77.7 38.9 N/A WSA 98.7 92...
Page 53 - Scroll compressor and main fan (for comparison purposes only) *
Electrical Data 45 Table 18 Scroll compressor and main fan (for comparison purposes only) * Voltage (3, 60 Hz) 208 230 460 575 Scroll Compressor RLA 20.7 20.7 10.0 7.4 LRA 128.0 128.0 63.0 49.0 Main FanMotor 1.5 hp (1.1 kW) RLA 5.7 5.2 2.6 2.1 LRA 35.9 31.2 15.6 12.6 Motor 2.0 hp (1.5 kW) RLA 7.5 6....
Page 54 - Outdoor condensing units—Quiet-Line
Electrical Data 46 Table 20 Outdoor condensing units—Quiet-Line Electrical Data 60 Hz, Quiet-Line, 95°F (35°C) Voltage Model PFHZ67A-_L 208/230-3-60 FLA 21.1 WSA 25.9 OPD 45.0 380-3-60 FLA 12.5 WSA 15.2 OPD 25.0 460-3-60 FLA 10.9 WSA 13.4 OPD 20.0 575-3-60 FLA 8.8 WSA 10.8 OPD 15.0 Table 21 Indoor c...
Page 55 - Fan speed control condensers *; Liebert Lee-Temp receiver heater pads for use w/CSL condensers
Electrical Data 47 Table 23 Fan speed control condensers * 95°F (35°C) Ambient, 1 Phase - 60 Hz CSF 104 Voltage 208/230 460 575 FLA 4.8 2.5 1.9 WSA 6.0 3.1 2.4 OPD 15.0 15.0 15.0 * Contact factory for 380-3-60 data. Table 24 Liebert Lee-Temp condensers * 95°F (35°C) Ambient, 3 Phase - 60 Hz CSL104 V...
Page 56 - Liebert Challenger ITR electrical data—50 Hz
Electrical Data 48 Table 27 Liebert Challenger ITR electrical data—50 Hz Model Type Self-Contained Split System Evaporator or Chilled Water B*065A, 070WG, 058G B*059E, 101C 3 Phase, 50Hz Voltage 200 230 380/415 200 230 380/415 With Electric Reheat and Humidifier (Infrared or Steam Generating) (Note:...
Page 57 - Self-contained with SCR reheat; Scroll compressor and main fan (for comparison only)
Electrical Data 49 Table 28 Self-contained with SCR reheat Voltage (3, 50 Hz) 200 230 380/415 Electric Reheat and Humidifier (Infrared or Steam Generating) Motor 1.1 kW (1.5 hp) FLA 78.8 75.5 40.8 Motor 1.5 kW (2.0 hp) FLA 80.5 77.0 41.6 Motor 2.2 kW (3.0 hp) FLA 83.6 79.7 43.2 Electric Reheat Only ...
Page 59 - DSF Model; Pumps; hp
Electrical Data 51 Table 36 Drycooler only - 35°C (95°F) ambient, three-phase Voltage (3, 50Hz) 200/230 380/415 DSF Model 112 112 FLA 3.5 1.7 DSO Model 112 112 FLA 3.5 1.7 DSO Model 174 174 FLA 7.0 3.4 Table 37 Drycooler only - 35°C (95°F) ambient, single phase Voltage (1, 50Hz) 200/230 380/415 DSF ...
Page 60 - Summary; and rear of the unit.
Electrical Data 52 G UIDE S PECIFICATIONS —N OMINAL 23 OR 33 K W E NVIRONMENTAL C ONTROL S YSTEM 1.0 G ENERAL 1.1 Summary These specifications describe requirements for an environmental control system. The system shall be designed to maintain temperature and relative humidity conditions within the r...
Page 61 - and time, and four analog inputs from sensors provided by others.; or from the central site monitoring system.; Sequential Load Activation; devices to bypass fluid into the coil on a programmed basis.; Front Monitor Display Panel; form. No symbols or codes shall be acceptable.
Electrical Data 53 2.1.4 Advanced Microprocessor Control (Standard) The Advanced control processor shall be microprocessor based with a front monitor LCD display panel and control keys for user inputs. The controls shall be menu driven with on-screen prompts for easy user operation. The system shall...
Page 62 - time delay of 0 to 255 seconds.
Electrical Data 54 Alarms The microprocessor shall activate an audible and visual alarm in event of any of the following condi- tions: • High Temperature• Low Temperature• High Humidity• Low Humidity• Short Cycle• Compressor Overload (Optional)• Main Fan Overload (Optional)• Humidifier Problem• High...
Page 65 - Data Collection; The control shall display the following graphical data:; Communications; with a 2-way motorized control valve and cleanable Y-strainer.
Electrical Data 57 Data Collection The control system shall maintain accumulative operating hours of compressor, reheat, humidifier, fan motor, Econ-O-Coil, and heat rejection. The sixty most recent alarms shall also be retained. Graphing The control shall display the following graphical data: • Tem...
Page 66 - 5 Remote Sensor Installation Location; highest point that equipment will draw in cooled air.; Direct Expansion Self-Contained Systems; Direct Expansion Coil
Electrical Data 58 2.1.12 Plenum The unit shall be supplied with a (2 way) (3 way) (4 way) (low-profile, cold-aisle) air discharge ple- num. The plenum shall be 18 in. (457mm) high or less, insulated and powder painted the same color as the room unit. 2.1.13 Disconnect Switch, Locking Type The manua...
Page 67 - as an integral feature of the electronic control panel.; Indoor Unit Condenser; Design Pressure; cooling tower loop or other open water system.
Electrical Data 59 Fan Speed Control (FSC) Head Pressure Control (Standard) The winter control system for the air-cooled condenser shall be Liebert Fan Speed Control (FSC). The variable speed motor shall turn on at 10% of the supply voltage and modulate in response to head pressure to a full speed o...
Page 68 - Outdoor Unit; Three-way GLYCOOL Valve; ture and relative humidity.; Glycol Condenser
Electrical Data 60 Outdoor Unit Propeller Fan Drycooler (Standard) The Liebert manufactured drycooler shall be the low profile, slow speed, direct drive propeller fan type. The drycooler shall be constructed of aluminum and contain a copper tube aluminum fin coil with an integral electric control pa...
Page 69 - Direct Expansion Split Systems; Centrifugal Fan Condensing Unit
Electrical Data 61 Propeller Fan Drycooler (Standard) The Liebert manufactured drycooler shall be the low profile, slow speed, direct drive propeller fan type. The drycooler shall be constructed of aluminum and contain a copper tube aluminum fin coil with an integral electric control panel. The dryc...
Page 70 - Propeller Fan Condensing Unit; evaporators for use on the 5 ton condensing units.; Water or Glycol-Cooled Condensing Unit; applied to a cooling tower loop or other open water system.
Electrical Data 62 Propeller Fan Condensing Unit The condenser coil shall be constructed of copper tubes and aluminum fins with a direct drive propel- ler type fan and shall include a scroll compressor, high pressure switch, Liebert Lee-Temp receiver, head pressure control valve, and liquid line sol...
Page 71 - Chilled Water Self-Contained Systems Chilled Water Coil; water around the coil.; switch shall be factory mounted and wired.
Electrical Data 63 Single Glycol Pump Package (Standard) This system shall be provided with a centrifugal pump mounted in a weatherproof and vented enclo- sure. The pump shall be rated for GPM (l/s) at _____ ft. of head (kPa), and operate on _____ Volt, 3 phase, _____ Hz. Dual Glycol Pump Package (O...
Page 72 - Comprehensive Monitoring Solutions; XECUTION; Installation of Environmental Control Units; recommended clearances.; Field Quality Control; controls and demonstrate compliance with requirements.
Electrical Data 64 2.5 Comprehensive Monitoring Solutions (For detailed Guide Specifications on these products, refer to information posted at www.liebert.com) • Liebert SiteScan Web System • Liebert SiteLink Module • Liebert Nform • Liebert IntelliSlot Web/485 Card With Adapter and Liebert IntelliS...
Page 74 - Precision Cooling
Ensuring The High AvailabilityOf Mission-Critical Data And Applications. Emerson Network Power, the global leader in enabling business-criticalcontinuity, ensures network resiliency and adaptability througha family of technologies—including Liebert power and coolingtechnologies—that protect and supp...