www.Fisher.com

D102796X012

FIELDVUE

R

HF300 Series HART

R

Filters

Introduction

Scope of Manual

This instruction manual includes installation and

maintenance information for the FIELDVUE

HF300

Series HART

Filters. Refer to separate manuals for

additional information on other FIELDVUE products

used with the HART filters, such as DVC6000 Series

digital valve controllers, and Type 2530H1 HART

interchange multiplexers.

Control system refers to a distributed control system

(DCS), programmable logic controller (PLC), or a

stand-alone controller that provides a control signal

to the FIELDVUE instrument.

Do not install, operate, or maintain HF300 Series

HART filters without first

being fully trained and

qualified in valve, actuator and accessory

installation, operation and maintenance and

carefully reading and understanding the contents of

the manual. If you have any questions about these

instructions, contact your Emerson Process

Management

sales office before proceeding.

Description

HF300 Series HART filters, shown in figure 1, are

used with HART-based FIELDVUE instrumentation,

such as DVC6000 Series digital valve controllers.

These filters are used when this instrumentation is

connected to a 4 to 20 mA DC control system output

that was not designed for the HART (Highway

Addressable Remote Transducer) communication

protocol.

The HF300 Series HART filters consist of the Type

HF340 HART filter that provides filtering and

isolation between the control system and FIELDVUE

instrument and the Type HF341 communication tap.

The Type HF341 does not provide any filtering. It is

simply a straight through device that provides a

convenient connection for HART communication.

FIELD INSTRUMENT CONNECTIONS (FLD)

HART COMMUNICATION

CONNECTIONS (COMM)

CONTROL SYSTEM

CONNECTIONS (SYS)

W8283 / IL

Figure 1. FIELDVUE

HF300 Series HART

Filters

The Type HF340 HART filter is a passive device that

is inserted in-line with both wires of a HART 4 to 20

mA DC output loop. The purpose of the filter is to

effectively isolate the control system analog output

from modulated HART communication signals. The

filter receives a 4 to 20 mA DC current signal from

the control system, which it shunts with a capacitor

and then passes through an inductor. The low AC

impedance of the capacitor prevents sudden

changes in the control system current output from

interfering with the HART communication. The high

AC impedance of the inductor permits HART

communication on the instrument side of the filter. It

also prevents the voltage modulation in the HART

loop from being seen by, or having an affect on, the

control system output. The filter introduces a

maximum input-to-output voltage drop of 2 volts DC

at 20 mA as long as the output load voltage is less

than 14 volts DC.

Instruction Manual

Form 5715

June 2007

HF300 Series

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Instruction Manual; Specifications

HF300 Series Instruction Manual Form 5715 June 2007 2 Table 1. Specifications Product Types Type HF340: Standard 35 mm DIN rail mounting with filtering components. Type HF341: Standard 35 mm DIN rail mounting without filtering components (straight through with capacitor blocking on COMM terminals). ...

Page 3 - Installation; Shields

HF300 Series Instruction Manual Form 5715 June 2007 3 CONTROL SYSTEM OUTPUT TERMINALS TYPE 2530H1 HART INTERCHANGE MULTIPLEXER OR OTHER HART MULTIPLEXER FIELD DEVICES + + + − − − FLD TERMINALS COMM TERMINALS HF300 SERIES HART FILTER + + − − SYS TERMINALS HART MULTIPLEXER NETWORK 375 FIELD COMMUNICAT...

Page 4 - Corrective Maintenance

HF300 Series Instruction Manual Form 5715 June 2007 4 Corrective Maintenance The most likely malfunction of a loop containing an HF300 Series HART filter is reverse polarity installation of one of the wire pairs. The Type HF340 filter will work with either polarity, but misconnection could result in...