www.Fisher.com
Module Definitions, IO Bytes, and Data Length
for FIELDVUE™ DVC6200p PROFIBUS PA Digital
Valve Controller
Contents
AO Module
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AI Module
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DO Module
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DI Module
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A GSD file contains information about the device capabilities.
Modules are defined within the GSD. Each module represents a distinct sub set of parameter values for a specific
function block in the DVC6200p; each function block can have one or more modules defined.
Slots originate in the Class 1 Master (Configuration Host) and represent an address range of bytes. Typically, slots will
define address ranges for Input values (I) and other address ranges for Output values (Q).
If a Slot is not used it must NOT be null or blank. It must be assigned as an Empty Module.
Modules are assigned to specific Slots. For example any of the AO modules must be assigned to Slot 1. If a DO module
is required it must be assigned to Slot 3. The slot assignments are defined in the device GSD file
FC051037.gsd
.
Slot Definition
Module
Slot (1) = AO
2
1
1,2,3,4,5,6,7,8,9,10,11,12,13,14,15
Slot (2) = AI
16 1,16,17
Slot (3) = DO
18 1,18,19,20,21,22,23,24
Slot (4) = DI 1
1 25 1,25
Slot (5) = DI 2
2 25 1,25
Note
The AO module is always assigned to the first slot. In some systems the first slot is defined as 0; consequently the AO module will
be defined as Slot 0, the AI module will be defined as Slot 1, etc.
Instruction Manual Supplement
D104019X012
DVC6200p
November 2014
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
Instruction Manual Supplement D104019X012 DVC6200p November 2014 2 The example below shows an AO Module, number 5, assigned to Slot 1. The slots that are not used have been assignedas an EMPTY_MODULE. Different Class 1 Masters will present different views and may have a different number ofconfigurab...
Instruction Manual Supplement D104019X012 DVC6200p November 2014 3 AO Module Slot 1 Assignment Module Module Name Input Bytes Output Bytes 1 EMPTY_MODULE 0 0 2 AO_SP(S) 0 5 3 AO_SP(L) 0 5 4 AO_SP_RDBK_POSD(S) 7 5 5 AO_SP_RDBK_POSD(L) 7 5 6 AO_SP_CKBK(S) 3 5 7 AO_SP_CKBK(L) 3 5 8 AO_SP_RDBK_POSD_CKBK...
Instruction Manual Supplement D104019X012 DVC6200p November 2014 4 Module 4 AO_SP_RDBK_POSD(S) Module Definition AO_SP_RDBK_POSD(S) Input data length 7 Output data length 5 Parameter data length 0 Identifiers 0x96, 0xA4 Module 5 AO_SP_RDBK_POSD(L) Module Definition AO_SP_RDBK_POSD(L) Input data leng...