Emerson FIELDVUEDVC6200p- User Manual

Emerson FIELDVUEDVC6200p

Emerson FIELDVUEDVC6200p– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
Page: / 10

Table of Contents:

  • Page 2 – Instruction Manual Supplement
  • Page 3 – AO Module; Slot 1 Assignment; Module 2
  • Page 4 – Module 6
  • Page 8 – AI Module; Slot 2 Assignment
  • Page 9 – DO Module; Slot 3 Assignment
  • Page 10 – DI Module
Loading the manual

www.Fisher.com

Module Definitions, IO Bytes, and Data Length
for FIELDVUE™ DVC6200p PROFIBUS PA Digital
Valve Controller

Contents

AO Module

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

AI Module

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

DO Module

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

DI Module

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A GSD file contains information about the device capabilities.

Modules are defined within the GSD. Each module represents a distinct sub set of parameter values for a specific
function block in the DVC6200p; each function block can have one or more modules defined.

Slots originate in the Class 1 Master (Configuration Host) and represent an address range of bytes. Typically, slots will
define address ranges for Input values (I) and other address ranges for Output values (Q).

If a Slot is not used it must NOT be null or blank. It must be assigned as an Empty Module.

Modules are assigned to specific Slots. For example any of the AO modules must be assigned to Slot 1. If a DO module
is required it must be assigned to Slot 3. The slot assignments are defined in the device GSD file

FC051037.gsd

.

Slot Definition

Module

Slot (1) = AO

2

1

1,2,3,4,5,6,7,8,9,10,11,12,13,14,15

Slot (2) = AI

16 1,16,17

Slot (3) = DO

18 1,18,19,20,21,22,23,24

Slot (4) = DI 1

1 25 1,25

Slot (5) = DI 2

2 25 1,25

Note

The AO module is always assigned to the first slot. In some systems the first slot is defined as 0; consequently the AO module will
be defined as Slot 0, the AI module will be defined as Slot 1, etc.

Instruction Manual Supplement

D104019X012

DVC6200p

November 2014

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Instruction Manual Supplement

Instruction Manual Supplement D104019X012 DVC6200p November 2014 2 The example below shows an AO Module, number 5, assigned to Slot 1. The slots that are not used have been assignedas an EMPTY_MODULE. Different Class 1 Masters will present different views and may have a different number ofconfigurab...

Page 3 - AO Module; Slot 1 Assignment; Module 2

Instruction Manual Supplement D104019X012 DVC6200p November 2014 3 AO Module Slot 1 Assignment Module Module Name Input Bytes Output Bytes 1 EMPTY_MODULE 0 0 2 AO_SP(S) 0 5 3 AO_SP(L) 0 5 4 AO_SP_RDBK_POSD(S) 7 5 5 AO_SP_RDBK_POSD(L) 7 5 6 AO_SP_CKBK(S) 3 5 7 AO_SP_CKBK(L) 3 5 8 AO_SP_RDBK_POSD_CKBK...

Page 4 - Module 6

Instruction Manual Supplement D104019X012 DVC6200p November 2014 4 Module 4 AO_SP_RDBK_POSD(S) Module Definition AO_SP_RDBK_POSD(S) Input data length 7 Output data length 5 Parameter data length 0 Identifiers 0x96, 0xA4 Module 5 AO_SP_RDBK_POSD(L) Module Definition AO_SP_RDBK_POSD(L) Input data leng...

Other Emerson Models