- Page 2 – Catalog Number Identification
- Page 3 – Rating Label; Do not exceed the values on the rating label.; Nameplate
- Page 4 – Wiring Diagram
- Page 5 – INSTALLATION; Controller Ground; Functional Test; – Manual Operation Test
- Page 6 – – Manual Operation; for maintenance purposes only; OPEN
- Page 7 – – Voltage Checks; Note; Refer to Section 3 of; – Electrical Operation
- Page 8 – Close the enclosure door first !; Transfer Test; This completes the Functional Test of the ADTS.; Transfer Control
- Page 9 – SECTION 2 TESTING & SERVICE; TRANSFER TEST; Electrical Operation; PREVENTIVE MAINTENANCE
- Page 10 – MANUAL LOAD TRANSFER; Note any optional accessories that may be furnished
- Page 12 – INDEX
381333–129 C
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
For sales or service call 1 800 800–2726 (ASCO)
www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
Operator’s
Manual
7000 Series ADTS
Automatic Delayed–Transition Transfer Switches
E–design 150–400A, F–design 600–800A,
G–design 1000–4000A, F–design 3000–4000A,
TABLE OF CONTENTS
section-page
INSTALLATION
1-1
. . . . . . . . . . . . . . . . . . . . . . . .
Mounting and Line Connections
1-1
. . . . . . . . .
Auxiliary Circuits and Harness
1-2
. . . . . . . . . . .
Engine Starting Contacts
1-2
. . . . . . . . . . . . . . .
Functional Test
1-2, 1-3, 1-4, 1-5
. . . . . . . . . . . . .
TESTING & SERVICE
2-1
. . . . . . . . . . . . . . . . . .
Transfer Test
2-1
. . . . . . . . . . . . . . . . . . . . . . . . . .
Preventive Maintenance
2-1
. . . . . . . . . . . . . . . .
Disconnecting the Controller
2-1
. . . . . . . . . . . .
Manual Load Transfer
2-2
. . . . . . . . . . . . . . . . . .
Trouble-Shooting
2-2
. . . . . . . . . . . . . . . . . . . . . .
INDEX
back cover
. . . . . . . . . . . . . . . . . . . . . . . . .
Refer to the outline and wiring drawings provided
with your 7000 Series ADTS for all installation and
connection details and accessories.
G design 2000 A
DANGER is used in this manual to warn of high
voltages capable of causing shock, burns, or death.
WARNING is used in this manual to warn
of possible personal injury.
CAUTION is used in this manual to warn
of possible equipment damage.
Refer to
Group 5 Controller User’s Guide
381333–126 for ATS status display messages, time
delays, pickup & dropout settings, and adjustments.
An experienced licensed electrician must install the
ADTS.
G design 4000 A
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
Catalog Number Identification Typical 7000 Series catalog no. for G–design switched neutral, 3 pole, 2000 A, 480 V, ADTS in Type 1 enclosure: 7ADTS B 3 2000 N 5 C Phase Poles Neutral A – solid Amperes Voltage Controller Enclosure B – switched 5X – if accessoriesordered 5 – standard G – type 4 C – ty...
Rating Label Each automatic delayed–transition transfer switch contains a rating label to define the loads and fault circuit withstand / closing ratings. Refer to the label on the transfer switch for specific values. Do not exceed the values on the rating label. Exceeding the rating can cause person...
SECTION 1 INSTALLATION 1--1 ASCO Series 7000 Automatic Delayed–TransitionTransfer Switches are factory wired and tested. Fieldinstallation simply requires mounting and connection ofservice cables, and auxiliary control circuits (if required). Remove the Shipping Skid For large switches, open the fro...