Contents THE LIEBERT DataMate3000 ENVIRONMENTAL CONTROL SYSTEM ................................................ 4 Chapter 1 Features and Benefits............................................................................................................ 1 Chapter 2 Model Configuration..................
Page 4 - systems and computers.
THE LIEBERT DataMate3000 ENVIRONMENTAL CONTROL SYSTEM The DataMate3000 is a small precise environmental control system specially designed for electrical system room cooling. Featuring high reliability, high sensible heat ratio and big air volume, the system is suitable for controlling the temperatur...
Page 5 - Chapter 1 Features and Benefits; electronic equipment.; products. They have the low noise. With volume ranging from 800m
Chapter 1 Features and Benefits 1 DataMate 3000 Series Air Conditioner Technical Manual Chapter 1 Features and Benefits Computer Matched -Liebert systems are designed to create the environment required for computers, telecom and other sensitive electronic equipment. DataMate3000 provides complete co...
Page 6 - Intelligent Microprocessor Control-; Easy Installation
2 Chapter 1 Features and Benefits DataMate 3000 Series Air Conditioner Technical Manual Intelligent Microprocessor Control- The system controller has a 128×64-matrix dot LCD screen with blue backlight. The man-machine-interface is easy-to-use. Multilevel passwords are configured to prevent unauthori...
Page 7 - Chapter 2 Model Configuration; Model Number Designations; Version
Chapter 2 Model Configuration 3 DataMate 3000 Series Air Conditioner Technical Manual Chapter 2 Model Configuration 2.1 Model Number Designations DM E 07 M C 1 2.2 Unit Mechanical Parameters The mechanical parameters of the indoor units are shown in Figure 2-1 and Table 2-1. 600 600 55 0 1 900 600 5...
Page 9 - Units Configuration; Refrigeration circuit
Chapter 2 Model Configuration 5 DataMate 3000 Series Air Conditioner Technical Manual 14 13 9 15 426 ± 1 35 20 15 11 50 24 1750 ± 15 (blue) 1600 ± 15 (brown) 12 2 、 3 、 4 、 5 、 6 、 7 、 8 1 10 Figure 2-4 Dimensions of heater (unit: mm) 2.3 Units Configuration Table 2-2 Configuration Table Of Indoor U...
Page 10 - Chapter 3 Operation Range; the altitude of outdoor unit - the altitude of indoor unit
6 Chapter 2 Model Configuration DataMate 3000 Series Air Conditioner Technical Manual Chapter 3 Operation Range DME3000 are provided for operating within the following working ranges: Table 3-1 horizontal ≤ 50m Installing position between indoor unit and outdoor unit vertical Δ H (1) : -5m ≤Δ H ≤ 20...
Page 11 - Chapter 4 Technical Data
Chapter 4 Technical Data 7 DataMate 3000 Series Air Conditioner Technical Manual Chapter 4 Technical Data Table 4-1 Standard DME3000 Technical Data Air cooled Nominal Cooling Capacity (kW) 7.5 12.5 Indoor Unit Model DME07MC1 DME07MO1 DME07MH1 DME12MC1 DME12MO1 DME12MH1 Net Capacity Data - kW High Fa...
Page 12 - All capacities are nominal values, actual performance will be ±5%.
8 Chapter 4 Technical Data DataMate 3000 Series Air Conditioner Technical Manual Table 4-2 DME3000 S Series Technical Data Air cooled Nominal Cooling Capacity (kW) 5.5 7.5 Indoor Unit Model DME05WCE1 DME05WOE1 DME07WCE1 DME07WOE1 Power Supply 220V~50Hz 220V~50Hz Net Capacity Data - kW High Fan Speed...
Page 13 - Chapter 5 Microprocessor Control; C o o l; Control Buttons
Chapter 5 Microprocessor Control 9 DataMate 3000 Series Air Conditioner Technical Manual Chapter 5 Microprocessor Control The microprocessor control features an easy-to-use menu-driven LCD display. It monitors and displays the operation status of the precision cooling unit to maintain a reasonable e...
Page 15 - EME R SON; E n g l i s h; 中 文; S t a r t i n g; There are three levels of password in the microprocessor control.; Method of entering password:
Chapter 5 Microprocessor Control 11 DataMate 3000 Series Air Conditioner Technical Manual 5.4 Control Screen 5.4.1 Off Screen The LCD displays this screen after the system is powered on. In addition, it will be displayed by pressing the ON/OFF button during system operation, as shown in Figure 5-3. ...
Page 16 - Note; S t a t u s
12 Chapter 5 Microprocessor Control DataMate 3000 Series Air Conditioner Technical Manual If the password entered is incorrect, the user can view the menu but cannot change the parameters. The user can return to the Normal screen by pressing Esc button and enter the password again. If the password e...
Page 18 - NO
14 Chapter 5 Microprocessor Control DataMate 3000 Series Air Conditioner Technical Manual Table 5-2 Alarm output logic Settings Alarm History Alarm Status Audible alarm Alarm prompt OPEN Yes Yes Yes Yes CLOSE Yes Yes No Yes STOP No No No No Note As the high pressure alarm, low pressure alarm and pow...
Page 19 - I n T e m p; Method of changing the time:
Chapter 5 Microprocessor Control 15 DataMate 3000 Series Air Conditioner Technical Manual 5.7 Setpoints The setpoints will not be lost when power fails. Select the Setpoints from the main menu and press Enter to configure the setpoints listed in Figure 5-16. TempStpt TempSens Hum Stpt Hum Sens 24°C ...
Page 20 - L o w F a
16 Chapter 5 Microprocessor Control DataMate 3000 Series Air Conditioner Technical Manual F a n ON C o o l ON H e a t O F F L o Sp d / De h u m O F F Hum OF F Ho s T OF F Sp a r e OF F S y s t e m N o r m H i P r e s s N o r m L o P r e s s N o r m S h o r t C y c l e N o r m Un i t N o r m Figure 5...
Page 22 - SIG; from the System Menu to calibrate the items listed in Figure 5-30.; will be reset to the defaults.; time (15 seconds for compressor and 5 minutes for other components).
18 Chapter 5 Microprocessor Control DataMate 3000 Series Air Conditioner Technical Manual Unit Status Hst Time Spr Time Chg Time SIG 24h24h 30s Figure 5-29 Standby sub-menu 1) Use Up/Down buttons to move the cursor to Unit State in the Standby sub-menu, and press Enter to set the system to Hst Time ...
Page 23 - L e v e l; password or press Esc to abort.; change the Service Info.
Chapter 5 Microprocessor Control 19 DataMate 3000 Series Air Conditioner Technical Manual L e v e l O n e * * * * L e v e l T w o * * * * Figure 5-32 Change Password menu Use Up/Down buttons to move the cursor to the password to be changed and press Enter. Use Left/Right buttons to move the cursor t...
Page 24 - Operation Help is not available at present.; view in the Service Record screen.
20 Chapter 5 Microprocessor Control DataMate 3000 Series Air Conditioner Technical Manual D a t a M a t e 3 0 0 0 Figure 5-36 Product Info screen Operation Help is not available at present. 5.10.2 Service Info Select Service Info from the Help Menu and press Enter to display the items listed in Figu...
Page 25 - Appendix 1 Control System Menu Structure; Main Menu
Chapter 5 Microprocessor Control 21 DataMate 3000 Series Air Conditioner Technical Manual Appendix 1 Control System Menu Structure Main Menu Spare Hi Hum Power Fail Short cycle Lo Hum Custom #1 Custom #2 Rpr MnFan Rpr Humid Custom #2 Custom #1 Humidifier Filter Main Fan Rpr Filter Custom Alarm Servi...
Page 26 - Appendix 2 Wiring Diagram
22 Appendix 2 Wiring Diagram DataMate 3000 Series Air Conditioner Technical Manual Appendix 2 Wiring Diagram Wiring Diagram Of DME3000 Standard
Page 28 - Appendix 3 Spare Parts; Indoor Unit Spare Parts
24 Appendix 2 Wiring Diagram DataMate 3000 Series Air Conditioner Technical Manual Appendix 3 Spare Parts Indoor Unit Spare Parts : Code Spare Parts DME05WCE1 DME05WOE1 DME07WCE1 DME07WOE1 DME07MC1 DME07MO1 DME07MH1 DME12MC1 DME12MO1 DME12MH1 Dosage each unit Compressor 02520014 02520015 02520011 02...
Page 29 - DC Power Systems Outside Plant Site Monitoring Services
Emerson Network Power. The global leader in enabling business-critical continuity. www.EmersonNetworkPower.com AC Power Systems Embedded Power Power Switching and Control Surge ProtectionConnectivity Integrated Cabinet Solutions Precision Cooling Embedded Computing DC Power Systems Outside Plant Sit...