Page 2 - Quick Installation Guide; IMPORTANT NOTICE; Emerson FZE
Quick Installation Guide 00825-0100-4664, Rev BB January 2013 Rosemount 8712 / 8700 Series 2 © 2013 Rosemount Inc. All rights reserved. All marks property of owner. IMPORTANT NOTICE This document provides basic installation guidelines for the Rosemount ® 8712. It does not provide instructions for de...
Page 3 - TEP; Mechanical Considerations
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 3 S TEP 1: P RE -I NSTALLATION Before installing the Rosemount 8712 Magnetic Flowmeter Transmitter, there are several pre-installation steps that should be completed to make the installation process easier: • I...
Page 4 - Figure 1. Rosemount 8712 Dimensional Drawing; LOI Keypad; WITH STANDARD COVER; NOTE; WITH LOI COVER
Quick Installation Guide 00825-0100-4664, Rev BB January 2013 Rosemount 8712 / 8700 Series 4 Figure 1. Rosemount 8712 Dimensional Drawing 4.31 (109) LOI Keypad Cover 9.01 (229) 11.15 (283) 2.81 (71) 3.11 (79) 12.02 (305) 0.44 (11) Ground Lug 1 / 2 –14 NPT Conduit Connection (4 Places) WITH STANDARD ...
Page 5 - Installation Procedures; Mount the Transmitter; Pipe Mounting; To mount the transmitter on a pipe:; Identify Options and Configurations; Changing Hardware Switch Settings; HIGH
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 5 Environmental Considerations To ensure maximum transmitter life, avoid excessive heat and vibration. Typical problem areas include: • Warm-climate installations in direct sunlight• Outdoor installations in co...
Page 6 - Figure 2. Rosemount 8705 Sensor Support for Handling
Quick Installation Guide 00825-0100-4664, Rev BB January 2013 Rosemount 8712 / 8700 Series 6 Electrical Considerations Before making any electrical connections to the Rosemount 8712, consider local and plant electrical standards and be sure to have the proper power supply, conduit, and other accesso...
Page 7 - Upstream/Downstream Piping; Figure 3. Upstream and Downstream Straight Pipe Diameters
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 7 S TEP 3: M OUNTING Upstream/Downstream Piping To ensure specification accuracy over widely varying process conditions, install the sensor a minimum of five straight pipe diameters upstream and two pipe diamet...
Page 8 - Figure 4. Sensor Orientation
Quick Installation Guide 00825-0100-4664, Rev BB January 2013 Rosemount 8712 / 8700 Series 8 The electrodes in the Rosemount 8705 sensor are properly orientated when the two measurement electrodes are in the 3 and 9 o’clock positions, as shown on the right of Figure 4. The electrodes in the Rosemoun...
Page 9 - Gaskets; Figure 6. Flanged gasket placement
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 9 S TEP 4: I NSTALLATION Flanged Sensors Gaskets The sensor requires a gasket at each of its connections to adjacent devices or piping. The gasket material selected must be compatible with the process fluid and...
Page 11 - Size
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 11 Table 2. Flange Bolt Torque and Bolt Load Specifications for 8705(EN 1092-1) Size Code Line Size PTFE/ETFE liner PN10 PN 16 PN 25 PN 40 (Newton- meter) (Newton) (Newton- meter) (Newton) (Newton- meter) (Newt...
Page 13 - Wafer Sensors; liner may be damaged.; Figure 8. Wafer gasket placement; Nominal Sensor Size
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 13 Wafer Sensors Gaskets The sensor requires a gasket at each of its connections to adjacent devices or piping. The gasket material selected must be compatible with the process fluid and operating conditions. M...
Page 14 - Rosemount Alignment Spacer Table
Quick Installation Guide 00825-0100-4664, Rev BB January 2013 Rosemount 8712 / 8700 Series 14 Table 4. Rosemount Alignment Spacer Table To order an Alignment Spacer Kit (qty 3 spacers) use p/n 08711-3211-xxxx along with the Dash No. above. Rosemount Alignment Spacer Table Dash No. Line Size Flange R...
Page 15 - Sanitary Sensors; Size Code
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 15 Flange Bolts Wafer sensors require threaded studs. See Figure 7 for torque sequence. Always check for leaks at the flanges after tightening the flange bolts. All sensors require a second torquing 24 hours af...
Page 17 - Figure 12. Grounding with Grounding Rings or Lining Protectors
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 17 Figure 12. Grounding with Grounding Rings or Lining Protectors Figure 13. Grounding with Grounding Electrode Grounding Rings or Lining Protectors 4664RevBBQIG.fm Page 17 Friday, January 11, 2013 6:13 PM
Page 18 - Conduit Ports and Connections; Both the sensor and transmitter junction boxes have ports for; Conduit Requirements; Figure 14. Conduit Preparation
Quick Installation Guide 00825-0100-4664, Rev BB January 2013 Rosemount 8712 / 8700 Series 18 S TEP 6: W IRING Conduit Ports and Connections This wiring section covers the connection between the transmitter and sensor, the 4-20 mA loop, and supplying power to the transmitter. Follow the conduit info...
Page 19 - tray as AC or DC power wiring.; Transmitter to Sensor Wiring; Figure 15. Cable Preparation Detail
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 19 Run the appropriate size cable through the conduit connections in your magnetic flowmeter system. Run the power cable from the power source to the transmitter. Run the coil drive and signal cables between th...
Page 20 - To order cable specify length as quantity desired.; Wiring the Transmitter to the Sensor; Connect the coil drive cable using terminals; WARNING
Quick Installation Guide 00825-0100-4664, Rev BB January 2013 Rosemount 8712 / 8700 Series 20 S TEP 6 CONTINUED ... To order cable specify length as quantity desired. 25 feet = Qty (25) 08732-0753-1003 Table 7. Cable Requirements Wiring the Transmitter to the Sensor When using individual cables for ...
Page 21 - Figure 16. Remote Mount Wiring Diagrams
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 21 S TEP 6 CONTINUED ... NOTE When using the Rosemount supplied combination cable, the signal wires for terminals 18 and 19 contain an additional shield wire. These two shield wires should be tied with the main...
Page 22 - Connect the 4–20 mA Analog Signal; Cabling considerations; Figure 18. 8712E Analog Signal Wiring Diagram
Quick Installation Guide 00825-0100-4664, Rev BB January 2013 Rosemount 8712 / 8700 Series 22 S TEP 6 CONTINUED ... Connect the 4–20 mA Analog Signal Cabling considerations If possible, use individually shielded twisted pair cable, either in single pair or multi-pair varieties. Unshielded cables may...
Page 23 - Supply Wire Requirements; Figure 19. DC Power Supply Current Requirements; Table 10. Overcurrent Limits; Power System
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 23 Powering the Transmitter The 8712E transmitter is designed to be powered by 90-250 Vac, 50–60 Hz or 12–42 Vdc. Before connecting power to the Rosemount 8712E consider the following standards and be sure to h...
Page 24 - Figure 20. 8712E Transmitter Power Connections; Transmitter
Quick Installation Guide 00825-0100-4664, Rev BB January 2013 Rosemount 8712 / 8700 Series 24 8712E Power Supply For AC power applications (90-250 VAC, 50-60 Hz) connect AC Neutral to terminal N and connect AC Line to terminal L1. For DC power applications, connect negative to terminal N (DC -) and ...
Page 25 - Step 7: Basic Configuration; Basic Setup; Tag
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 25 Step 7: Basic Configuration Once the magnetic flowmeter is installed and power has been supplied, the transmitter must be configured through the basic setup. These parameters can be configured through either...
Page 26 - Local Operator Interface; Function
Quick Installation Guide 00825-0100-4664, Rev BB January 2013 Rosemount 8712 / 8700 Series 26 Table 11. Field Communicator Fast Key Sequence Local Operator Interface The optional Local Operator Interface (LOI) provides an operator communications center for the 8712E. By using the LOI, the operator c...
Page 27 - RODUCT; Emerson Process Management Flow — Ede, The Netherlands; European Directive Information; Type n protection type in accordance with EN 50021; CE Marking; International Certificates; Rosemount Inc. complies with the following IEC Requirements:; Hazardous Locations Certifications; North American Certifications
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 27 P RODUCT C ERTIFICATIONS Approved Manufacturing Locations Rosemount Inc. — Eden Prairie, Minnesota, USA Fisher-Rosemount Technologias de Flujo, S.A. de C.V. — Chihuahua Mexico Emerson Process Management Flow...
Page 28 - ATEX Type n; International Certifications
Quick Installation Guide 00825-0100-4664, Rev BB January 2013 Rosemount 8712 / 8700 Series 28 Canadian Standards Association (CSA)N0 Non-incendive for Class I, Division 2 Groups A, B, C, and D non-flammable fluids(T4 at 40 °C)Dust-ignition proof Class II/III, Division 1Groups E, F, and G(T4 at 40 °C...
Page 29 - Sensor Approval Information
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 29 Sensor Approval Information Approval Codes Rosemount 8705 Sensor Rosemount 8707 Sensor Rosemount 8711 Sensor Rosemount 8721 Sensors For Non-flammable Fluids For Flammable Fluids For Non-flammable Fluids For ...
Page 30 - Maximum Ambient Temperature
Quick Installation Guide 00825-0100-4664, Rev BB January 2013 Rosemount 8712 / 8700 Series 30 Table 12. Electrical Data Rosemount 8705 and 8711 Sensors Coil excitation circuit: 40 V DC (pulsed), 0,5 A, 20 W maximum Electrode circuit: in type of explosion protection intrinsic safety EEx ia IIC, U i =...
Page 31 - EC Declaration of Conformity; Transmitters; USA
Quick Installation Guide 00825-0100-4664, Rev BBJanuary 2013 Rosemount 8712 / 8700 Series 31 Figure 21. Declaration of Conformity EC Declaration of Conformity No: RMD 1031 Rev. E FILE ID: 8712 CE Marking Page 1 of 2 8712_RMD1031E.DOC We, Rosemount Inc. 12001 Technology Drive Eden Prairie, MN 55344-3...
Page 32 - Schedule; EC Declaration of Conformity RMD 1031 Rev. E; LVD Directive; All Models; ATEX Notified Bodies for EC Type Examination Certificate; Baseefa; ATEX Notified Body for Quality Assurance
Quick Installation Guide 00825-0100-4664, Rev BB January 2013 Rosemount 8712 / 8700 Series 32 Schedule EC Declaration of Conformity RMD 1031 Rev. E FILE ID: 8712 CE Marking Page 2 of 2 8712_RMD1031E.DOC LVD Directive (2006/95/EC) All Models EN 61010-1: 2001 EMC Directive (2004/108/EC) All Models EN ...