Emerson 7ATB - Manual
Emerson 7ATB – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 3 – Catalog Number Identification; Typical 7000 Series ATB catalog no. for overlapping
- Page 5 – SECTION 1 INSTALLATION; Remove the Shipping Skid; To prevent serious damage, remove 3 shipping; remove 3 or 4 shipping brackets ( L–angles)
- Page 6 – INSTALLATION; Wiring Diagram
- Page 7 – Functional Test; Wiring Diagrams; Section 3; – Voltage Checks; Use extreme caution when using a meter
- Page 8 – – Electrical Operation; Transfer Test; Isolation Handle
- Page 9 – SECTION 2 TESTING & SERVICE; TRANSFER TEST; Electrical Operation – Transfer; PREVENTIVE MAINTENANCE; Return to Service
- Page 10 – MANUAL LOAD TRANSFER; CLOSED; MAINTENANCE HANDLE
- Page 11 – SECTION 3 BYPASSING & ISOLATING; You can only bypass to the same source; To Bypass Normal Source*; ISOLATING
- Page 12 – BYPASSING & ISOLATING; ISOLATING THE ATS; BYPASSING; TEST
- Page 13 – Drawout procedure
- Page 14 – RETURN TO SERVICE; NOTE
- Page 15 – To Un–Bypass Normal Source*
- Page 16 – INDEX; Controller User’s Guide
381333–132 F
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
Operator’s
Manual
7000 Series 7ATB
Automatic Transfer &
Bypass–Isolation Switches
G design 1000 through 4000 amp. sizes
DANGER is used in this manual to warn of high
voltages capable of causing shock, burns, or death.
WARNING is used in this manual to
warn of possible personal injury.
CAUTION is used in this manual to
warn of possible equipment damage.
4000 amp. size
Refer to the outline and wiring drawings provided
with your 7000 Series ATB for all installation and
connection details and accessories.
Refer to
Group 5 Controller User’s Guide
381333–126
for ATS status display messages, time delays, pickup
& dropout settings, and adjustments.
An experienced licensed electrician must install the
7ATB.
Rating Label
Each 7000 Series 7ATB contains a rating label to
define the loads and fault circuit withstand/closing
ratings. Refer to the label on the Transfer Switch for
specific values.
Do not exceed the values on the rating label.
Exceeding the rating can cause personal injury
or serious equipment damage.
Nameplate
The Transfer Switch nameplate includes data for each
specific 7000 Series ATB. Use the switch only within the
limits shown on this nameplate. A typical Catalog
Number is shown below with its elements explained:
TABLE OF CONTENTS
section-page
INSTALLATION
Mounting
1-1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Connections
1-2
. . . . . . . . . . . . . . . . . . . .
Engine Starting & Auxiliary Circuits
1-2
. . . . . .
Functional Test
1-3, 1-4
. . . . . . . . . . . . . . . . . . . . .
TESTING & SERVICE
Transfer Test
2-1
. . . . . . . . . . . . . . . . . . . . . . . . . .
Preventive Maintenance
2-1
. . . . . . . . . . . . . . . .
Disconnecting the Controller
2-1
. . . . . . . . . . . .
Manual Load Transfer
2-2
. . . . . . . . . . . . . . . . . .
Trouble-Shooting
2-2
. . . . . . . . . . . . . . . . . . . . . .
BYPASSING & ISOLATING
Bypassing the ATS
3-1
. . . . . . . . . . . . . . . . . . . .
Isolating the ATS
3-2
. . . . . . . . . . . . . . . . . . . . . .
Return to Service
3-3, 3-4
. . . . . . . . . . . . . . . . . . .
INDEX
back cover
. . . . . . . . . . . . . . . . . . . . . . . . .
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
Catalog Number Identification Typical 7000 Series ATB catalog no. for overlapping neutral, 3 pole, 4000 amp., 480 V, in Type 1 enclosure: G7ATB C 3 4000 N 5 C Phase Poles Neutral A – solid Amperes Voltage Controller Enclosure B – switching 5X – if accessoriesordered 5 – standard G – type 4 C – type ...
1 --- 1 SECTION 1 INSTALLATION The ASCO 7000 Series Automatic Transfer &Bypass–Isolation Switch (ATB) consists of an upperbypass–isolation switch, a lower transfer switch, amonitoring and transfer controller, and door–mountedcontrols. The ATB is factory wired and tested.Installation requires rem...
INSTALLATION (continued) 1 --- 2 De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine gen- erator starting control in the OFF position. Make sure engine generator is not in ...