Do not use on circuits exceeding specified volt-
ages. Higher voltages will damage control and
could cause shock or fire hazard.

Printed in U.S.A.

PART NO. 37-2398D

Replaces 37-2398C

9507

INSTALLATION INSTRUCTIONS

5C06

High Limit Control

Open On Rise, Manual Reset

This high limit control is of the non-cycling manual reset
type; once the contacts open, they will remain open until
the reset button is pushed.

This control is designed to break a line voltage (or low
voltage) circuit if air temperature at its element location
ever reaches its predetermined cut-out setting.

This control may be used to protect against high tempera-
tures in heating and ventilation systems by opening circuit
to burner if circulated air reaches a temperature above the
fixed setting of the control. It is also suitable for use on
downflow furnaces to lock out burner in event of blower
failure or slow start.

Follow any wiring instructions provided by the furnace
manufacturer. Typical diagram is shown for normal use of
this control. A normal cycling type high limit control should
always be used in addition to the High Limit Control for
monitoring burner operation.
All wiring should be installed according to local and
national electrical codes and ordinances. Controls
are required to be installed with 75

°

C minimum wire.

This control has a fixed setting. If temperature ever reaches the cut-out setting, the contacts will open. When
temperature drops to safe level, the reset button must be pushed before contacts will reclose.

ADJUSTMENT

DESCRIPTION

L1

L2

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.

Operator: Save these instructions for future use!

5C06 HIGH LIMIT CONTROL

FAN CONTROL

POWER SUPPLY

HOT

BLOWER

MOTOR

WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123
(314) 577-1300, Fax (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625

R

To prevent electrical shock and/or equipment
damage, disconnect electric power to Furnace at
main fuse or circuit breaker box, until installation
is complete.

CAUTION

!

WARNING

!

SPECIFICATIONS

ELECTRICAL DATA
Electrical Rating:
Motor Loads –

10 FLA (60 LRA), 120V 60 Hz.
6 FLA (36 LRA), 240V 60 Hz.

Valves & Relays– 4A @ 25V 60 Hz.

SWITCH ACTION: Open On Rise, Manual Reset

THERMAL DATA

Cut-Out Range: 125

°

– 250

°

F (52

°

– 121

°

C)

Standard Cut-Out Settings: 125

°

, 165

°

, 200

°

, 240

°

F

(52

°

, 74

°

, 93

°

, 116

°

C)

Element Insertion Length: 3 Inches

PRECAUTIONS

LOCATION:
Normal use of this control requires that it be located
in the return air duct where the sensing element will
be subjected to normal flow of air returning to the
furnace.

Fig.1-Diagram for shutting off burner

TO OIL BURNER

OR GAS VALVE

(LINE VOLTAGE)

WIRING

WHITE-RODGERS