Page 3 - TABLE OF CONTENTS
i TABLE OF CONTENTS I MPORTANT S AFETY I NSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 G LOSSARY OF S YMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.0 I NSTALLA...
Page 4 - ii; UPS S
ii 3.4 Non-Standard Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 3.5 BCB Shunt Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 3.6 Alber Monitor...
Page 5 - iii; PERATING
iii 8.10 Current Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 8.11 UPS Status Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 8.12 Types of LCD S...
Page 6 - iv; FIGURES
iv 11.0 S PECIFICATIONS AND T ECHNICAL D ATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 11.1 Lug Size and Torque Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 11.2 Cable Lengths: Floor to Connection Point...
Page 7 - TABLES
v Figure 41 Mimic display indicators location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Figure 42 Location of control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5...
Page 9 - SAVE THESE INSTRUCTIONS; Liebert NX; Retain this manual for use by installing personnel.; before handling the UPS. Test lift and balance the cabinet; WARNING; carried out only by trained personnel.; WARNING
1 I MPORTANT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation of your Liebert NX ™ UPS and ancillary equipment. Read this manual thoroughly, paying special attention to the sections that apply to your installation, ...
Page 10 - Battery Cabinet Precautions
2 Battery Cabinet Precautions The following warning applies to all battery cabinets supplied with UPS systems. Additional warn- ings and cautions applicable to battery cabinets may be found in 3.0 - Battery Installation . ! WARNING Under typical operation and with all UPS doors closed, only normal s...
Page 12 - Installation; NSTALLATION; External Inspections; carrier and your local Liebert representative immediately.; information contained in this section.; with large amounts of water.; NOTE; The Liebert NX UPS can be used in TN utility system.
Installation 4 1.0 I NSTALLATION Liebert’s NX Uninterruptible Power Supply system provides continuous, high-quality AC power to your business-critical equipment, such as telecommunications and data processing equipment. The Liebert NX UPS supplies power that is free of the disturbances and variation...
Page 13 - Internal Inspections; the Liebert NX from excessive moisture (see; Preliminary Checks; Choose a location for the UPS that offers:; Table 7; for details on heat dissipation.; CAUTION
Installation 5 1.2 Internal Inspections 1. Remove any packaging material, then visually examine the UPS and battery equipment for transit damage, both internally and externally. Report any such damage to the shipper and to Liebert immediately. 2. Check the nameplate inside the cabinet door to verify...
Page 14 - Battery Location; Considerations in Moving the Liebert NX; Final Position; Mechanical Considerations; Battery Cabinet Precautions on page 2
Installation 6 Battery Location Batteries must be installed in Liebert NX 480V battery cabinets or battery room. Temperature is a major factor in determining battery life and capacity. Battery manufacturers recommend an operat- ing temperature of 77°F (25°C). Ambient temperatures higher than this re...
Page 15 - System Composition; before; Table 8; at the output of the UPS.
Installation 7 1.6.1 Clearances There are no ventilation grilles on the sides or rear of the UPS. The unit may be placed with the rear against a wall and optional cabinets on either side.To enable routine tightening of power terminations within the UPS, make sure there is sufficient clearance in fro...
Page 16 - Figure 1
Installation 8 Figure 1 Cabinet arrangement—Liebert NX units and battery cabinets Front of Units Battery Cabinet Battery Cabinet Battery Cabinet Liebert NX UPS Front of Units Battery Cabinet Battery Cabinet Battery Cabinet Liebert NX UPS Front of Units Multi-Module Parallel Cabinet Battery Cabinet B...
Page 17 - Figure 2
Installation 9 Figure 2 Cabinet arrangement—Liebert NX units, battery cabinets and Liebert FPC Front of Units Multi-Module ParallelCabinet Liebert Foundation Power Center Battery Cabinet Battery Cabinet Battery Cabinet Battery Cabinet Liebert NX UPS Liebert NX UPS Liebert NX UPS Liebert NX UPS Front...
Page 18 - Electrical Connections; LECTRICAL; Power Cabling; Lug Size and Torque Requirements
Electrical Connections 10 2.0 E LECTRICAL C ONNECTIONS The UPS requires both power and control cabling once it has been mechanically installed. All control cables must run separate from power cables in metal conduits or metal ducts that are electrically bonded to the metalwork of the cabinets to whi...
Page 19 - Figure 3; input bus bars, then wire the Main input directly to CB1 (see; Figure 4; data in; Output and input cables must be run in separate conduit.; electromagnetic interference.
Electrical Connections 11 2.1.2 UPS Input Configuration Figure 3 illustrates the Liebert NX in a split bypass (dual-input) configuration. In this configuration the Static Bypass and the Maintenance Bypass lines are supplied from a separate feed from the Main input. Both sources must be protected ext...
Page 20 - and below the circuit breaker, as shown in; . These busbars are accessible when the front
Electrical Connections 12 2.1.4 Cable Connections The rectifier input, bypass and output are easily accessible from the front of the unit for installation. All require lug type terminations. They are connected to busbars on the front side of the Liebert NX and below the circuit breaker, as shown in ...
Page 21 - UPS Rectifier and Bypass Input Supply
Electrical Connections 13 2.1.5 Safety Ground The safety ground busbar is located below the Maintenance Bypass circuit breaker as shown in Figure 4 . The safety ground cable must be connected to the ground busbar and bonded to each cabi- net in the system.All cabinets and cable conduit should be gro...
Page 22 - Steps 5; Common Input Connections; Observe the battery cable polarity.; applicable local codes.
Electrical Connections 14 2.1.7 Cabling Procedure Once the equipment has been positioned and secured for operation, and the battery and ground col- lars have been connected (see 2.1.4 - Cable Connections ), connect the power cables as described below. (Study the reference drawing in 6.0 - Installati...
Page 23 - Frequency Converter Mode; Control Cables; interface; Figure 5; rectifier input are removed.
Electrical Connections 15 Frequency Converter Mode If a frequency converter configuration is used, connect the AC input supply cables to the rectifier input busbars (A-B-C terminals). Torque to 88 lb-in (10N-m) for M8 bolts. Ensure correct phase rota- tion. There will not be any AC bypass supply cab...
Page 24 - Figure 6; Dry Contacts; The UPS provides input dry contacts and output dry contacts.; NOTE: The black square
Electrical Connections 16 Figure 6 Auxiliary terminal block detail (Monitoring Board) 2.3 Dry Contacts The UPS provides input dry contacts and output dry contacts. NOTE When operating the Liebert NX with dry contacts, ESD measures must be taken or the contacts may be damaged. NOTE: The black square ...
Page 25 - There are several input dry contacts at the X3 slot.; Maintenance Bypass Cabinet Interface; J26 and J30 are the MBC interface.
Electrical Connections 17 2.3.1 Input Dry Contacts There are several input dry contacts at the X3 slot. Figure 7 Input dry contacts 2.3.2 Maintenance Bypass Cabinet Interface J26 and J30 are the MBC interface. Table 1 Input dry contacts at X3 Position Name Description J4.1 ENV 3 Battery Room Alarm (...
Page 26 - J10 is the BCB box interface.; Figure 8; Position; needs to added between Pin 3 and Pin 4.; OL
Electrical Connections 18 2.3.3 BCB Control Interface J10 is the BCB box interface. Figure 8 Jumper connection for BCB interface without a battery interface board Table 3 BCB control interface Position Name Description J10.1 DRV BCB Driver Signal J10.2 FB BCB Contact State J10.3 GND Power Ground J10...
Page 27 - There are three output dry contact relays at the X1 slot (see; Figure 9; and; Table 4; Bypass feedback protection relay center; NOTE: The black square on each slot
Electrical Connections 19 2.3.4 Output Dry Contacts There are three output dry contact relays at the X1 slot (see Figure 9 and Table 4 ). Figure 9 Output dry contacts and EPO wiring for firmware before M170 Table 4 Output dry contact relays Position Name Description J13.2 BFP_O Bypass feedback prote...
Page 28 - , is the remote EPO input interface. The EPO has a NO/NC contact; Table 5; EPO Activated when opened to J28.2; board and must remain installed if using NO contacts.
Electrical Connections 20 2.3.5 EPO Input—Optional The UPS has an Emergency Power Off (EPO) function operated by a button on the control panel or by a remote contact provided by the user. The local EPO button is under a hinged, clear plastic shield.The X2 slot, shown in Figure 10 , is the remote EPO...
Page 29 - Battery Installation; ATTERY; Introduction; bert representative for a list of approved batteries.; Safety; and is POTENTIALLY LETHAL.; supply must be at least 600VDC.
Battery Installation 21 3.0 B ATTERY I NSTALLATION 3.1 Introduction If using multiple sets of batteries connected in parallel to provide the required battery backup run times, fit each set with an isolating device to permit working on one of the battery sets while leaving the others in service and p...
Page 30 - External Battery Cabinet Installation; Figure 11 Battery cabinet; contact Liebert Global Services for recommended precautions.; Any battery system should be installed by qualified personnel.
Battery Installation 22 3.3 External Battery Cabinet Installation 3.3.1 Battery Cabinets Figure 11 Battery cabinet The same model battery cabinet may be installed in parallel in multiple cabinet strings for additional capacity. Battery run time depends on the cabinet model, the number of cabinets an...
Page 31 - Figure 12 Battery cabinet—details; side and rear service clearance requirements. Refer to
Battery Installation 23 3.3.2 Connecting the Batteries If the Liebert NX battery cabinets are installed on a raised floor, the battery power cables and circuit breaker control cables may be routed to the UPS cabinet via the floor of the cabinet (bottom entry).If the Liebert NX battery cabinets are i...
Page 32 - Figure 13 Battery tray and supports; Connecting the Battery Cabinet to the UPS; breaker before the equipment has been commissioned.; Non-Standard Batteries; shunt trip will open the circuit breaker.; and all applicable local codes.; Slot in support
Battery Installation 24 Figure 13 Battery tray and supports 3.3.4 Connecting the Battery Cabinet to the UPS After the battery cabinet equipment has been positioned and secured for operation and the batteries have been connected, connect the power cables as described below. (See Figure 28 .) 1. Verif...
Page 33 - Alber Monitoring System—Optional; UPS-protected source. This power is to be field supplied. See; This power must be UPS protected.
Battery Installation 25 3.6 Alber Monitoring System—Optional The Liebert matching battery cabinet allows installing an optional Alber Battery monitoring system in the cabinet. The Alber Battery Monitoring by Liebert continuously checks all critical battery parameters, such as cell voltage, overall s...
Page 34 - Options; PTIONS; Load Bus Synchronization; The LBS operates under the following conditions:
Options 26 4.0 O PTIONS 4.1 Load Bus Synchronization The Load Bus Synchronizer (LBS) keeps the output of two independent UPS systems or parallel UPS systems in synchronization even when the systems are operating in different modes and even when either or both systems are operating on batteries. When...
Page 35 - LCD will display “LBS active.”; Configuring Parallel System Operation; the overload is cleared.; UPS
Options 27 Figure 15 Load Bus Synchronization cable connection with multi-module systems The LBS function is activated with configuration software; when the LBS takes effect, the graphic LCD will display “LBS active.” 4.2 Configuring Parallel System Operation 4.2.1 General The Liebert NX uses intell...
Page 36 - Figure 16 Parallel system block diagram; Redundancy Paralleling; increase, the parallel system will trigger an alarm.; Normal Mode Operation; wise, the system will operate at nominal frequency.; Battery Mode Operation; The bypass of all the UPS modules powers the load.; Maintenance Bypass Mode Operation; Installing Parallel System
Options 28 Figure 16 Parallel system block diagram 4.2.3 Operating Principles Redundancy Paralleling The parallel redundant system can noticeably improve system reliability. In normal condition, none of the UPS modules work at full load. That means that even if the load is increased, the system will...
Page 37 - bypass inputs and outputs must be correct and the same.; Parallel System Control Cables; for the location of the parallel logic board):; be no more than four times the power rating of the smallest UPS
Options 29 4.3.1 Conditions for Parallel System • Each UPS module must have the same bypass source.• The outputs of all UPS modules are connected altogether.• The main inputs can be from different sources, but the phase rotation sequence of main inputs, bypass inputs and outputs must be correct and ...
Page 38 - Figure 17 Connecting system parallel control cables; Auxiliary Dry Contact Cables; For startup procedure,; Interconnecting
Options 30 Figure 17 Connecting system parallel control cables Auxiliary Dry Contact Cables The external output breaker of each UPS must have Normally Open auxiliary contacts. These con- tacts must be wired to connector X3 on the Parallel Logic Board (M3). See Figures 18 and 19 . Figure 18 Auxiliary...
Page 39 - Input Distribution; UPS N; To Load
Options 31 Figure 19 Dry contacts, multiple UPS modules with distribution panel Input Distribution UPS 1 M 3 Board X3 Ext. Maint. Ext. Out UPS 2 M 3 Board X3 Ext. Maint. Ext . Out UPS N M 3 Board X3 Ext. Maint. Ext. Out To Load QUPS QByp Q1 Ext Q2 Ext QnExt
Page 40 - Figure 20 Connecting EPO push button; Normally; Normally
Options 32 4.3.6 Emergency Power Off (EPO) The external emergency stop facility is identical to that described for the single unit installation— that an individual emergency stop button is provided for each unit. Figure 20 Connecting EPO push button UPS2 UPS1 Monitor Board Monitor Board X2:1X2:2 X2:...
Page 41 - UPS Specifications; PECIFICATIONS; Conformity and Standards; The UPS has been designed to conform to the following standards:; UPS Environmental; radation in electrical operating characteristics:; UPS Mechanical Characteristics; Table 6; Rated Power; Parameter
UPS Specifications 33 5.0 UPS S PECIFICATIONS These specifications describe requirements for the Liebert NX UPS. 5.1 Conformity and Standards The UPS has been designed to conform to the following standards: • IEEC 61000-4-5• ASME• CSA 22.2, No. 107.1• FCC Part 15, Class A• ISO 9001• National Electri...
Page 42 - UPS Electrical Characteristics
UPS Specifications 34 5.4 UPS Electrical Characteristics Table 8 UPS terminal Input (For Single-Input Unit) Unit Rating Nominal Input Current Maximum Input Current OCP Current OCP Device Rating Bolt Size Maximum Recommended Lug (Thomas & Betts part number) Compression 2-Hole; 3/8" Bolt Mecha...
Page 43 - Rated Power kVA; Battery Manufacturer
UPS Specifications 35 5.4.1 Input Rectifier Battery Unit Rating Nominal Input Current Maximum Input Current OCP Device Rating Bolt Size Maximum Recommended Lug (Thomas & Betts Part Number) Compression 2-Hole; 3/8" bolt Mechanical 2-Hole; 40 82 at 480VDC 98 at 400VDC 70 8M 54106 ADR21 60 122 ...
Page 44 - DC intermediate circuit; Inverter output; Bypass input; Time
UPS Specifications 36 5.4.2 DC Intermediate Circuit See Table 8 for current ratings. 5.4.3 Inverter Output See Table 8 for current ratings. 5.4.4 Bypass Input Table 12 DC intermediate circuit Rated Power kVA 40 60 80 100 120 Recommended number of lead-acid batteries Total 40 battery blocks of 12VDC ...
Page 45 - Installation Drawings; Figure 21 Dimensional view- front and left side views; Left Side; Liquid
Installation Drawings 37 6.0 I NSTALLATION D RAWINGS The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert NX UPS System cabinets. Figure 21 Dimensional view- front and left side views 39.6mm (1.6") 997 mm (39 .3") 360 mm (14 .2") Center...
Page 46 - Figure 22 Dimensions continued—top and bottom views
Installation Drawings 38 Figure 22 Dimensions continued—top and bottom views Figure 23 Main components—typical unit 113.5(4.5") 150 (5.9") 150 (5.9") 987.1 (38.9") 514.5 (20.3") 120 (4.7") 841 (33.1") 600 (23.6") 87.6 (3.5") 77 (3") 671.6 (26.4") 367.7 (14...
Page 47 - Figure 24 Cable connections; NOTES
Installation Drawings 39 Figure 24 Cable connections 965 (38") 600 (23.6") 2000 (78.7") LEFT SIDE VIEW (with side panel removed) FRONT VIEW (with door removed) 20 (.79") 35 (1.38") 158.1 (6.22") 35 (1.38") 36 (1.42") Output GND DC Bypass Main 25.4 (1") 6 (.24"...
Page 48 - Bottom
Installation Drawings 40 Figure 25 Outline drawing, 33" battery power pack system, single cabinet 169.5 (6.7) 372.7 (14.7) 575.9 (22.7) 779.1 (30.7) 172.1 (6.8) 965 (38) Bottom (Viewed From Below) Right Side Front (Without Door) Top (Viewed From Above) Max. Door Swing: 120° 490.3 (19.3) 896.6 (3...
Page 49 - Front; DETAIL B; PCB
Installation Drawings 41 Figure 26 Terminal details, 33" battery power pack system, single cabinet Liebert NX NOTES:1. All dimensions are in millimeters (inches).2. All cables should be routed before bolting cabinets together.3. The cables between the battery cabinet and the UPS cabinet must be ...
Page 50 - Figure 27 Battery connections
Installation Drawings 42 Figure 27 Battery connections H1 H2 H3 X2 X3 X1 H4 X4 B r ow n B lue Y e llo w /Gr e en AC 480V Field-Supplied UPS Module E xt . B a tt. 11 12 14 C1 C2 MX A UX + 1 234 56 78 9 1011 12 AC 120V (To Alber Controller) Option: Power for Alber System X 100 X10 2 +220 V - 12 3 X 7_...
Page 51 - Figure 28 Battery cabinet interconnection; Run
Installation Drawings 43 Figure 28 Battery cabinet interconnection NOTES: 1. All cables must be repositioned prior to and while setting the cabinets in their installed location. 2. Refer to the individual drawing of each piece of equipment for additional details. Run From To Conductors A UPS Battery...
Page 52 - Top
Installation Drawings 44 Figure 29 Outline drawing, Liebert NX480V, 80-120kVA Type E and E2 parallel cabinet Top Right Side 800 (31.5) 965 (38) Front 2000 (78.7) NOTE:1. All dimensions are in millimeters (in).2. Eight-inch minimum clearance above unit required for air exhaust. 3. Keep cabinet within...
Page 55 - Rear
Installation Drawings 47 Figure 32 Main component location drawing Liebert NX 480V, Type E1 parallel cabinet Front (With Covers ) BypassTieBreaker BypassTieBreaker GroundBus UPS Input System Input 1240 (48.8) 2000 (78.7) Front Without Covers Rear With Covers Rear Without Covers UPSOutput OutputDistr...
Page 56 - FRONT
Installation Drawings 48 Figure 33 Main component location drawing Liebert NX 480V, Type E2 parallel cabinet SystemO/P TieBreaker Kirk-KeyFuseDisconnect SystemOutputBusbars BroundBusbar UPSOutputBreakers FRONT
Page 57 - Figure 34 Lineup detail—Parallel Type E connection to Liebert NX
Installation Drawings 49 Figure 34 Lineup detail—Parallel Type E connection to Liebert NX C1-C4 D E1-E4 B1-B4 C1-C4 B1-B4 A G1-G4H1-H4 E1-E4F FRONT (Without Covers) FRONT (Door Open) REAR (Without Covers) G1-G4H1-H4 Run From To Conductors A Utility Source Parallel Cabinet Ph A, B, C - System Input B...
Page 58 - Figure 35 Lineup detail—Parallel Type E1 connection to Liebert NX
Installation Drawings 50 Figure 35 Lineup detail—Parallel Type E1 connection to Liebert NX FRONT (Without Covers REAR (Without Covers FRONT (With Door Open) E1-E4, F B1-B4 A D B1-B4 E1-E4 C1-C4 G1-G4,H1-H4 G1-G4,H1-H4 C1-C4 Run From To Conductors A Utility Source Parallel Cabinet Ph A, B, C - System...
Page 59 - Figure 36 Lineup detail—Parallel Type E2 connection to Liebert NX
Installation Drawings 51 Figure 36 Lineup detail—Parallel Type E2 connection to Liebert NX C1-C4 E1-E4 B1-B4 C1-C4 G1-G4H1-H4 D E1-E4F FRONT (Without Covers) FRONT (Door Open) G1-G4H1-H4 Run From To Conductors B1-B4 Utility UPS #1-UPS #4 Module AC Input Ph A, B, C - UPS Inputs C1-C4 UPS #1-UPS #4 Mo...
Page 60 - LEFT SIDE
Installation Drawings 52 Figure 37 Line-up detail, bolt together description, 40-120 kVA Liebert NX Removewhen cabinetsare to be boltedtogether DETAIL A A U3819301 NOTES:1. All dimensions are in millimeters (inches)2. All cables should be routed before bolting cabinets together.3. The cables between...
Page 61 - Operation; PERATION; General Description; service to the maintenance bypass.; Figure 38 Single module block diagram (dual input configuration)
Operation 53 7.0 O PERATION 7.1 General Description Liebert’s NX provides continuous, high-quality AC power to your business-critical equipment, such as telecommunications and data processing equipment. The Liebert NX UPS supplies power that is free of the disturbances and variations in voltage and ...
Page 62 - Normal Mode; to Normal mode, with the rectifier powering the critical load.; Bypass Mode; and any of the following occurs:; interrupt time setting.
Operation 54 7.1.1 Bypass Supplies The Liebert NX contains an electronically controlled switching circuit that enables the critical load to be connected to either the inverter output or to a bypass power source via the static bypass line. Dur- ing normal system operation the load is connected to the...
Page 63 - Maintenance Mode; permitting disconnecting the batteries for maintenance.; Parallel Redundancy Mode (System Expansion); maintenance mode, the input and output busbars remain energized.
Operation 55 Maintenance Mode For maintenance or repair, the Liebert NX may be operated in maintenance mode. To place the Lie- bert NX in maintenance mode, the load must be transferred to bypass and the inverter must be turned off. When those conditions are met, the CB3 may be turned on and the UPS ...
Page 64 - Operator Control and Display Panel; PERATOR; Operator Control Panel; Mimic Display
Operator Control and Display Panel 56 8.0 O PERATOR C ONTROL AND D ISPLAY P ANEL 8.1 Operator Control Panel The control panel and LCD on the front of the Liebert NX let the operator: • turn the UPS On or Off• transfer into the various operating modes• silence alarms• check the status of the UPS and ...
Page 65 - Figure 40 Detailed view of control panel; Mimic indicators; Rectifier indicator 8. Inverter Off Button
Operator Control and Display Panel 57 Figure 40 Detailed view of control panel 1 3 2 4 5 6 7 8 9 10 11 1213 14 15 16 17 18 19 Mimic indicators Control buttons Navigation keys 1. Rectifier indicator 8. Inverter Off Button 15. F1 2. Battery indicator 9. Emergency Power Off Button 16. F2 3. Inverter in...
Page 66 - Mimic Display Indicators; depicting the various paths of UPS power, as shown in; Figure 41 Mimic display indicators location; provides a guide to inter-; Mimic display status indicators
Operator Control and Display Panel 58 8.2 Mimic Display Indicators The Mimic display on the front panel consists of six indicators arranged in a single-line diagram depicting the various paths of UPS power, as shown in Figure 41 . Figure 41 Mimic display indicators location The current operational s...
Page 67 - The; Control Buttons; function of each button is described in; Figure 42 Location of control buttons; Completely shuts down the UPS, including the static switch.; Silence On/Off button; Inverter On button
Operator Control and Display Panel 59 8.3 Control Buttons The Control Buttons on the front panel may be used to shut down the UPS completely, turn the inverter On or Off, restart the UPS after a fault and silence the alarm, as shown in Figure 42 . The function of each button is described in Table 16...
Page 68 - Audible Buzzer; Figure 43 Buzzer location; LCD Overview; Figure 44 Sections of the LCD; Buzzer; Output; LCD menu
Operator Control and Display Panel 60 8.4 Audible Buzzer The buzzer produces three types of sounds: • Single beep - when any control button is pressed • Single beep repeating every two seconds - the system has a general alarm • Continuous - the system has a serious fault If the buzzer makes no sound...
Page 69 - Navigation Keys; UPS System Information; Icons for navigation keys; ESC
Operator Control and Display Panel 61 8.6 Navigation Keys The navigation keys on the front panel—F1 through F4 and Help—are used to access the LCD to view the current status and other information about the Liebert NX.Navigation key icons on the LCD appear above each key to indicate its operation (se...
Page 70 - LCD Menus and Data Items; menu choices are listed below and described in detail in; Figure 45 Menu tree
Operator Control and Display Panel 62 8.8 LCD Menus and Data Items The LCD menus provide access to the following categories of information and settings for the UPS. Selecting a menu changes the information displayed in the UPS data items portion of the LCD. The menu choices are listed below and desc...
Page 71 - Descriptions of UPS menus and data window items
Operator Control and Display Panel 63 Table 19 Descriptions of UPS menus and data window items Menu Type Item Type Explanation Mains (input) L-N current (A) Phase current Frequency (Hz) Input frequency L-L voltage (v Line-line voltage Power factor Power factor TX Input L-L voltage (V) Line-line volt...
Page 72 - Language Selection; Language
Operator Control and Display Panel 64 8.9 Language Selection The LCD menus and data display are available in 12 languages (Chinese, Dutch, English, French, German, Italian, Japanese, Polish, Portuguese, Russian, Spanish and Swedish). To select a different language: • From the main menu, press the F1...
Page 73 - Current Date and Time; Settings; Date format
Operator Control and Display Panel 65 8.10 Current Date and Time To change the system date and time: • From the main menu, press the F1 (shift) key to move the cursor to the menu at the top of the screen. • Press F2 and F3 (left and right arrows) as needed to select the Settings menu. • Press F1 (sh...
Page 74 - UPS Status Messages; The Liebert NX displays status changes as they occur in the; current status window of the LCD; then stores that data in the; history log; for a complete list of; History Log
Operator Control and Display Panel 66 8.11 UPS Status Messages The Liebert NX displays status changes as they occur in the current status window of the LCD , then stores that data in the history log , as shown in Figure 48 . • Current Status Window: The status messages are displayed chronologically ...
Page 75 - Types of LCD Screens; Figure 49 Opening display
Operator Control and Display Panel 67 8.12 Types of LCD Screens This section provides a quick guide to the main types of LCD screens. 8.12.1 Opening Display As the UPS begins powering up, the opening display appears, as shown in Figure 49 . Figure 49 Opening display 8.12.2 Default Screen After the U...
Page 76 - Press the HELP key below the LCD to display the Help window shown in; Figure 51 Help screen; active again when any key is pressed.; Figure 52 Screen saver window; Press any key back to main menu
Operator Control and Display Panel 68 8.12.3 UPS Help Screen Press the HELP key below the LCD to display the Help window shown in Figure 51 . (Press the HELP key again to exit the Help window.) Figure 51 Help screen 8.12.4 Screen Saver Window If there has been no interaction with the Liebert NX’s LC...
Page 77 - From Bypass to Inverter Mode With Power Interruption
Operator Control and Display Panel 69 8.13 Pop-Up Windows Pop-up prompt windows appear when the user must confirm a choice or perform an operation. This section describes the pop-up windows. 8.13.1 From Bypass to Inverter Mode With Power Interruption If the bypass voltage or frequency exceeds the sy...
Page 78 - Operating Instructions; Liebert NX Operating Modes; The Liebert NX can operate in any of four modes, as shown in; UPS operating modes; The UPS is powering the load.
Operating Instructions 70 9.0 O PERATING I NSTRUCTIONS 9.1 Liebert NX Operating Modes The Liebert NX can operate in any of four modes, as shown in Table 20 . This section provides instructions on switching between modes, resetting the UPS, switching the inverter On and Off and performing other opera...
Page 79 - Figure 53 Circuit breakers
Operating Instructions 71 9.1.1 Circuit Breakers The UPS can be isolated by means of circuit breakers, mounted inside the cabinet and accessible after opening the front door.The location of the UPS power switches is shown in Figure 53 . Figure 53 Circuit breakers The UPS unit circuit breakers are CB...
Page 80 - UPS Startup; output circuit breaker is still open, the UPS channels; Indicator
Operating Instructions 72 9.2 UPS Startup The Liebert NX must be fully installed and commissioned before startup, and external power isolators must be closed. Once those general conditions are met, the UPS may be started. 9.2.1 Startup Procedure To start the UPS from a fully powered-down condition:1...
Page 81 - Press the INVERTER ON control button for 2 seconds.; Verify Switching Between Operation Modes; after 10 seconds and resume feeding power to the inverter.; Switch from Normal Mode to Bypass Mode; • Press the INVERTER OFF button to switch to bypass mode.; Switch from Bypass Mode to Normal Mode; switch to normal mode.; through the inverter.
Operating Instructions 73 6. Press the INVERTER ON control button for 2 seconds. The inverter will start and the inverter indicator will flash green. After the inverter is ready, theUPS will transfer from bypass to inverter, the bypass indicator will turn off and the inverter and load indicators wil...
Page 82 - Maintenance Bypass Procedure and Powering Down the UPS; displayed until the relevant condition is rectified.
Operating Instructions 74 9.3 Maintenance Bypass Procedure and Powering Down the UPS Follow the procedure below to transfer the load from the inverter output to the Maintenance Bypass line of the UPS. This procedure assumes that the UPS is operating normally.1. Press the INVERTER OFF button on the o...
Page 83 - Auto Restart; margin for equipment shutdown if input power fails again.; Emergency Shutdown With EPO; there will be power at the output terminals of the UPS.
Operating Instructions 75 9.4 Auto Restart When the main and bypass sources fail, the UPS draws power from the battery system to supply the load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it will shut down.The UPS will automatically restart and enabl...
Page 84 - Battery Protection; masked and output becomes inhibited.
Operating Instructions 76 9.7 Battery Protection 9.7.1 Battery Undervoltage Pre-Warning Before the end of discharge, the Liebert NX displays a Low Battery pre-warning. After this pre-warn- ing, the battery has the capacity for 5 minutes discharging with full load (default time). The Liebert NX can b...
Page 85 - optional output / bypass distribution panel
Operating Instructions 77 Figure 54 Typical parallel system block diagram with common input supply, with separate batteries and optional output / bypass distribution panel NOTE All equipment servicing procedures must be carried out only by trained personnel. I Line Output Input 480V 3W+G FPC 480V 3W...
Page 86 - adjacent to the battery racks.; LED Function
Operating Instructions 78 9.8.2 Inserting One Module into a Multi-Module System This procedure outlines how to integrate a UPS module that has been previously isolated from other modules of a group of paralleled UPS modules. It is assumed that the installation is complete, the sys- tem has been comm...
Page 87 - Shutdown Procedure—Complete UPS and Load Shutdown; Commissioning a Parallel System; This procedure will shut off power to the load.
Operating Instructions 79 9.8.3 Shutdown Procedure—Complete UPS and Load Shutdown This procedure must be followed to completely power down the UPS and the load. All power switches, isolators and circuit breakers will be opened and power will be removed from the load.In multi-module systems, perform ...
Page 88 - Parallel System Start Up; Start each UPS normally as described in
Operating Instructions 80 9.10 Parallel System Start Up 1. Start each UPS normally as described in 9.2 - UPS Startup 2. Turn on the inverter of each UPS module one at a time.3. Apply the load after the last UPS module transfers to inverter. The total load can be determined through the LCD of either ...
Page 89 - Communication and Other User Terminals; such as Windows-based UPS Monitor, MultiLink; Figure 55 Monitoring board (U2) auxiliary terminal block detail; percent. “ENV-T” is used for environment temperature detecting.
Options 81 10.0 O PTIONS Several items of optional equipment are available for connection to the Liebert NX UPS. 10.1 Communication and Other User Terminals The UPS can be integrated into advanced networking environments via UPS monitoring software such as Windows-based UPS Monitor, MultiLink ™ , Nf...
Page 90 - Liebert IntelliSlot Web Card - SNMP/HTTP Network Interface Card; Liebert NX communication options
Options 82 10.1.4 Communication and Monitoring Liebert IntelliSlot Web Card - SNMP/HTTP Network Interface Card This network interface card provides all real-time data and status information as SNMPv1 traps for connection to a 10/100-baseT Ethernet connection. The same card also will transmit the sam...
Page 91 - appropriate Comm Channel.; Scroll down to view them on the screen.
Options 83 10.1.5 Configuring Baud Rates The default baud rate for Liebert IntelliSlots is 9600. To communicate with the OCWEB-LB, Modbus/ Jbus, or the MultiLink cards, the baud rate must be set to 2400.To change the baud rate (refer to Table 21 ): 1. Use the Navigation keys directly below the LCD t...
Page 92 - Figure 56 Liebert IntelliSlot Web card display
Options 84 Figure 56 Liebert IntelliSlot Web card display
Page 93 - Relay Card; On UPS
Options 85 Relay Card The relay card provides voltage-free contact closures for remote monitoring of alarm conditions.Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS sig- nals, the easy-to-install card integrates with AS/400 computers (additional cable required) an...
Page 94 - MultiPort 4 Card; Figure 57 MultiPort 4 card pin assignment; CPU; Pin
Options 86 MultiPort 4 Card The MultiPort 4 card provides four sets of voltage-free contact closures for remote monitoring of alarm conditions UPS operation On Battery and Low Battery condition. A typical application is to allow a maximum of four computer systems to simultaneously monitor the status...
Page 95 - LBS Mode—Load Bus Synchronization; to achieve dual bus configuration.; Replacing Dust Filters; dust filter in place, as shown in; Figure 58 Dust filter replacement; Sems screw
Options 87 10.2 LBS Mode—Load Bus Synchronization The function of LBS is to keep the output of two independent UPS systems (single unit or multiple unit) in synchronization even when the two systems are operating in different modes (bypass/ inverter) or on batteries. It is usually used with a Static...
Page 96 - Specifications and Technical Data; Lug Size and Torque Requirements; To help calculate the total cable length required, refer to; Torque specifications
Specifications and Technical Data 88 11.0 S PECIFICATIONS AND T ECHNICAL D ATA 11.1 Lug Size and Torque Requirements Use commercially available solderless lugs for the wire size required for your application. Refer to Table 24 . Connect wire to the lug using tools and procedures specified by the lug...
Page 97 - Distance to connection points on the Liebert NX UPS
Specifications and Technical Data 89 Liebert NX, then add the appropriate length from the table and adequate slack for repair and mainte- nance. Table 26 Distance to connection points on the Liebert NX UPS Connection Point on UPS Distance From Floor in. (mm) From Top of Unit in. (mm) Bypass AC input...
Page 98 - Cable size and tightening torques; External cabinet dimensions, including side panels
Specifications and Technical Data 90 11.3 Cable size and tightening torques Table 28 External cabinet dimensions, including side panels Type E1 Parallel Cabinet Unit Width Depth Height mm (inch) 1240 (48.8) 965 (38) 2000 (78.7) Type E Parallel Cabinet Unit Width Depth Height mm (inch) 845 (33.2) 965...
Page 99 - Cable size tightening torque at Liebert NX 80kVA UPS terminals
Specifications and Technical Data 91 Table 32 Cable size tightening torque at Liebert NX 80kVA UPS terminals Bus Type Cable Size (Copper Wire Only) Torque to Tighten Terminal Bus & Lug Body Main Input (Single Input) 2/0 10 N*m Main Input (Dual Input) 2/0 10 N*m Bypass Input (Dual Input) 1/0 10 N...
Page 100 - Battery Run Times; Estimated battery run time, minutes; Number of Cabinets
Specifications and Technical Data 92 11.4 Battery Run Times Table 35 Estimated battery run time, minutes UPS Rating/Model Number of Cabinets 1 2 3 4 40kVA UPS UPS12-100MR 5 18 32 47 UPS12-150MR 13 33 53 75 UPS12-210MR 21 51 81 123 60kVA UPS UPS12-100MR - 9 18 27 UPS12-150MR 7 19 33 47 UPS12-210MR 11...
Page 101 - PPENDIX; current status area and the history log, see; UPS Status Messages; Event Message
UPS Status Messages 93 A PPENDIX A - UPS S TATUS M ESSAGES Table 36 shows all event messages as they appear in the current status area of the LCD and in the history log, along with a description and recommended actions, if any. For further information on the current status area and the history log, ...
Page 102 - UPS status messages
UPS Status Messages 94 Bypass Unable to Trace This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage is beyond the normal range. The amplitude threshold is fixed for positive and negative 10% rating. This alarm automatically resets once the bypass v...
Page 108 - AC Power
EmersonNetworkPower.com Ensuring The High Availability0f Mission-Critical Data And Applications. Emerson Network Power, the global leader in enabling business-criticalcontinuity, ensures network resiliency and adaptability througha family of technologies—including Liebert power and coolingtechnologi...