Emerson 299H- Installation Manual

Emerson 299H

Emerson 299H– Installation Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
Page: / 8

Table of Contents:

  • Page 2 – Type VSX-2 Installation; Warning; Overpressure Protection; Type VSX-2 Trip Adjustment; To adjust the Overpressure Trip Spring:
  • Page 4 – To adjust the Underpressure Trip Spring:; Adjust the underpressure trip spring back to its; To avoid personal injury resulting from; Parts List; 99H Series Regulator; 99H Series Regulator
  • Page 5 – Optional P590 Series Filter; Type VSX-2 Assembly; VIEW A
  • Page 6 – 99H Series Registration Assemblies; 99H Series Pilot Assemblies
  • Page 7 – 99H Series Interior Assembly
  • Page 8 – 99H Series Exterior Assembly
Loading the manual

D102684XUS2

Installation Guide

English – September 2012

299H Series

www.fisherregulators.com

Introduction

This Installation Guide provides instructions for

installation, startup, and adjustment of 299H Series

regulators. To receive a copy of the Instruction

Manual, contact your local Sales Office or view

a copy at www.fisherregulators.com. For further

information refer to: 299H Series Instruction

Manual, form 5497, D102684X012.

P.E.D. Categories

This product may be used as a safety accessory

with pressure equipment in the following Pressure

Equipment Directive 97/23/EC categories. It may

also be used outside of the Pressure Equipment

Directive using sound engineering practice (SEP)

per table below.

product size

category

fluid type

DN 40, 50 / NPS 1-1/2, 2

I

1

Specifications

Available Configurations

Type 299H:

Pilot-operated pressure reducing

regulator with a pilot integrally mounted to the

actuator casing

Type 299HR:

A Type 299H with a token internal

relief valve to relieve minor overpressure caused

by thermal expansion

Type 299HS:

Same as the Type 299H

with a Type VSX-2 slam-shut valve which

provides overpressure or overpressure and

underpressure protection

Type 299HSR:

Same as the Type 299HS with

an internal token relief valve

Body Size and End Connection Styles

See Table 1

Maximum Operating Inlet Pressure

(1)

by Orifice Size

6.4 x 9.5 mm / 1/4 x 3/8 inch – 12.1 bar / 175 psig

9.5 mm / 3/8 inch – 12.1 bar / 175 psig

13 mm / 1/2 inch – 12.1 bar / 175 psig

19 mm / 3/4 inch – 10.3 bar / 150 psig

22 mm / 7/8 inch

(3)

– 8.6 bar / 125 psig

25 mm / 1 inch

(3)

– 6.9 bar / 100 psig

30 mm / 1-3/16 inch

(3)

– 5.5 bar / 80 psig

Maximum Casing and Emergency

Outlet Pressure

(1)

4.5 bar / 66 psig

Proof Test Pressure

All Pressure Retaining Components have been

proof tested per Directive 97/23/EC - Annex 1,

Section 7.4

Outlet (Control) Pressure Ranges

(1)(2)

See Table 2

Minimum Differential Pressure For Full Stroke

0.10 bar / 1.5 psi

Maximum Set Pressure for Type 299HS

(1)

1.1 bar / 16 psig

Maximum Set Pressure for Type VSX-2

Slam-Shut Device

(1)

1.6 bar / 23 psig

Minimum and Maximum Trip Pressure Ranges

(1)

See Table 3

Temperature Capabilities

(1)

-29 to 66°C / -20 to 150°F

Installation

Warning

!

Only qualified personnel should

install or service a regulator.

Regulators should be installed,

operated, and maintained in

accordance with international and

applicable codes and regulations,

and Emerson Process Management

Regulator Technologies Inc. (Regulator

Technologies) instructions.
If the regulator vents fluid or a leak

develops in the system, it indicates that

service is required. Failure to take the

regulator out of service immediately

may create a hazardous condition.
Personal injury, equipment damage,

or leakage due to escaping fluid

or bursting of pressure-containing

parts may result if this regulator is

overpressured or is installed where

service conditions could exceed the

limits given in the Specifications

section, or where conditions exceed

any ratings of the adjacent piping or

piping connections.

1. The pressure/temperature limits in this Installation Guide and any applicable

standard or code limitation should not be exceeded.

2. For optimum performance, a pilot supply regulator may be installed in the pilot

supply tubing between the main valve and pilot.

3. This orifice size is not available for Types 299HS and 299HSR.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Type VSX-2 Installation; Warning; Overpressure Protection; Type VSX-2 Trip Adjustment; To adjust the Overpressure Trip Spring:

2 299H Series To avoid such injury or damage, provide pressure-relieving or pressure- limiting devices (as required by the appropriate code, regulation, or standard) to prevent service conditions from exceeding limits.Additionally, physical damage to the regulator could result in personal injury and...

Page 4 - To adjust the Underpressure Trip Spring:; Adjust the underpressure trip spring back to its; To avoid personal injury resulting from; Parts List; 99H Series Regulator; 99H Series Regulator

4 299H Series To adjust the Underpressure Trip Spring: 1. Adjust the underpressure trip spring back to its minimum compression. 2. Backpressure the unit with the desired underpressure trip pressure. 3. Increase the underpressure trip spring compression until the Type VSX-2 trips. Taking Out of Servi...

Page 5 - Optional P590 Series Filter; Type VSX-2 Assembly; VIEW A

5 299H Series Figure 2. Optional P590 Series Filter 83 82 VIEW A T80423 Figure 1. Type VSX-2 Assembly 83 82 VIEW A VIEW A NOTE: FOR KEYS 82 AND 83, REFER TO 299H SERIES REGULATORS PARTS LIST. 6 5 2 5 7 1 4 3 VIEW A A7008

Other Emerson Models