Wall-Mounted RH Sensor and RH/Temperature Sensor

Product Information Sheet

203-5751

Overview

CPC specs a wall-mounted relative humidity (RH)
sensor (P/N 203-5751) and/or RH and temperature

sensor (P/N 203-5752) for use in building control and

anti-sweat control applications using CPC input

boards.

Specifications

General

Input Power

12VDC

Enclosure

High-impact plastic, white

Relative Humidity (RH)

Sensing
Element

Digitally profiled thin-film
capacitive

RH Accuracy

±3% RH over the range 20%-90%
RH

Stability

<0.5% RH per year

Operating
Humidity Range

0-100% RH

Analog Output

0-5VDC; 3-wire, observe
polarity

Scaling

0-100% RH

Temperature

Temperature
Accuracy

±0.4°F from 32°F to 140°F

Analog Out

Resistive, 2-wire, no polarity

Choosing a Mounting
Location

Mount the sensor indoors in a central location within

the zone to be measured, away from doors, windows,

vents, heaters, and outside walls that could affect
temperature readings. The sensor should be at least

four feet from the floor, and no higher than necessary

to prevent tampering.

Mounting

1.

Insert a screwdriver into the gap in the plastic
on the bottom side of the sensor enclosure,

and pry the front part of the enclosure away

from the rear mounting plate. Pull the front

away from the mounting plate until the top

separates from the mounting plate.

2.

Remove the punch outs above the wiring

connectors so that the sensor cables can be

run into the sensor enclosure (see Figure 1).

3.

Use the pre-made holes to mount the plate
on a junction box using the screws provided,

or mount it against a wall or riser. Do not

mount the plate upside down or sideways.

The plate should be mounted with the

terminal blocks toward the bottom.

4.

If necessary, drill or cut a hole in the wall to

allow the sensor cable to be run through the

wall into the sensor’s terminal block.






Figure 1 - RH/Temp Sensor Back Plate

Wall-Mounted RH Sensor and RH/Temperature Sensor

Product Information Sheet

29