1A11-2 LIGHT DUTY FAN COIL THERMOSTAT

For Direct Control of Line Voltage Valves and/or Blower Motors on

Fan Coil Units Featuring Manual Changeover From Heat to Cool and

a 3-Speed Fan Switch, Subbase Included

FEATURES

• Mounts to a standard vertical outlet box or on a two-gang outlet box. May also be

mounted on a 4

x 4

junction box with an adapter (not provided).

• Wiring color coded for ease of installation.

• 3-speed manual fan switch: High – Medium – Low.

• System Switch: Heat – OFF – Cool. “OFF” breaks both valve and fan circuits.

• Beige color.

1A11-2

– Thermostat cycles both fan and valve
– Thermostat cycles fan only (if valve is not used tape orange lead)

– System “OFF” breaks both valve and fan circuits

– Thermostat cycles valve only with continuous fan (interchange valve and L1 leads)

SPECIFICATIONS

Dimensions. . . . . . . . . . . . . . . . . . . . . . . . 4

1

/

2

H x 4

1

/

2

W x 2

1

/

4

D

Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . U.L. listed and C.S.A. approved

PARTS AND ACCESSORIES

• Thermostat guards – see pages 24-25

LINE VOLTAGE

THERMOSTATS

TAN

BLUE

COOL

COOL

HEAT

HEAT

VALVE

(SOL)

L1*

(HOT) GND

HIGH

HIGH

FAN

SWITCH

SYSTEM

SWITCH

MED

FAN

MED

OFF

LOW

LOW

RED

BLUE

RED

ORANGE

BLACK

GREEN

1A11-2

5-wire with ground, for single valve,

manual heat/cool changeover

CUSTOMER

CONNECTIONS

Note: Above FAN and SYSTEM switches shown in

MED and HEAT positions respectively.

THERMOSTAT

SCHEMATIC

*L1 is Power In

Model

Number

Range

Differential

Switch

Action

Contact Ratings

Pilot Duty

Motor Ratings (inductive) Full Load

Motor Ratings (inductive) Locked Rotor

120/240

120 VAC

240 VAC

277 VAC

120 VAC

240 VAC

277 VAC

277 VAC

1A11-2

36 to 90°F

(2 to 32°C)

1.5°F

SPDT

5.5A

2.75A

2.3A

33.0A

16.5A

13.8A

120A

THERMOST

ATS

www.white-rodgers.com