Installation Guide

English – July 2011

Types 1098-EGR and 1098H-EGR

www.fisherregulators.com

product sizes

categories

DN 25 / NPS 1

SEP

DN 50, 80, 100, 150, 200 x 150, 300 x 150 /

NPS 1, 2, 3, 4, 6, 8 x 6, 12 x 6

II

Introduction

This installation guide provides instructions for

installation, startup, and adjustment. To receive a copy

of the instruction manual, contact your local Sales Office

or view a copy at www.fisherregulators.com. For further

information refer to: Types 1098-EGR and 1098H-EGR
Instruction Manual, form 5084, D100339X012.

P.E.D. Categories

This product may be used as a safety accessory with

pressure equipment in the following Pressure Equipment

Directive 97/23/EC categories. It may also be used

outside of the Pressure Equipment Directive using sound
engineering practice (SEP) per table below.

Specifications

Body Sizes and End Connection Styles

See Table 1

Main Valve Maximum Inlet Pressure

(1)

27,6 bar / 400 psig or body rating limit whichever

is lower.

Maximum Pilot Supply Pressure

(1)

41,4 bar / 600 psig

Outlet Pressure Ranges

(1)

See Table 2

Actuator Sizes and Maximum Pressures

(1)

See Table 3

Maximum and Minimum Differential Pressures

(1)

See Table 4

Maximum Temperature Capabilities

(1)

Nitrile (NBR):

-20° to 180°F / -29° to 82°C

Fluorocarbon (FKM):

0° to 300°F / -18° to 149°C,

except water is limited to 0° to 200°F / -18° to 93°C

Ethylenepropylene (EPR):

-20° to 275°F / -29° to 135°C

1. The pressure/temperature limits in this installation guide and any applicable standard or code limitation should not be exceeded.

Installation

Only qualified personnel should install or

service a regulator. Regulators should

be installed, operated, and maintained

in accordance with international and

applicable codes and regulations, and

Fisher instructions.
If the regulator vents fluid or a leak

develops in the system, it indicates that

service is required. Failure to take the

regulator out of service immediately may

create a hazardous condition.
Personal injury, equipment damage, or

leakage due to escaping fluid or bursting of

pressure-containing parts may result if this

regulator is overpressured or is installed

where service conditions could exceed the

limits given in the Specifications section,

or where conditions exceed any ratings of

the adjacent piping or piping connections.
To avoid such injury or damage, provide

pressure-relieving or pressure-limiting

devices (as required by the appropriate

code, regulation, or standard) to prevent

service conditions from exceeding limits.
Additionally, physical damage to the

regulator could result in personal injury

and property damage due to escaping fluid.

To avoid such injury and damage, install

the regulator in a safe location.

Clean out all pipelines before installation of the regulator

and check to be sure the regulator has not been damaged

or has collected foreign material during shipping. For

NPT bodies, apply pipe compound to the external pipe

threads. For flanged bodies, use suitable line gaskets

and approved piping and bolting practices. Install the

regulator in any position desired, unless otherwise

specified, but be sure flow through the body is in the

direction indicated by the arrow on the body.

Note

It is important that the regulator be installed

so that the vent hole in the spring case

is unobstructed at all times. For outdoor

!

Warning

Table 1.

Body Sizes and End Connection Styles

BodY sizes

cast iron

steeL or stainLess steeL

dn

nps

25, 50

1, 2

NPT, CL125 FF, or CL250 RF

NPT, CL150 RF, CL300 RF,

CL600 RF, BWE, SWE, or PN 16/25/40

80, 100, 150

3, 4, 6

CL125 FF or CL250 RF

CL150 RF, CL300 RF, CL600 RF,

BWE, or PN 16/25/40

200 x 150, 300 x 150

8 x 6, 12 x 6

- - - -

CL150 RF, CL300 RF, CL600 RF,

or BWE

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Overpressure Protection; The recommended pressure limitations are stamped on

2 Types 1098-EGR and 1098H-EGR installations, the regulator should be located away from vehicular traffic and positioned so that water, ice, and other foreign materials cannot enter the spring case through the vent. Avoid placing the regulator beneath eaves or downspouts, and be sure it is above the...

Page 3 - Warning; Key Description; Type EGR Main Valve Assembly; Startup; results. With proper installation completed and relief; Adjustment

3 Types 1098-EGR and 1098H-EGR Taking Out of Service (Shutdown) To avoid personal injury resulting from sudden release of pressure, isolate the regulator from all pressure before attempting disassembly. ! Warning Type EGR Parts list (Figure 1) Key Description 1 Valve Body 2 Body Flange 3 Cap Screw o...

Page 4 - Standard P590 Series Filter Assembly; Key Description

4 Types 1098-EGR and 1098H-EGR Figure 2. Types 1098 and 1098H Actuator Assemblies TYPE 1098H P590 Series Parts list (Figure 3) Key Description 1 Filter Body 2 Filter Element 3 Filter Head 4 Machine Screw 5 Washer 6 Spring Washer 7 Gasket 11 NACE Tag (not shown) 12 Tag Wire (not shown) Types 1098 and...

Other Emerson Models