Page 1

1592020060 XR60CX GB m&M r1.1 27.04.2015

XR60CX

1/5

Digital controller with defrost and fans management

XR60CX

CONTENTS

1.

GENERAL WARNING ________________________________________________________ 1

2.

GENERAL DESCRIPTION ____________________________________________________ 1

3.

CONTROLLING LOADS ______________________________________________________ 1

4.

FRONT PANEL COMMANDS __________________________________________________ 1

5.

MAX & MIN TEMPERATURE MEMORIZATION ____________________________________ 1

6.

MAIN FUNCTIONS __________________________________________________________ 2

7.

PARAMETERS _____________________________________________________________ 2

8.

DIGITAL INPUT (ENABLED WITH P3P = N) ______________________________________ 3

9.

TTL SERIAL LINE – FOR MONITORING SYSTEMS ________________________________ 3

10.

X-REP OUTPUT – OPTIONAL _________________________________________________ 3

11.

INSTALLATION AND MOUNTING ______________________________________________ 3

12.

ELECTRICAL CONNECTIONS _________________________________________________ 3

13.

HOW TO USE THE HOT KEY __________________________________________________ 3

14.

ALARM SIGNALS ___________________________________________________________ 3

15.

TECHNICAL DATA __________________________________________________________ 4

16.

CONNECTIONS _____________________________________________________________ 4

17.

DEFAULT SETTING VALUES __________________________________________________ 4

1.

GENERAL WARNING

1.1

PLEASE READ BEFORE USING THIS MANUAL

This manual is part of the product and should be kept near the instrument for easy and quick
reference.

The instrument shall not be used for purposes different from those described hereunder. It
cannot be used as a safety device.

Check the application limits before proceeding.

Dixell Srl reserves the right to change the composition of its products, even without notice,
ensuring the same and unchanged functionality.

1.2

SAFETY PRECAUTIONS

Check the supply voltage is correct before connecting the instrument.

Do not expose to water or moisture: use the controller only within the operating limits avoiding
sudden temperature changes with high atmospheric humidity to prevent formation of
condensation

Warning: disconnect all electrical connections before any kind of maintenance.

Fit the probe where it is not accessible by the End User. The instrument must not be opened.

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell
S.r.l.” (see address) with a detailed description of the fault.

Consider the maximum current which can be applied to each relay (see Technical Data).

Ensure that the wires for probes, loads and the power supply are separated and far enough
from each other, without crossing or intertwining.

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in
parallel with inductive loads could be useful.

2.

GENERAL DESCRIPTION

Model

XR60CX

, format 32 x 74 mm, is microprocessor based controller, suitable for applications on

medium or low temperature ventilated refrigerating units. It has three relay outputs to control
compressor, fan, and defrost, which can be either electrical or reverse cycle (hot gas). It is also
provided with three NTC or PTC probe inputs, the first one for temperature control, the second one,
to be located onto the evaporator, to control the defrost termination temperature and to managed the
fan, the third one, optional, to connect to the HOT KEY terminals to signal the condenser
temperature alarm or to display a temperature. The digital input can operate as fourth temperature
probe.
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a
network line

ModBUS-RTU

compatible such as the Dixell monitoring units of X-WEB family. It allows

to program the controller by means the HOT KEY programming keyboard.
The instrument is fully configurable through special parameters that can be easily programmed
through the keyboard.

3.

CONTROLLING LOADS

3.1

COMPRESSOR

The regulation is performed according
to the temperature measured by the
thermostat probe with a positive
differential from the set point: if the
temperature increases and reaches set
point plus differential the compressor is
started and then turned off when the
temperature reaches the set point value
again.

Time

Temper.

Compr.

SET

ON

In case of fault in the thermostat probe the start and stop of the compressor are timed through
parameters “

COn

” and “

COF

”.

3.2

DEFROST

Two defrost modes are available through the “

tdF

” parameter: defrost through electrical heater (

tdF

= EL

) and hot gas defrost (

tdF = in

). Other parameters are used to control the interval between

defrost cycles (IdF), its maximum length (MdF) and two defrost modes: timed or controlled by the
evaporator’s probe (P2P).
At the end of defrost dripping time is started, its length is set in the Fdt parameter. With Fdt =0 the
dripping time is disabled.

3.3

CONTROL OF EVAPORATOR FANS

The fan control mode is selected by means of the “

FnC

” parameter:

FnC = C_n:

fans will switch ON and OFF with the compressor and

not run

during defrost;

FnC = o_n

fans will run even if the compressor is off, and not run during defrost;

After defrost, there is a timed fan delay allowing for drip time, set by means of the “

Fnd

” parameter.

FnC = C_Y

fans will switch ON and OFF with the compressor and

run

during defrost;

FnC = o_Y

fans will run continuously also during defrost

An additional parameter “

FSt

” provides the setting of temperature, detected by the evaporator probe,

above which the fans are always OFF. This is used to make sure circulation of air only if his
temperature is lower than set in “FSt”.

3.3.1 Forced activation of fans

This function managed by the

Fct

parameter is designed to avoid short cycles of fans, that could

happen when the controller is switched on or after a defrost, when the room air warms the
evaporator.

Functioning:

if the difference of temperature between the evaporator and the room

probes is more than the value of the Fct parameter, the fans are switched on. With Fct=0 the function
is disabled.

3.3.2 Cyclical activation of the fans with compressor off.

When Fnc = c-n or c-Y (fans in parallel to the compressor), by means of the Fon and FoF
parameters the fans can carry out on and off cycles even if the compressor is switched off. When the
compressor is stopped the fans go on working for the Fon time. With Fon =0 the fans remain always
off, when the compressor is off.

4.

FRONT PANEL COMMANDS

: To display target set point; in programming mode it selects a parameter or confirm an

operation.

(DEF)

To start a manual defrost

(

UP)

: To see the max. stored temperature; in programming mode it browses the parameter

codes or increases the displayed value.

(

DOWN

) To see the min stored temperature; in programming mode it browses the parameter

codes or decreases the displayed value.

To switch the instrument off, if onF = oFF.

Not enabled.

KEY COMBINATIONS:

+



To lock & unlock the keyboard

.

+

To enter in programming mode.

+

To return to the room temperature display.

4.1

USE OF LEDS

Each LED function is described in the following table.

LED

MODE

FUNCTION

ON

Compressor enabled

Flashing

Anti-short cycle delay enabled

ON

Defrost enabled

Flashing

Drip time in progress

ON

Fans enabled

Flashing

Fans delay after defrost in progress.

ON

An alarm is occurring

ON

Continuous cycle is running

ON

Energy saving enabled

°C/°F

ON

Measurement unit

°C/°F

Flashing

Programming phase

5.

MAX & MIN TEMPERATURE MEMORIZATION

5.1

HOW TO SEE THE MIN TEMPERATURE

1.

Press and release the

n

key.

2.

The “Lo” message will be displayed followed by the minimum temperature recorded.

3.

By pressing the

n

key again or by waiting 5s the normal display will be restored.

5.2

HOW TO SEE THE MAX TEMPERATURE

1.

Press and release the

o

key.

2.

The “Hi” message will be displayed followed by the maximum temperature recorded.

3.

By pressing the

o

key again or by waiting 5s the normal display will be restored.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Was this manual helpful?

About this manual

Brand
Dixell
Model
Universal XR60CX
Document type
Manual
Category
Thermostat
Language(s)
English
Pages
5
Format
PDF

Summary

Page 2 - optional

1592020060 XR60CX GB m&M r1.1 27.04.2015 XR60CX 2/5 5.3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 1. Hold press the SET key for more than 3s, while the max. or min temperature is displayed. (rSt message will be displayed) 2. To confirm the operation the “rSt” message starts blinking and ...

Page 3 - DIGITAL INPUTS POLARITY; EXCLUDES; the serial connection.; PROBE CONNECTION

1592020060 XR60CX GB m&M r1.1 27.04.2015 XR60CX 3/5 Ab= absolute temperature: alarm temperature is given by the ALL or ALU values. rE = temperature alarms are referred to the set point. Temperature alarm is enabled when the temperature exceeds the “SET+ALU” or “SET-ALL” values. ALU MAXIMUM tempe...

Page 4 - TECHNICAL DATA; Line; Comp; DEFAULT SETTING VALUES; dPo

1592020060 XR60CX GB m&M r1.1 27.04.2015 XR60CX 4/5 Message Cause Outputs “P3” Third probe failure Outputs unchanged “P4” Fourth probe failure Outputs unchanged “HA” Maximum temperature alarm Outputs unchanged. “LA” Minimum temperature alarm Outputs unchanged. "HA2" Condenser high temper...