Delta SSW 230 V - 20 kVA - Manual

Delta SSW 230 V - 20 kVA

Delta SSW 230 V - 20 kVA – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
Page: / 1
Loading the manual

SSW 230V-6kVA


SSW 230 V – 20 kVA






Description:

The static switch product line is a micro-controller driven
state-of-the-art switch between the AC mains and the
inverter to provide uninterruptible AC power. After an
extremely quick detection of a mains fault, the static
switch transfers the load almost without cut off to the
redundant AC line. A communication and synchronization
bus is responsible for the system performance and the
Delta inverters are synchronized to the public AC mains.
Modular UPS configurations in ON LINE or OFF LINE
mode can be realized in combination with Delta inverters
and DC power systems with battery backup.

Features

Two static switch models 6 kVA and 20 kVA

230 Vrms / 50 Hz single phase

ON LINE or OFF LINE mode selection

High performance AC line quality monitoring

Quick detection of AC faults

Configurable switching criteria

Load transfer of up to 6 kVA or 20 kVA

Synchronization of the Delta inverter group

Convection cooled

Compact and light

Power connectors on the rear











Specification

General

Product name

SSW 230 V – 6 kVA

SSW 230 V – 20 kVA

Safety

EN 60 950, class I

EMI, radiated compliant with

EN 55 022, class B

EN

300

386-2

Cooling Convection cooled

Public AC Input

Voltage range

184 ... 276 V

rms

Frequency range

45 - 55 Hz

EMI, conducted compliant with EN 55022, class B

Inverter AC Input

Voltage range

230 V

rms

± 1%

Frequency

50 Hz

EMI, conducted compliant with EN 55022, class B

AC Output

Voltage, nominal

230 V

rms

Frequency, nominal

50 Hz

Maximum power

6 kVA / 20 kVA

cos

φ

, range

0 .. 1 ind. and cap.

EMI, conducted compliant with EN 55022, class B

Mechanics

6kVA

;

20kVA

Width, overall

2.8” / 70 mm

;

5.3” / 135 mm

Depth, overall

13.8” / 350 mm

;

13.8” / 350 mm

Height, overall

12.2” / 311 mm

;

12.2” / 7U / 311 mm

Weight

7.7 lb / 3.5 kg

;

18.0 lb / 8.6 kg

Switching Criteria

According to

ETS 300 132-1

Static rms deviation

± 10 %

Dynamic rms deviation

± 15 % for max. 500 ms

Static freq. deviation

± 2Hz

Dynamic freq. deviation

± 2Hz for 5 s maximum

Environment

Operating temperature

0 ... + 50 °C

Relative humidity 95 % max, non condensing