The FR 2000 rectifier is a single phase, hot-pluggable, fan-cooled rectifier. The constant output power characteristic
supplies the specified power over the full output voltage range. The benefit is an optimised modular system design
(fewer number of modules) and matches the supply requirements for state-of-the-art telecom equipment. This
performance as well as the extended temperature range, wide input voltage range, high power density and
advanced technology are the key factors of the success of this rectifier and it offers a cost effective and reliable
solution.
The rectifier meets the requirements set by the telecommunications standards.


Features

Efficiency

91%

Compact (500 W / l) and light (4.4 kg)

Hot pluggable, all connectors at the rear

Fan cooled with air flow monitoring

Wide input voltage range: 88 - 276 V

rms

Power factor ~ 1.0 (sinusoidal input current)

Constant output power characteristic

Analogue system bus

Operating temperature range up to 70°C


Specification

General

Product name

FR 48 V - 2000 W - E

Efficiency

91 %

Losses, max.

200 W

Safety

EN 60 950, class I

UL 60 950

CAN / CSA – C22.2

EMI, radiated compliant with

EN 55 022, class B

EN 300 386-2

Cooling Fan

cooled

Power density 500 W / l 8.2 W / in

3

Input

Voltage range

88 ... 276 V

rms

Volt. range, red. power

88 ... 184 V

rms

Current maximum

12 A

rms

Line current

Meets IEC 1000-3-2

THD

< 5 %

EMI, conducted

EN 55 022, class B

Output

Voltage, nominal

53.5 V

dc

Voltage adjust range

42 ... 58 V

dc

Voltage error, static

± 250 mV

dc

EMI, conducted compliant with EN 55 022, class A
Current limit, nominal

46.5 A

dc

Limit adjustment range

0 ... 46.5 A

dc

Load sharing

<

±

3 A

dc

Power limit 2000 W, fixed

Mechanics

Width, overall

2.6” / 65 mm

Depth, overall

13.6” / 346 mm

Height, body

7.9” / 200 mm

Weight 9.7 lb / 4.4 kg

Environment

Ambient temperature

-25 ... + 70 °C

Reduced power

60 ... + 70 °C

Relative humidity 95 % max, non cond.

Accessories

Single back plane P/N: D0100298