Delta ESI 48/230V - Manual
Delta ESI 48/230V – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Description:
The ESI 48/230V inverters are single phase, fan-cooled inverters. They convert all direct voltages from 48 V battery
systems to an uninterruptible, stabilized AC voltage. The outstanding dynamic performance matches the supply
requirements for state-of-the-art telecom equipment. This performance as well as the advanced technology is the
key factors of the success of this inverter and it offers a cost effective and reliable solution.
Features
•
Standard 19”, 23”and 25” rack
•
1KVA/800W, 2KVA/1600W
•
Selectable 208/220V/230V/240V system output
•
High efficiency
•
Pure sine wave output
•
Compact, lightweight modular design
•
Bypass function
•
RS-232 communication
•
User friendly LED and LCD display
Specification
General
Product name
ESI 48 / 230 V – 1k VA
ESI 48 / 230 V – 2k VA
Efficiency, at 230Vrms
85 %
Safety UL
60950
EN
60950
CAN/CSA-C22.2
No.
60950
EMI, radiated compliant with
FCC Part 15 class A
EN 55022 class A
Cooling Fan
cooled
On/Off Switch
Yes
MTBF
450K Hours
Input
Input voltage
40 … 60 V
dc
Rated current
25 A (1k VA) / 50 A (2k VA)
EMI, conducted
EN 55022, class A
Input protection
Fuse and DC breaker
AC Input(Bypass)
Input voltage
208 / 220 / 230 / 240 V
rms
± 20 V
rms
Frequency
50 / 60 Hz ± 5 Hz
EMI, conducted compliant with FCC Part 15 class A
EN 55022 class A, EN 55022 class A
Output
Output voltage
208 / 220 / 230 / 240 V
rms
Voltage regulation
< ± 2 %
Frequency
50 / 60 Hz ± 0.2 Hz
THD
3 %: 100% liner load
5 %: 100% SPS load
Current, nominal
5 A
rms
(1k VA)
10
A
rms
(2k VA)
Crest factor
3 : 1
Power, nominal
1k VA / 800 W
2k VA / 1600 W
Mechanics
Width, overall
17.3” / 440 mm
Depth, overall
11.8” / 300 mm
Height, overall
3.5” / 88.0 mm
Weight
17.6 lb / 8.0 kg (1k VA)
18.7 lb / 8.5 kg (2k VA)
Environment
Operating temperature
0 ... + 45 °C
Relative humidity
20 ~ 90 %, non condensing
Altitude
- 500 ~ 10000 feet
*Specifications are subject to change due to technical progress
The ESI 48/230V Inverter
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.