Delta DVPPF02-H2 - Manual

Delta DVPPF02-H2

Delta DVPPF02-H2 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
Page: / 2
Loading the manual

Warning

Please read this instruction sheet carefully before use and follow this instruction to operate the device in order
to prevent damages on the device or injuries to staff.

Switch off the power before wiring.

This instruction sheet only provides introductory information on electrical specification, functions, wiring,
trouble-shooing the peripherals for DVPPF02-H2. Details of PROFIBUS DP protocol are not included in this
sheet. For more information on PROFIB US DP protocol, please refer to relevant reference or literatures.

DVPPF02-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the
device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device
may occur.

DVPPF02-H2 is to be used for controlling the operating machine and equipment. In order not to damage it,
only qualified professional staff familiar with the structure and operation of if can install, operate, wire and
maintain it.

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur.
Check all the wiring again before switching on the power, and DO NOT touch any terminal when the power is
switched on. Make sure the ground terminal

is correctly grounded in order to prevent electromagnetic

interference.

Introduction

Thank you for choosing Delta DVPPF02-H2 PROFIBUS DP communication module. DVPPF02-H2 can
be applied to the connection with DVP-EH2 series PLC MPU in a PROFIBUS DP network. DVPPF02-H2
does not need to be connected to an external power supply. The power will be supplied from DVP-EH2
once it is connected to DVP-EH2.

Features

1. Supports loop-type data exchange between DP master and many slaves.
2. Supports GSD files in PROFIBUS DP network configuration tools.
3. Supports 4 slots in PROFIBUS DP network configuration tools.
4. Auto-detects baud rates; supports Max. 12Mbps.
5. The length of I/O data can be freely configured through PROFIBUS DP network configuration tools.

Max. input data length = 100 words (the sum of 4 slots); Max. output data length = 100 words (the
sum of 4 slots).

6. Error code diagnosis.

Product Profile & Outline

82 [3. 228]

9

0

[ 3

.5

4

3

]

40 [1. 575]

7

[0

.2

7

6

]

P O WE R

NET

X

1 6

X

1 6

2

3

5

4

6

7

1

8

Unit: mm

1

Extension port

2

Address setup switch

3

POW ER indicator

4

NET indicator

5

PROFIBUS DP connector

6

Extension module interface

7

DIN rail clip

8

DIN rail

ENGLISH

Specifications

PROFIBUS DP Connector

Interface

DB9 connector

Transmission
method

High-speed RS-485

Transmission cable

Shielded twisted pair cable

Electrical isolation

500V DC

Communication

Message type

Loop-type data exchange

Equipment ID

0AFE (hex)

Serial transmission

speed supported

(auto-detection)

9.6kbps; 19.2kbps; 93.75kbps; 187.5kbps; 500kbps; 1.5Mbps; 3Mbps; 6Mbps;
12Mbps (bits per second)

Environment

Standards

IEC 61131-2,UL508

Storage/operation

Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), pollution degree 2

Shock/vibration
immunity

International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC
68-2-27 (TEST Ea)

Interference
immunity

RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1000MHz, 1.4GHz ~ 2GHz, 10V/m
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge

Certificates

CE, UL

Components

PROFIBUS DP Connector

To connect to PROFIBUS DP network, use standard DP connector for the wiring.

PIN

PIN name

Definition

1

-

Not defined

2

-

Not defined

3

Rxd/Txd-P

Sending/receiving data P(B)

4

-

Not defined

5

DGND

Data reference potential

6

VP

Power voltage - positive

7

-

Not defined

8

Rxd/Txd-N

Sending/receiving data N(A)

9

-

Not defined

1

6

5

9

Address Setup Rotary Sw itch

The two rotary address setup switches set up the node addresses on
PROFIBUS DP network in hexadecimal form. Setup range: 0x01 ~ 0x7D (0 or
0x7E ~ 0xFF are forbidden).

Rotary switch

x 16

1

x 16

0

Multiple

× 16

× 1

N

O

D

E

A

D

D

R

E

S

S

x 1 6

0

x 1 6

1

Example:

If you need to set the node address of DVPPF02-H2 as 26 (1A Hex) , simply switch the

corresponding rotary switch of x16

1

to “1" and the corresponding rotary switch of x16

0

to”A”.

Switch setting

Description

0x01 ~ 0x7D

Valid PROFIBUS DP address

0 or 0x7E ~ 0xFF

Invalid PROFIBUS DP address

Note:

The changed values on switches are

only valid when DVPPF02-H2 is re-powered.
When DVPPF02-H2 is operating, changing
the set value of the address will be regarded
invalid.

Extension Port

The extension port on DVPPF02-H2 is used for the connection to the next DVPPF02-H2 or extension
modules of DVP-EH2 series PLC MPU.

Basic Operation

Connecting DVPPF02-H2 to DVP-EH2 Series PLC MPU

S TO P

R UN

0

1

IN

O UT

P O W E R

R UN

E R RO R

B AT .L OW

D V P - 2 0 E H

x 16

0

x 16

1

Switch off DVP-EH2. Open the connection

port on the right hand side of DVP-EH2 and

connect DVPPF02-H2 to DVP-EH2. Switch

on DVP-EH2, and DVP-EH2 will supply

power to DVPPF02-H2. There is no need to

connect DVPPF02-H2 to an external power

supply.

Installing DVP-EH2 and DVPPF02-H2 on DIN Rail

x 16

0

x 16

1

STO P

R UN

0

1

IN

OUT

P O WE R

RUN

E RR OR

B A T.LO W

DV P- 2 0E H

1. Use 35mm DIN rail.

2. Open the DIN rail clips on DVP-EH2 and

DVPPF02-H2. Insert DVP-EH2 and

DVPPF02-H2 on the DIN rail.

3. Clip up the DIN rail clips on DVP-EH2

and DVPPF02-H2 to fix DVP-EH2 and

DVPPF02-H2 on the DIN rail.

Connecting to PROFIBUS DP Connector

Insert the PROFIBUS DP bus connector into

the PROFIBUS DP connector on

DVPPF02-H2. Screw it tight to ensure

DVPPF02-H2 and the PROFIBUS DP bus

are properly connected.

Installation & Wiring

1. Install DVPPF02-H2 in an enclosure with sufficient

space around it to allow heat dissipation (see the
figure).

2. DO NOT place the I/O signal wires and power

supply wire in the same wiring circuit.

D>5 0mm

PF 0 2- H2

D

D

D

D

D

D

E 2 PL C

H

Control Register

The control registers (CR) are the registers inside DVPPF02-H2. See the table below for the definitions of
all the CRs. DVP-EH2 series PLC MPU can read or write the CR allowed through DFROM/DTO
instructions.

CR#

Attribute

Content

High byte

Low byte

#0

Read

Model name

DVPPF02-H2 model code = H

0250

#1

Read

Firmware version

Displaying the current firmware version in hex, e.g.
V1.00 is indicated as H’0100.

#2

Read

Length of I/O data

Length of output I/O data Length of input I/O data

#3 ~ #102

Write/read

Input data mapping

Area for storing data from DVPPF02-H2 to
PROFIBUS DP master

#103 ~ #202

Read

Output data
mapping

Area for storing data from PROFIBUS DP master to
DVPPF02-H2.

#203 ~ #206

Set up by the system. DO NOT use it.

#207 ~ #250

Reserved

#251

Read

Error

Register for storing errors. See

for error codes.

#252 ~ #383

Reserved

#384 ~ #511

Set up by the system. DO NOT use it.

LED Indicators & Trouble-Shooting

There are 2 LED indicators on DVPPF02-H2. POWER indicator displays the status of the working power.
NET indicator displays the connection status of the communication.

POWER LED

LED status

Indication

How to deal with it?

Green light on

The power is normal.

--

Off

No power

1. Check if the power of DVP-EH2 is normal.

2. Check if the connection between DVPPF02-H2

and DVP-EH2 is normal.

NET LED

LED status

Indication

How to deal with it?

Off

No power

1. Check if the power of DVP-EH2 is normal

2. Check if the connection between DVPPF02-H2

and DVP-EH2 is normal

Red light on

DVPPF02 is operating but is
not connected to PROFIBUS
DP bus.

Check if DVPPF02-H2 is normally connected to
PROFIBUS DP bus.

Red light
flashes

Depending on the value in
CR#251

See the error code table for how to deal with it.

Green light on

DVPPF02-H2 is in data
exchange status.

--

Error Codes

Code

Description

How to deal with it?

00

DVPPF02-H2 operates normally.

--

01

Hardware error

Send your DVPPF02-H2 back to the factory for
repair.

02

PROFIBUS DP watch dog error

Check if DVPPF02-H2 is normally connected to
PROFIBUS DP bus.

03

Address setup error (0, or exceeding
0x01 ~ 0x7D)

Set the address within the range 0x01 ~ 0x7D and
re-power DVP-EH2.

04

24V low voltage error

Check if the power voltage of DVP-EH2 is normal;
check if DVPPF02-H2 is normally connected to
DVP-EH2.

05

5V low voltage error

Send your DVPPF02-H2 back to the factory for
repair.

注意事項

使用前請務必仔細閱讀本使用手冊,並依照本手冊指示進行操作,以免造成產品受損或人員受傷。

配線時請務必關閉電源。

本使用說明書僅提供電氣規格、功能規格、安裝配線、故障排除及周邊裝置部分說明,本使用說明書僅
作為

DVPPF02-H2

操作指南和入門參考,

PROFIBUS DP

協定的詳細內容這裏不作介紹。如果讀者想瞭

解更多

PROFIBUS DP

協定的內容,請參閱相關專業文章或書籍資料。

本機為開放型機殼,因此使用者使用本機時,必須將其安裝於具防塵、防潮及免於電擊∕衝擊意外的外

殼配線箱內。另必須具備保護措施(如:特殊的工具或鑰匙才可打開),防止非維護人員操作或意外衝
擊本體,造成危險及損壞。

本產品用來控制運轉中的機械及設備。為避免損壞本產品,只有合格且熟悉本產品結構及操作的專業人
員才可進行本產品的安裝、操作、配線及維護。

交流輸入電源不可連接於輸入∕輸出信號端,否則可能造成嚴重損壞。請在上電前再次確認電源配線,
且請勿在上電時觸摸任何端子。本體上的接地端子

務必正確的接地,以提高產品抗雜訊能力。

產品簡介

謝謝您使用台達

DVPPF02-H2

網路通訊模組。

DVPPF02-H2

定義為

PROFIBUS DP

通訊模組,可用於

PROFIBUS DP

網路與

DVP-EH2

系列

PLC

主機的連接,

DVPPF02-H2

無需外接電源,與

DVP-EH2

主機連

接好後由

DVP-EH2

主機提供電源。

功能特色

1.

支持

DP

主站與多個從站之間的迴圈資料傳輸。

2.

PROFIBUS DP

網路配置工具中支援

GSD

文檔。

3.

PROFIBUS DP

網路配置工具中支援

4

(slot)

配置。

4.

自動偵測通訊速率,最高通訊速率支援

12Mbps

5.

I/O

資料長度可通過

PROFIBUS DP

網路配置工具自由配置

,

輸入資料長度總和最大可配置

100

word

4

slot

配置長度之和),輸出資料長度總和最大可配置

100

word

4

slot

配置長度之和)。

6.

錯誤碼診斷功能。

產品外觀及各部介紹

8 2 [ 3 . 2 2 8]

9

0

[3

.5

4

3

]

40 [1 . 5 7 5]

7

[0

.2

7

6

]

P O WE R

NET

X

1 6

X

1 6

2

3

5

4

6

7

1

8

尺寸單位:

mm

1

擴充模組連接埠

2

位址設定開關

3

POWER LED

指示燈

4

NET LED

指示燈

5

PROFIBUS DP

通訊連接器

6

擴充模組連接頭

7

DIN

軌固定扣

8

DIN

軌槽

繁體中文

功能規格

PROFIBUS DP

連接器

接頭

DB9

接頭

傳輸方式

高速

RS-485

傳輸電纜

遮罩式雙絞線

電氣隔離

500V DC

通訊

資訊類型

迴圈式資料交換

.

設備

ID

0AFE (hex)

支援串列傳輸速度

(自動偵測)

支持

9.6kbps; 19.2kbps; 93.75kbps; 187.5kbps; 500kbps; 1.5Mbps; 3Mbps; 6Mbps;

12Mbps

(位元∕秒)

環境規格

標準

IEC 61131-2,UL508

標準

操作∕儲存環境

儲存:

-25°C ~ 70°C

(溫度),

5 ~ 95%

(濕度)

操作:

0°C ~ 55°C

(溫度),

50 ~ 95%

(濕度),污染等級

2

耐震動∕衝擊

國際標準規範

IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27

(TEST Ea)

雜訊免疫力

RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1000MHz, 1.4GHz ~ 2GHz, 10V/m
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge

認證專案

CE

認證、

UL

認證

各部分元件介紹

PROFIBUS DP

通訊連接器

PROFIBUS DP

網路連接時,使用標準

PROFIBUS DP

連接器進行配線。

接腳

名稱

定義

/

說明

1

-

未指定

2

-

未指定

3

Rxd/Txd-P

接收∕發送資料

P (B)

4

-

未指定

5

DGND

資料參考接地

6

VP

電源電壓

-

正壓

7

-

未指定

8

Rxd/Txd-N

接收∕發送資料

N (A)

9

-

未指定

1

6

5

9