Page 3 - IMPORTANT INFORMATION - READ CAREFULLY; DANGER; Indicates an imminently haz ardous situation; CAUTION; WARNING; Indicates a potentially haz ardous situation; NOTICE; Indicates special instructions on installation,
3 IMPORTANT INFORMATION - READ CAREFULLY , g n i b m u l P l a c o L d n a e t a t S ,l a n o it a N h ti w e c n a d r o c c a n i d e ll a t s n i e b t s u m s r e li o b ll A e s e h T . s e it il it u g n i v r e s e h t f o s n o it a l u g e r e h t d n a s e d o C l a c i r t c e l E d n a g...
Page 4 - by ow ner and service technician.
4 WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Failure to follow all instructions in the proper order can cause personal injury or death. R ead and understand all instructions, including all those contained ...
Page 5 - boiler. See page 9 for standard safety relief valve set pressures.
5 G N I N R A W , a n i m u l a n i a t n o c l e u f e h t d n a n o it s u b m o c f o s t c u d o r p , n o it c u r t s n o c f o s l a ir e t a m e c n a il p p A r o c i x o t r e h t o r o / d n a s e d y h e d l a , s e d i x o n e g o r ti n , e d i x o n o m n o b r a c , s l a t e m y v a...
Page 6 - TABLE OF CONTENTS
6 SECTION I - GENERAL INFORMATION Dimensional Information ............................................................................................................................................... 8 Ratings/Data ......................................................................................
Page 7 - Primary Loop using Sequencer and Outdoor Reset.; TABLE OF CONTENTS - Continued
7 SECTION VI - BURNER SPECIFICATIONS Beckett Burners (Table VI) ........................................................................................................................................... 57 SECTION VII - REPAIR PARTS & CARTON CONTENTS Regional Office Directory ......................
Page 8 - Section I - General Information; FIGURE 1: Dimensional Information
8 Section I - General Information FIGURE 1: Dimensional Information
Page 9 - TABLE I; Maximum Allowable Working Pressure:
9 TABLE I BOILER RATINGS/DATA ) 1 ( ) 2 ( ) 3 ( ) 4 ( r e li o B l e d o M - e s r o H r e w o P s s o r G t u p t u O ) H B M ( g n it a R R = B = I t e N r e n r u B t u p n I g n it a e H e c a f r u S ). t F . q S ( t e N x o b e ri F e m u l o V ). t F . u C ( e r u s s e r P n i x o b e ri F )...
Page 10 - R ecommended clearance for service may be; Table III: Recommended Rear Service Clearance
10 SECTION I - GENERAL INFORMATION (CONTINUED) A . INSPECT SHIPMENT carefully for any signs of damage.1. ALL EQUIPMENT is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of crated boiler to the carrier in good condition. 2. ANY CLAIMS for damage or shortage in s...
Page 11 - WAR N IN G; Failure to supply adequate air to the boiler
11 Figure 2: Boiler Foundation Figure 3a: Typical Arrangement for Stub Vent C . PROVIDE AIR SUPPLY AND VENTILATION to accommodate proper combustion. For commercial and industrial equipment, permanent facilities for supplying an ample amount of outside air shall be provided in accordance with the fol...
Page 12 - FIGURE 3b: VENTS — FAULTS & SUGGESTIONS; VENT SIZING; FAULTY BOILER BURNER OPERATION
12 G N I N R A W f o n g i s e d e h t n o t r e p x e g n it n e v a tl u s n o C . y l n o s n o it a d n e m m o c e r e r a s n o it c u r t s n I g n it n e V l a n o it a N e h T d n a e d i u G g n it n e V E A R H S A e h T . n o it a c il p p a r u o y r o f m e t s y s t n e v c if i c e p...
Page 13 - B oiler sections must be draw n-up on; C AU TION; When assembling sections w ithout; SECTION II - CAST IRON BLOCK ASSEMBLY; Figure 5: Positioning of Back Section
13 C AU TION B oiler sections must be draw n-up on perfectly level surface or improper assembly may result. A. FIELD ASSEMBLED SECTIONS — If the boiler was ordered to be field assembled, follow the assembly procedure outlined on the following pages.1. ASSEMBLY OF SECTIONS (MANUAL DRAW- UP) These sect...
Page 14 - N ipples must be driven in evenly and to
14 WAR N IN G N ipples must be driven in evenly and to the proper depth to assure tight joints. Most nipple leaks are caused by tilted or cocked nipples.D O N OT use steel/iron head hammer to drive nipples w ithout using a w ood block. N ipple damage may result. g. A special nipple setting gauge is ...
Page 15 - To avoid damage to the draw -up rod; Figure 8: Series 24 Section Arrangement
15 i. From the “Section Arrangement” chart, select the next section according to the “Identification Code” at the top of the chart. See Figure 8. Use a wire brush to clean the groove in the face of the next section. Then, using a cartridge of RTV 6500 or RTV 736 sealant in a caulking gun, fill the gro...
Page 16 - D o not over torque draw up nuts after grind
16 When you start, grind surfaces between adjoining sections should be approximately 3/8” apart. Use three (3) or four (4) passes at tightening the four (4) draw-up rods a little at a time so that sections are pulled up evenly. During the last pass, pay close attention to the silastic sealant as it ...
Page 17 - READ THE STATEMENTS BELOW BEFORE
17 Figure 11: Center Section Channel Block Position (Partial Block Draw-Up) Figure 10: Front and Rear Section Channel Block Positions (Hydraulic Draw-up) C AU TION D o not apply pressure directly on threaded tappings on front and rear sections w ith draw -up channels during assembly procedures. R od...
Page 18 - D O N OT install gauge until after hydrostatic; Failure to properly hydrotest all boilers at
18 Figure 12: Hydraulic Draw-Up of Sections B . HYDROSTATIC TEST — After the boiler sections have been assembled, it is essential that the boiler be hydrostatically tested before the canopy, flue cover plates, jacket, or piping is installed.1. Tankless Heater Installation If boiler is ordered with ta...
Page 19 - SECTION III - INSTALLATION INSTRUCTIONS; INSTALL CANOPY/FLUE OUTLET ASSEMBLY
19 SECTION III - INSTALLATION INSTRUCTIONS A . INSTALL CANOPY/FLUE OUTLET ASSEMBLY , Refer to Figures 14, 15 and 16. 1. Open canopy carton.2. Attach the two (2) canopy brackets to the front end cap of canopy with four (4) #10 x 1/2” sheet metal screws each. 3. Across the top of the front section and...
Page 21 - Warning; AVOID Breathing Fiber Particulates and Dust; Precautionary Measures; Important P roduct S afety Information
21 Warning : This product contains refractory ceramic fibers (RCF). RCF has been classified as a possible human carcinogen. After this product is fired, RCF may, when exposed to extremely high temperature (>1800F), change into a known human carcinogen. When disturbed as a result of servicing or repa...
Page 23 - To install multiple side panels, start at the
23 C. MOUNT REAR OBSERVATION PORT COVER Refer to Figure 16. 1. With the silastic sealant, secure the 3/16” diameter rope gasket into the groove around the perimeter of the rear observation port cover. 2. Mount the rear observation port cover onto the rear section (with the word “Top” in the upright ...
Page 24 - Figure 22: Series 24 Jacket
24 Figure 22: Series 24 Jacket Assembly (Boiler Models 24-03 thru 24-12)
Page 25 - Failure to properly fill all gaps betw een the; For boilers without tankless heaters
25 8. Combination Label and Crown Logo Plate were attached to jacket front panel at time of manufacture. If loose or peeling, apply pressure to reset adhesive. 9. On steam boilers, attach lowest permissible water level plate (from steam trim carton) to the front panel using sheet metal screws. 10. T...
Page 26 - Figure 25a Purpose of Tappings - Steam Boilers
26 Figure 25a Purpose of Tappings - Steam Boilers Size Size (in) (in) B 4 Plug (24-03 thru 24-06) Supply (24-07 thru 24-12) K Steam Boiler A 4 Supply Tapping Location Steam Boiler Tapping Location C 3 Blow-Off Valve D 3 Return E 3 Plug J1 1 F 3 Plug G 1-1/2 Safety Valve/Surface Skim Tap Plug J2 1 Fl...
Page 27 - Figure 25b: Steam Trim
27 1 1/2" X 3" BR NIPPLE ALL 2 29 1" X 12" NIPPLE CSD-1 EQUIPPED BOILERS PUMPED RETURN 1 2 1/2" BR UNION ALL 2 30 4" BK PLUG ALL 1 3 1/2" BR CLOSE NIPPLE ALL 2 31 1-1/2" X 4 NIPPLE ALL 1 4 LWCO, #67 ALL 2 32 1-1/2" TEE ALL 1 5 GAUGE GLASS SET ALL 2 33 1-1/2" S...
Page 28 - STEAM BOILERS — INSTALL STEAM TRIM
28 WAR N IN G S afety valve discharge piping must be piped to w ithin six (6) inches of floor or to floor drain to eliminate potential of severe burns. D o not pipe in any area w here freez ing could occur. D o not install any shut-off valves, plugs or caps in discharge piping. H. STEAM BOILERS — IN...
Page 30 - Figure 26a: Purpose of Tappings - Water Boilers
30 Figure 26a: Purpose of Tappings - Water Boilers Tapping Location Size Water Boiler Tapping Location Size Water Boiler (in) (in) A 4 Supply J2 1 Plug B 4 Plug K 3/4 Probe L.W.C.O. C 3 Return M 3/4 Operating Temperature Limit Control D 3 Plug (24-03 thru 24-11) Return (24-12) N 3/4 Hi Temperature L...
Page 31 - Figure 26b: Water Trim
31 1 3" SQ. HD. PLUG 24-03 THRU 24-12 2 16 1-1/2" x 3/4" BLK BUSHING 24-03 THRU 24-07 1 1 3" SQ. HD. PLUG 24-12 WITH 20° DROP 1 16 1-1/2" x 1" BLK BUSHING 24-08 THRU 24-10 1 2 1" RECESSED HD PLUG ALL 4 16 1-1/2" x 1-1/4" BLK BUSHING 24-11 THRU 24-12 1 3 3" X 3...
Page 32 - Failure to properly pipe boiler may result in; All steam and hot water pipes must have; BURNER INSTALLATION
32 WAR N IN G Failure to properly pipe boiler may result in improper, unsafe system operation and void manufacturer's warranty. DO NOT improperly pipe boiler. WAR N IN G All steam and hot water pipes must have clearances of at least 1/2" from all combustible construction. I. WATER BOILERS - INST...
Page 33 - reduce boiler longevity.; A hot w ater boiler installed above radiation
33 WARNING R eturn w ater cannot be low er than 135°F for prolonged periods of time. Operation under these conditions w ill result in sustained condensing w ithin the combustion chamber and potentially reduce boiler longevity. In addition, the return w ater cannot be introduced into the boiler if it...
Page 34 - Typical Crown Boiler Loop w/3-way Diverting
34 of the RTC cannot be used on multiple boiler installations. d. Boiler Circulator – The boiler circulator selection will maintain a constant and minimum flow through the boiler during every heat demand. In addition, the circulator will maintain a flow around the return sensor. The circulator must be...
Page 35 - Recommendation 1 — Use when:; system flow does not impact flow through the boiler; Pipe Sizing and Notes
35 Recommendation 1 — Use when: • system return water is not less than 135° F for prolonged periods of time • system flow does not impact flow through the boiler Figure 31: Series 24 Minimum Piping Recommendation 1 - Water Boiler NOTES: 1. All piping is schedule 40. 2. Pipe sizes listed are based on a...
Page 36 - Figure 32: Series 24 Minimum Piping Recommendation 2 - Water Boiler; Recommendation 2 — Use when:; Figure 33: Series 24 Minimum Piping Recommendation 3 - Water Boiler
36 Figure 32: Series 24 Minimum Piping Recommendation 2 - Water Boiler Recommendation 2 — Use when: • system return water is not less than 135° F for prolonged periods of time • system flow does impact flow through the boiler(ie. zoning, mixing) NOTES: 1. All piping is schedule 40. 2. Pipe sizes liste...
Page 37 - Recommendation 3 — Use when:
37 Figure 32: Series 24 Minimum Piping Recommendation 2 - Water Boiler Figure 33: Series 24 Minimum Piping Recommendation 3 - Water Boiler Recommendation 3 — Use when: • system return water is less than 135° F for prolonged periods of time • system flow does impact flow through the boiler(ie. zoning, ...
Page 38 - professional to design for the proper application.; BOILER PIPING, DOMESTIC HOT WATER; D O N OT use the boiler circulator as an
38 NOTICE When possible, domestic hot w ater production should utiliz e a dedicated boiler(s). This w ill allow the other boiler(s) to be shut dow n and isolated during the summer months. If the boiler load is shared betw een heating and domestic hot w ater, then one needs to determine if a hot w at...
Page 40 - ypical Steam Piping
40 Figure 35: T ypical Steam Piping Arrangement for Boilers with Pumped Condensate Return and Boiler Feed Unit
Page 41 - CONNECT TANKLESS HEATER PIPING; The follow ing guidelines should be follow ed; D o not operate tankless heater w ith hard
41 M. CONNECT TANKLESS HEATER PIPING as shown in Figure 38. See Table IV for Tankless Heater Ratings. 1. Install Flow Regulator If flow through the heater is greater than its rating, the supply of adequate hot water may not be able to keep up with the demand. For this reason a FLOW REGULATOR matching...
Page 42 - Ratings are given in gallons per minute continuous
42 Figure 37: Minimum Piping Requirements for Series 24 Tankless Heater Manifolds Figure 38: Schematic Tankless Heater Piping s g n it a R r e t a e H s s e l k n a T V I e l b a T r e li o B l e d o M s r e t a e H s s e l k n a T 4 - T f o r e b m u N d e ll a t s n I 1 2 3 4 3 0 - 4 2 5 7 . 6 -- ...
Page 44 - Figure 40b: Water Boiler - Pressure Relief Valve
44 Figure 40b: Water Boiler - Pressure Relief Valve Hook-Up placement. The 14 gauge mounting bracket must be attached to the jacket first using four (4) #8 x ¾” drill point sheet metal screws. One may find it easier to install some of the conduit connectors with their corresponding conduit runs onto t...
Page 45 - ypical Boiler W
45 Figure 41: T ypical Boiler W iring with RTC (Front)
Page 46 - ypical Boiler with RTC Return Sensor (Rear)
46 Figure 42: T ypical Boiler with RTC Return Sensor (Rear)
Page 47 - SECTION IV - OPERATING INSTRUCTIONS; ALWAYS INSPECT INSTALLATION BEFORE; Failure to clean the system w ill result in
47 SECTION IV - OPERATING INSTRUCTIONS A . ALWAYS INSPECT INSTALLATION BEFORE STARTING BURNER. B . FILL HEATING SYSTEM WITH WATER. Boiler must be cleaned and fully free of oil and dirt. CLEAN HEATING SYSTEM IF boiler water or condensate return water is dirty or if erratic water lines or surging exis...
Page 48 - ADJUST BURNER; D o not attempt to start the burner w hen
48 of installation. 5. ON WATER BOILERS WITH TANKLESS HEATERS, set low limit operating control dial at 190°F and high limit dial 210°F. Operating control must be a minimum of 20° below high limit setting. Set differential at 25°. D. ADJUST BURNER according to the Burner Manual. 1. FLAME FAILURE The ...
Page 49 - Table V: Boil Min Delay Settings
49 ASHRAE Fundamentals for the area closest to the installation. This value has a default of 10°F, and is adjustable between –60ºF to 32ºF. e. WWSD – The Warm Weather Shut Down feature is used only when the outdoor reset feature is selected. (OUTDR DESIGN = ON) If the outdoor temperature rises above...
Page 50 - TEST CONTROLS; B efore installation of the boiler is
50 J. TEST CONTROLS WAR N IN G B efore installation of the boiler is considered complete, the operation of the boiler controls should be checked, particularly the low w ater cutoff and the high limit control. All controls must be checked prior to putting the boiler in service. 1. CHECK OPERATING CON...
Page 51 - P robe and float type low w ater cutoff
51 sufficiently to permit a steady trickle of water from the surface blowoff pipe. Continue this slow boiling and trickle of overflow for several hours until the water coming from the overflow is clear. d . Stop burner and drain boiler in a manner and to a location that hot water can be discharged with...
Page 53 - FREQUENT WATER ADDITION
53 T N A T R O P M I S I T I , N O I T A R E P O L A M R O N G N I R U D , F I R E P R E T A W E R O M D D A O T Y R A S S E C E N T L U S N O C , W O L E B D E T A C I D N I N A H T H T N O M O T N A I C I N H C E T E C I V R E S D E I F I L A U Q A . S K A E L R O F M E T S Y S R U O Y K C E H C :...
Page 54 - SECTION V - SERVICE INSTRUCTIONS; that the w ires are reconnected properly.; D AN GE R; N ever modify, remove or tamper w ith any control device.
54 2. CLEAN THE BOILER FLUEWAYS a. Remove the jacket left side panels.b. Loosen nuts securing the flue cleanout plates and remove the plates. The insulation should be removed with the plates taking care not to damage the insulation. c. Using a 1¼” diameter wire or fibre bristle brush (36” handle) clea...
Page 55 - D o not start the burner unless canopy,; E xercise caution w hen handling phosphoric
55 b. Using wire or fibre bristle brush clean crown of boiler and inside of water legs. c. Inspect target wall (903A only) for damage or deterioration. If target wall is damaged, replace. 5. REASSEMBLE BOILER CAUTION D o not start the burner unless canopy, smokepipe, burner mounting plate and all flu...
Page 56 - If boiler is not used during w inter time, it
56 2. FLOAT TYPE LOW WATER CUTOFF During the heating season, if an external low water cutoff is on the boiler, the blow off valve should be opened once a month (use greater frequency where conditions warrant) to flush out the sediment chamber so the device will be free to function properly. Low water...
Page 57 - Table VI: Beckett Burner Specifications; SECTION VI - BURNER SPECIFICATIONS; OIL BURNERS
57 Table VI: Beckett Burner Specifications SECTION VI - BURNER SPECIFICATIONS E C I T O N , s e r u s s e r p p m u p , s r e n r u b g n i w o ll o f e h t n o p u d e s a b e r a s e it i c a p a c d n a s g n it a r r e li o b 4 2 s e i r e S l a n o it i d d a r o f r e n r u b h ti w d e h s i n...
Page 58 - SECTION VII - REPAIR PARTS & CARTON CONTENTS; consult the area Crown representative or the factory at:
58 SECTION VII - REPAIR PARTS & CARTON CONTENTS The following parts may be obtained from any Crown distributor. To find the closest Crown distributor, consult the area Crown representative or the factory at: Crown Boiler Co. Customer Service P.O. Box 14818 Philadelphia, PA 19134 www.crownboiler.c...
Page 59 - SERIES 24 MASTER PARTS LIST
59 SERIES 24 MASTER PARTS LIST DESCRIPTION SECTIONS SECTION JOINER CARTON REAR FLUE OUTLET CARTON FLA ME O BS . C AR TO N WA TE R T RIM C AR TO N STE AM TR IM C AR TO N TA RG ET WA LL CA RTO N BURNER MTG PLATE CARTON BU RN ER A DAP TE R P LA TE CA RTO N BU NR ER C AR TO N CA NO PY C AR TO N JA CK ET...
Page 60 - Figure 43: Series 24 Jacket; AIR P
60 Figure 43: Series 24 Jacket Assembly (Boiler Models 24-03 thru 24-12) SECTION VII - REP AIR P ARTS (Continued)
Page 61 - JACKET CARTON
61 CROWN CARTON PART # 33 02 03 33 02 04 33 02 05 33 02 06 33 02 07 33 02 08 33 02 09 33 02 10 33 02 11 33 02 12 24 -0 3 24 -0 4 24 -0 5 24 -0 6 24 -0 7 24 -0 8 24 -0 9 24 -1 0 24 -1 1 24 -1 2 1 FRONT JACKET PANEL 330310 1 1 1 1 1 1 1 1 1 1 2 REAR JACKET PANEL 330320 1 1 1 1 1 1 1 1 1 1 UPPER TIE BA...
Page 63 - SECTION JOINER CARTON ASSY; CANOPY CARTON
63 "F" "G" "H" 7 7" PUSHNIPPLE 310005 2 3 4 8 3" PUSHNIPPLE 310006 4 6 8 9 5/8 X 9 3/4 TIE ROD 900310 8 12 16 5/8 HEAVY HEX NUT (GRADE 9) 900307 16 24 32 5/8 HI-STRENGTH FLAT WASHER 900308 16 24 32 LOCTITE # 592, 50 ml TUBE 900350 1 2 2 GASKET ROPE, 3/8 DIA x 96" ...
Page 66 - V Return Temperature Control (RTC) Packages
66 ACTUATOR (24V, 50 SECOND MOTOR) 332801 1 NIPPLE 3" X 12", (SPECIAL, SCH 40) 332802 1 MOUNTING BRACKET FOR RTC 332803 1 MIX SENSOR, TEKMAR #071, SURFACE MOUNT 332804 1 OUTDOOR AIR SENSOR, TEKMAR #070 332805 1 ACTUATOR (24V, 50 SECOND MOTOR) 332801 1 NIPPLE 3" X 12", (SPECIAL, SCH 4...
Page 70 - MINIMUM; This diagram is for reference only; SECTION VIII - APPENDIX
70 A1. 3-way RTC in Primary/Secondary – Heating Only/No DHW ; with/without Outdoor Reset (MECHANICAL) NOTES: 1) Install the boiler as indicated above for systems where return temperatures may be less than 135F and heating application only . 2) The Outdoor Sensor (S3) and the Mix Supply Sensor (S2) a...
Page 73 - A2. 3-way RTC in Primary/Secondary – Heating and DHW using T
73 NOTES: 1) Refer to the I&O to determine correct valve orientation and actuator wiring. 2) 120 V AC supplying the R TC should be separate from the burner/boiler circuit. 3) Heat demand can be any electrical signal consisting of 24 – 240 V AC. 4) The Outdoor Sensor (S3) and the Mix Supply Senso...
Page 75 - AC supplying the R
75 A3. 3-way RTC in Primary/Secondary – Heating and DHW using Indirect W ater Heater; with/without Outdoor Reset (ELECTRICAL) NOTES: 1) Refer to the I&O to determine correct valve orientation and actuator wiring. 2) 120 V AC supplying the R TC should be separate from the burner/boiler circuit. 3...
Page 76 - NOT
76 A4. 3-way RTC in Primary/Secondary – Heating and DHW using Indirect W ater Heater on Primary Loop; without Outdoor Reset (MECHANICAL) NOTES: 1) Install the boiler as indicated above for systems where return temperatures may be less than 135F and heating/DHW with an indirect water heater . 2) This...
Page 78 - ater Heater on Primary Loop
78 A5. 3-way Multiple Boiler RTC in Primary/Secondary – Heating and DHW using Indirect W ater Heater on Primary Loop; Using Sequencer with & without Outdoor Reset (MECHANICAL) NOTES: 1) Install the boiler as indicated above for systems where return temperatures may be less than 135F and heating/...
Page 80 - ankless
80 A6. T ankless Application Only with RTC – NO Building Heat; with and without storage tank (MECHANICAL) NOTES: 1) Install the boiler as indicated above for systems where the boiler return temperatures may be less than 135F and heating DHW with a tankless coil. 2) The boiler circulator must be size...
Page 82 - Application Only with RTC – NO Building Heat (MECHANICAL); The return sensor
82 A7. Indirect Application Only with RTC – NO Building Heat (MECHANICAL) NOTES: 1) Install the boiler as indicated above for systems where the boiler return temperatures may be less than 135F and heating DHW with an indirect water heater or heat exchanger . 2) The boiler circulator must be sized us...
Page 83 - Application Only with RTC – NO Building Heat (ELECTRICAL)
83 A7. Indirect Application Only with RTC – NO Building Heat (ELECTRICAL) NOTES: 1) Refer to the I&O to determine correct valve orientation and actuator wiring. 2) 120 V AC supplying the R TC may or may not be separate from the burner/boiler circuit. 3) Heat demand can be any electrical signal c...
Page 86 - Bell and Gossett
86 APPENDIX B3 - Series 24 Boiler Circulator and Diverting Valve Selection Chart, 20°F & 40°F ∆ T, Bell and Gossett F ° 0 2 ( tt e s s o G d n a ll e B - n o it c e l e S r o t a l u c ri C r e li o B 4 2 s e ir e S )l a it n e r e ff i D E Z I S R B I S S O R G T U P T U O ) H B M ( L A T O T M...
Page 87 - Armstrong
87 APPENDIX B4 - Series 24 Boiler Circulator and Diverting Valve Selection Chart, 20°F & 40°F ∆ T, Armstrong )l a it n e r e ff i D F ° 0 2 ( g n o rt s m r A - n o it c e l e S r o t a l u c ri C r e li o B 4 2 s e ir e S E Z I S R B I S S O R G T U P T U O ) H B M ( L A T O T M P G e p i P e z...
Page 88 - APPENDIX C – VALVE AND ACTUATOR MOUNTING INSTRUCTIONS
88 APPENDIX C – VALVE AND ACTUATOR MOUNTING INSTRUCTIONS Application For use with ESBE ½” to 6” 3-Way and 4-Way rotary valves for mixing and diverting applications. Use with 24Vac 3-point “floating” signal controller. Mounting the Motor 1. Place drive sleeve onto shaft and secure with bolt . Chec...
Page 89 - SERVICE RECORD; DATE
Page 90 - Manufacturer of Hydronic Heating Products
90 Manufacturer of Hydronic Heating Products P.O. Box 14818 3633 I. Street Philadelphia, PA 19134 Tel: (215) 535-8900 • Fax: (215) 535-9736 • www.crownboiler.com D E S I G N E D T O L E A D PN: 980417 S24 - 12/05