Crestron GLS-LOL - Manual

Crestron GLS-LOL

Crestron GLS-LOL – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
Page: / 2
Loading the manual

Crestron

GLS-LOL

(Wattstopper P/N LS-290C)

PHOTOCELL LIGHT SENSOR

Operations & Installation Guide

FCC Compliance Statement:

Further Inquiries

If you cannot locate specific information or have questions after reviewing this guide, please take

advantage of Crestron's award winning customer service team by calling Crestron at

1-888-CRESTRON [1-888-273-7876].

You can also log onto the online help section of the Crestron website (www.crestron.com/onlinehelp) to

ask questions about Crestron products. First-time users will need to establish a user account to fully

benefit from all available features.

Future Updates

As Crestron improves functions, adds new features and extends the capabilities of the GLS-LOL units,

additional information may be made available as manual updates. These updates are solely electronic

and serve as intermediary supplements prior to the release of a complete technical documentation

revision.

Check the Crestron website periodically for manual update availability and its relevance. Updates are

identified as an “Addendum” in the Download column.

This device complies with part 15 and part 18 of the FCC rules. Operation is subject to the following

two conditions: (1) This device must not cause harmful interference, and (2) This device must accept

any interference received, including interference that may cause undesired operation.

The GLS-LOL is a low voltage photocell which senses light levels and signals this data

to an interface device such as the GLS-SIM connected to the Crestron

®

control system.

GLS-LOL Specifications

Photocell Placement

The photocell is designed for mounting in a dry location that views daylight. The photocell

should not directly view illumination from an electric light source. The following figure

shows the GLS-LOL field of view.

Where windows are the primary source of daylight, the photocell typically mounts on the

ceiling between the window and the first row of fixtures. (Refer to the following figure.) The

photocell points toward the window.

For skylight applications, the photocell mounts in the lightwell of the skylight and should

view the incoming daylight. Typically, the photocell is aimed toward the skylight. The light

level range adjustment jumper may need to be changed to 60-6000fc for skylight

applications.

Light Level Testing

Before installing the photocell, verify the daylight levels on a sunny day at the proposed

location of the photocell. With the lights switched off, use a light meter to read the daylight

level. Orient the light meter in the same direction that the photocell will view. The light

levels under sunny conditions must be at least 35fc. If the light levels are less, you should

select another location or reorient the photocell.

INSTALLATION

Wiring and Testing

Use CRESNET-P/-NP cables only. Maximum distance is 250 feet.

1. To access the GLS-LOL wiring terminals, insert a small, flatblade

screwdriver into a slot on the housing and remove the base from the lens

assembly.

2. Review the “MOUNTING” section on the next page to determine how the

cable to the controller will enter the photocell housing. Modify either the

lens housing or the base as instructed in step 2A or 2B.

DESCRIPTION

To be installed and/or used in accordance with appropriate electrical codes and

regulations.

If you are unsure about any part of these instructions, consult a qualified electrician.

Sensors must be mounted on a vibration free surface.

All sensors must be mounted at least 6 feet away from air vents.

WARNINGS, CAUTIONS & NOTES

When wiring the Cresnet

®

network, consider the following:

Use Crestron Certified Wire.

• Use Crestron power supplies for Crestron equipment.

Provide sufficient power to the system.

NETWORK WIRING

CAUTION:

Insufficient power can lead to unpredictable results or damage to the

equipment. Please use the Crestron Power Calculator to help calculate how much power

is needed for the system. (www.crestron.com/calculators).

WARNING:

To avoid fire, shock, or death; turn off power at circuit breaker or fuse and

test that power is off before wiring!

NOTES:

Observe the following points regarding sensor installation.

PREPARING AND CONNECTING WIRES

Strip the ends of the wires approximately 1/2”. Use care to avoid nicking the conductors.

Twist together the ends of the wires that share a connection and tin the twisted

connection. Apply solder only to the ends of the twisted wires. Avoid tinning too far up

the wires or the end becomes brittle.

Field of View & Mounting

Placement

Peak

Sensitivity

GLS-LOL

Light Fixture

Window

45°

Crestron Electronics, Inc.

Operations & Installation Guide-DOC. 6774A

15 Volvo Drive Rockleigh, NJ 07647

(2023057)

Tel: 888.CRESTRON

12.08

Fax: 201.767.7576

Specifications subject to

www.crestron.com

change without notice.

SPECIFICATION

DETAILS

Power Consumption

0.2W (8mA @ 24VDC)

Field of View Coverage

60° Cone

Output

Signal Range:

Light Level Range:

0 - 10VDC

Selectable, 3 to 300 footcandles (fc),

30 to 3000fc, 60 to 6000fc

Recommended Mounting Location

Directly above work space

Cable to GLS-SIM or other

compatible Crestron interface

device.

GLS-LOL

Peak

sensitivity

1.2 in.

(3.05 cm)

45º

30º

30º

Ceiling tile or drywall

60º field of view

2.0 in.

(5.08 cm)

UL and cUL Listed

Class 2

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Crestron Models

All Crestron Other