INSTALLATION INSTRUCTIONS, BIN STAT KIT, P/N 631500074,
631500099, 631500108, 631500109, AND 631500116
These Bin Stat kits apply to all “X” Series Ice makers
Table 1. Loose–Shipped Parts
Item No.
Part No.
Name
Qty.
1
630000837
Thermostat Asy
1
2
07578
Screw TC 08–32
2
3
630460162
Installation Instruction, Thermostat
1
4
630900895
Hex Nut 8–32 SS Keps
1
5
620045454 or
620045455 or
620045456 or
620045457 or
620050327
Bin Stat Support
1
1. Disconnect power.
2. Remove front cover of the unit and the electrical box cover plate. For 22” wide units you will need to
remove the Grill from the right side of the unit.
3. To mount bin thermostat in electrical box:
A.
Route wires and connector through grommet in electrical box (see Figure 1).
B.
Attach bin thermostat to electrical box with two 08–32 TC screws provided (see Figure 1).
4. Connect the bin thermostat lead to the circuit board (see Figure 2).
5. Straighten approximately 12” of capillary tube to go through hole in chassis base. Re–coil the re-
mainder. Do not disturb the tightly coiled end.
6. Insert the “1/4” diameter wire Bin Stat support into the coiled end of capillary tube. Carefully wrap 5
turns of free capillary tube tightly around the Bin Stat support. Insert the assembly through the hole
in the chassis base. Route capillary tube to follow the Bin Stat support as closely as possible (see
Figure 3).
7. Slip eye of Bin Stat support over the 8–32 weld stud in the chassis base. If a nut exists on this weld
stud remove before assembling the Bin Stat support. Secure the Bin Stat support with the 8–32
Keps nut provided in the kit (see Figure 3).
8. Any excess capillary tubing must be carefully pulled back into the compressor compartment to pre-
vent ice from damaging it during dispenser operation.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
IMI CORNELIUS INC. 2001–2003 October 9, 2003 630460162 2 Rev C 9. Seal ½ ” diameter hole with sealant (RTV). 10. Turn bin stat adjustment screw clockwise until it stops. Then turn it counterclockwise 1/8 of a turn. 11. Reinstall the front cover of the electrical box and the ice machine and reconnect...
IMI CORNELIUS INC. 2001–2003 October 9, 2003 630460162 3 Rev C Figure 2 Unit Stack Switches Bin 1 In Com Out 2 Switch LH Evap. SelectionSwitch Switch RH Evap. NS S N 4 3 5 On S3–2 S3–1 Off On Transformer YL Triac YL YL YL (Manufacturing Date) Processor 36430001 Micro pot. #5 #1 #2 #3 #4 #6 #7 (White...
CAPILLARY TUBE BIN STAT SUPPORT SEE DETAIL A DETAIL A SCALE 1:2 INSERT COIL AROUND BIN STAT SUPPORT 8–32 HEX BIN STAT Figure 3 SUPPORT NUT