COPPER EVAPORATOR COIL KIT (P/N 185216000)

ON

UNIVERSAL 750 PRE-MIX DISPENSER

IMPORTANT: Only qualified Personnel should install this Kit.

INTRODUCTION

The purpose of this kit is to replace the original expanded aluminum evaporator, which also doubles as the wa-
ter bath tank, with a new copper tube style evaporator. The old aluminum evaporator remains in place as the
water bath tank only.

A new anode and refrigeration system dual inlet strainer/dryer are also included with the kit and must be instal-
led.

Retain these instructions as part of your equipment manual.

UNPACKING THE KIT

Unpack and inspect the kit. Make sure Loose-Shipped Parts are present and in good condition (see Figure 1).

Table 1. Loose-Shipped Parts

Item

No.

Part No.

Name

Qty.

1

319238088

Suction Line Ass’y

1

2

186843000

Anode

1

3

187969000

Sheet Metal Screw, Phil Pan Hd, Type ‘‘A’’ Alum; No. 10 by 1/2-in.

1

4

185215000

Copper Evaporator Coil

1

5

319225000

Coil Spacer

4

6

320389000

Thread Rolling Screw, Phil Pan Hd, No. 6-32 by 1/4-in.

4

7

960050

Rubatex Insulation, 6-ft. long

1

8

2601

Strainer Dryer, Dual Inlet

1

9

189159001

Instructions

1

REQUIRED SUPPLIES AND EQUIPMENT

Supplies required are as follows:

Brazing alloy ‘‘Phos-Copper’’, ‘‘Silfos’’ or equivalent is required for copper-to-copper connections. These alloys
contain about 15% silver.

Brazing alloy. ‘‘Easy-flow’’ or equivalent is required for copper-to-steel connections. This alloy contains about
50% silver.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - REQUIRED EQUIPMENT; Item; DISASSEMBLY

2 189159001 Flux for use with copper-to-steel connections. Principal equipment needed for installing this kit is listed in the following table. Equivalent items maybe substituted. REQUIRED EQUIPMENT Item No. Name and Description Use 1 Torch, Oxy-fuel (acetylene, propane, etc.) Brazing 2 Torch Tips s...

Page 5 - DO NOT VENT REFRIGERANT TO ATMOSPHERE; KIT INSTALLATION

5 189159001 WARNING: To avoid eye injury, wear protective glasses or goggles while working withrefrigerant or brazing. DO NOT VENT REFRIGERANT TO ATMOSPHERE NOTE: Work in a well-ventilated area. Refrigerant is not toxic, but will displace air. Fumes from brazingcontain toxic gases. 1. Remove refrige...

Page 6 - LEAK CHECK; CHARGING

6 189159001 11. Purge system at least 10-minutes with dry nitrogen prior to brazing. 12. Adjust nitrogen flow until a very small amount (less than 1-psi) of nitrogen is flowing through refrigeration system. 13. While nitrogen is slowly flowing through refrigeration system, solder in lower part of su...