Carrier TJF005-007 - Manual

Carrier TJF005-007

Carrier TJF005-007 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
17 Page 17
18 Page 18
19 Page 19
20 Page 20
21 Page 21
22 Page 22
23 Page 23
24 Page 24
25 Page 25
26 Page 26
27 Page 27
28 Page 28
29 Page 29
30 Page 30
31 Page 31
32 Page 32
33 Page 33
34 Page 34
35 Page 35
36 Page 36
37 Page 37
38 Page 38
39 Page 39
40 Page 40
41 Page 41
42 Page 42
43 Page 43
44 Page 44
45 Page 45
46 Page 46
47 Page 47
48 Page 48
49 Page 49
50 Page 50
51 Page 51
52 Page 52
Page: / 52

Table of Contents:

  • Page 2 – Fig. 1 — Horizontal Conversion Panels
  • Page 3 – Fig. 2 — Roof Curb Dimensions
  • Page 4 – MAXIMUM ALLOWABLE; Fig. 3 — Unit Leveling Tolerances
  • Page 5 – Step 7 — Make Electrical Connections; Unit weights do not include economizer. See Table 1 for econo-; Fig. 5 — Rigging Details
  • Page 6 – Table 1 — Physical Data; Scroll
  • Page 8 – Fig. 6 — Base Unit Dimensions
  • Page 9 – Fig. 8 — Gas Piping Guide (With Accessory; SPACING OF SUPPORTS; Fig. 7 — Flue Hood Details; LEGEND; Fig. 10 — Component Location; Integrated Gas Unit Controller
  • Page 10 – Fig. 11 — Power Wiring Connections; COMP —
  • Page 11 – Table 2 — Electrical Data
  • Page 14 – Fig. 21 — Durablade Economizer Installed in Unit
  • Page 15 – OAT; Outdoor-Air Thermostat
  • Page 16 – Fig. 31 — Rear EconoMi$er Flange Installation
  • Page 18 – OR; Fig. 35 — Wiring Diagram for Power Exhaust System
  • Page 19 – Fig. 39 — Barometric Relief Capacity
  • Page 20 – Step 9 — Adjust Evaporator-Fan Speed —; Set movable flange at nearest keyway of pulley hub and; Fig. 41 — Belt Drive Motor Mounting
  • Page 37 – Table 30 — Altitude Compensation*; *As the height above sea level increases, there is less oxygen per; Fig. 43 — Service Panel Location
  • Page 38 – Heating; Fig. 44 — Burner Section Details
  • Page 40 – Fig. 45 — Coil Cleaning
  • Page 41 – Fig. 47 — Separating Coil Sections
  • Page 43 – Table 31 — LED Error Code Description*; Main Burners —; Fig. 53 — Burner Section Details
  • Page 44 – LOW HEAT
  • Page 45 – TROUBLESHOOTING; Table 32 — LED Error Code Service Analysis; Table 33 — Heating Service Analysis; IGC; LED —
  • Page 46 – Table 34 — Cooling Service Analysis
  • Page 47 – Table 35 — Durablade Economizer Troubleshooting
  • Page 48 – Table 36 — EconoMi$er Troubleshooting; PL —; Plug
  • Page 49 – Fig. 56 — Typical Wiring Diagram and Component Arrangement
  • Page 52 – ELECTRICAL
Loading the manual

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

PC 111

Catalog No. 534-774

Printed in U.S.A.

Form 48TJ-18SI

Pg 1

10-00

Replaces: 48TJ-16SI

Book 1

4

Tab

1a 6a

Installation, Star t-Up and

Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-36

Step 1 — Provide Unit Support

. . . . . . . . . . . . . . . . . . . 1

• ROOF CURB
• SLAB MOUNT

Step 2 — Field Fabricate Ductwork

. . . . . . . . . . . . . . . 2

Step 3 — Install External Trap for

Condensate Drain

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Step 4 — Rig and Place Unit

. . . . . . . . . . . . . . . . . . . . . 2

• POSITIONING

Step 5 — Install Flue Hood

. . . . . . . . . . . . . . . . . . . . . . . 4

Step 6 — Install Gas Piping

. . . . . . . . . . . . . . . . . . . . . . 4

Step 7 — Make Electrical Connections

. . . . . . . . . . . 5

• DISCONNECT BOX LOCATION
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
• HEAT ANTICIPATOR SETTINGS

Step 8 — Make Outdoor-Air Adjustment and

Install Outdoor-Air Hood

. . . . . . . . . . . . . . . . . . . . . . 12

• MANUAL OUTDOOR-AIR DAMPER
• OPTIONAL DURABLADE ECONOMIZER
• OPTIONAL ECONOMI$ER

Step 9 — Adjust Evaporator-Fan Speed

. . . . . . . . . 20

• DIRECT-DRIVE MOTORS
• BELT-DRIVE MOTORS

START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-39

SERVICE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-44

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . . . 45-50

START-UP CHECKLIST

. . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can

be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func-

tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that apply.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.

INSTALLATION

Unit is shipped in the vertical discharge configuration. To

convert to horizontal configuration, remove screws from side
duct opening covers and remove covers. Using the same
screws, install covers on vertical duct openings with the insula-
tion side down. Seals around duct openings must be tight. See
Fig. 1.

Step 1 — Provide Unit Support

ROOF CURB — Assemble and install accessory roof curb in
accordance with instructions shipped with curb. See Fig. 2. In-
stall insulation, cant strips, roofing felt, and counter flashing as
shown. Ductwork must be attached to curb, not to the unit. The
accessory thru-the-bottom power and gas connection package
must be installed before the unit is set on the roof curb.
If field-
installed (thru-the-roof curb) gas connections are desired, use
factory-supplied

3

/

4

in. pipe coupling and gas plate assembly to

mount the thru-the-roof curb connection to the roof curb. Gas
connections and power connections to the unit must be field in-
stalled after the unit is installed on the roof curb.

If electric and control wiring is to be routed through the

basepan, attach the accessory thru-the-bottom service connec-
tions to the basepan in accordance with the accessory installa-
tion instructions.

Ensure voltage listed on unit data plate agrees with electri-
cal supply provided for the unit.

Disconnect gas piping from unit when leak
testing at pressure greater than

1

/

2

psig. Pres-

sures greater than

1

/

2

psig will cause gas valve

damage resulting in hazardous condition. If
gas valve is subjected to pressure greater than

1

/

2

psig, it must be replaced before use. When

pressure testing field-supplied gas piping at
pressures of

1

/

2

psig or less, a unit connected to

such piping must be isolated by manually clos-
ing the gas valve.

Before performing service or maintenance operations on
unit, turn off main power switch to unit and install lockout
tag. Electrical shock could cause personal injury.

IMPORTANT: The gasketing of the unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 2. Improperly
applied gasket can also result in air or water leaks and
poor unit performance.

48TJE,TJF004

48TJD,TJE,TJF005-007

Single-Package Rooftop Heating/Cooling Units

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Fig. 1 — Horizontal Conversion Panels

2 Curb should be level. Unit leveling tolerances are shown in Fig. 3. This is necessary for unit drain to function properly. Re-fer to Accessory Roof Curb Installation Instructions for addi-tional information as required.SLAB MOUNT (Horizontal Units Only) — Provide a levelconcrete slab that extends ...

Page 3 - Fig. 2 — Roof Curb Dimensions

3 TO ENSURE AIRTIGHT CONNECTIONPLACE UNIT AS CLOSE TOEND AS POSSIBLE. TO ENSURE AIRTIGHT CONNECTIONPLACE UNIT AS CLOSE TOEND AS POSSIBLE. Fig. 2 — Roof Curb Dimensions ROOF CURB ACCESSORY ‘‘A’’ UNIT SIZE 48TJ CRRFCURB001A00 1 ′ -2 ″ [356] 004-007 CRRFCURB002A00 2 ′ -0 ″ [610] NOTES: 1. Roof curb acc...

Page 4 - MAXIMUM ALLOWABLE; Fig. 3 — Unit Leveling Tolerances

4 POSITIONING — Maintain clearance around and above unitto provide minimum distance from combustible materials,proper airflow, and service access. See Fig. 6. A properly posi-tioned unit will have the following clearances between unit androof curb: 1 / 4 -in. clearance between roof curb and base rai...