Carrier NP034-074- User Manual
Carrier NP034-074– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 3 – If roof curb is not used, support unit with steel beams along; Positioning —; Provide clearance around and above unit; UNIT; Fig. 1 — Rigging Label
- Page 6 – Table 2 — Operating Weights of Options and Accessories; Field-Fabricated Ductwork —; Units are designed for; UNIT CENTER OF GRAVITY AND CORNER WEIGHTS; Fig. 2 — Weight Distribution and Center of Gravity
- Page 15 – ROOF MOUNT DRAIN; Fig. 8 — Condensate Drain Piping Details
- Page 16 – Fig. 13 — Psychrometric Chart for
- Page 17 – Field Wire Routing; If field power wiring is brought through the roof curb, route; Field Electrical Connections; Fig. 14 — Wiring Connections for Solid-State
- Page 18 – — Ground; Fig. 18 — Field Power Wiring Connections
- Page 19 – Table 3 — Electrical Data, 034 Units
- Page 22 – Table 4 — Electrical Data, 044 Units
- Page 25 – Table 5 — Electrical Data, 054 Units
- Page 28 – Table 6 — Electrical Data, 064 Units
- Page 31 – Table 7 — Electrical Data, 074 Units
- Page 34 – NOTES AND LEGEND FOR FIG. 20; Fig. 19 — Field Control Thermostat Wiring
- Page 35 – Fig. 20 — Field Wiring for Building Pressurization and Smoke Purge
- Page 36 – Fig. 21 — Gas Piping Details
- Page 38 – Table 8 — Oil Charge; UNIT SIZE
- Page 43 – All gas system components are in the gas section.; Fig. 35 — Modulating Power Exhaust Damper
- Page 44 – The electric heater control box contains:; Fig. 37 — Gas Section Detail, 48 Series 034 and; Fig. 40 — Flue Box Assembly, 48 Series Units Only
- Page 45 – Fig. 42 — Typical Electric Heat Control Box
- Page 46 – Adjustments; Fig. 44 — Motor Plate Adjustment
- Page 47 – Fig. 45 — Pulley Alignment
- Page 50 – Fig. 60 — Auxiliary Switch Stroke Adjustment
- Page 51 – Fig. 61 — Auxiliary Switch Adjustment
- Page 52 – Table 11 — Pressure Switch Settings (psig); Control Circuit, 115 V —; Table 12 — Economizer Motor Checkout
- Page 53 – Unit Control Board Checkout —; Table 16 — Economizer Control Board Checkout,
- Page 54 – — Plug; Fig. 64 — Control Board Component Arrangement
- Page 56 – Fig. 65 — Compressor Lockout Connections
- Page 70 – PACKAGED SERVICE TRAINING; equipment discussed in this manual. Product programs cover:
Installation, Start-Up and
Service Instructions
CONTENTS
Page
GENERAL
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
SAFETY CONSIDERATIONS
. . . . . . . . . . . . . . . . . . . 2
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-37
Rigging and Unit Placement
. . . . . . . . . . . . . . . . . . 2
Roof Curb
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Roof Mount
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Slab Mount
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Positioning
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Field-Fabricated Ductwork
. . . . . . . . . . . . . . . . . . . . 6
Condensate Drains
. . . . . . . . . . . . . . . . . . . . . . . . . . 10
Install Outdoor Hoods
. . . . . . . . . . . . . . . . . . . . . . . 10
• UNIT SIZES 034 AND 044
• UNIT SIZES 054-074
Outdoor-Air Inlet Adjustments
. . . . . . . . . . . . . . . 10
• MANUAL OUTDOOR-AIR DAMPER
• ECONOMIZER SETTINGS
Field Wire Routing
. . . . . . . . . . . . . . . . . . . . . . . . . . 17
• UNIT SIZES 034 AND 044
• UNIT SIZES 054-074
Field Electrical Connections
. . . . . . . . . . . . . . . . . 17
• POWER WIRING
• CONTROL WIRING
Gas Piping (48 Series Units Only)
. . . . . . . . . . . . 36
Installing Flue/Inlet Hoods (48 Series Units
Only)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
• UNIT SIZES 034 AND 044
• UNIT SIZES 054-074
PRE-START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-41
Unit Preparation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Compressor Mounting
. . . . . . . . . . . . . . . . . . . . . . . 38
Evaporator-Fan Shipping Brackets
. . . . . . . . . . . 38
• UNIT SIZES 034 AND 044
• UNIT SIZES 054-074
Internal Wiring
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Refrigerant Service Valves
. . . . . . . . . . . . . . . . . . . 38
Crankcase Heaters
. . . . . . . . . . . . . . . . . . . . . . . . . . 38
Compressor Oil
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Gas Manifold Pressure (48 Series
Units Only)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Unit Voltage
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Leak Test and Dehydration
. . . . . . . . . . . . . . . . . . 39
Evaporator-Fan Belts, Pulleys, and Sheaves
. . 39
Condenser Fans and Motors
. . . . . . . . . . . . . . . . . 40
Return-Air Filters
. . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Economizer Inlet Screens
. . . . . . . . . . . . . . . . . . . 40
Economizer Dampers
. . . . . . . . . . . . . . . . . . . . . . . 40
25% Outdoor-Air Damper
. . . . . . . . . . . . . . . . . . . . 40
Initial Check
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41,42
General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Operating Sequences
. . . . . . . . . . . . . . . . . . . . . . . 41
• COOLING, UNITS WITHOUT ECONOMIZER
• HEATING, UNITS WITHOUT ECONOMIZER
Page
• COOLING, UNITS WITH ECONOMIZER
• HEATING, UNITS WITH ECONOMIZER
• VENTILATION AIR CIRCULATION (Continuous Fan)
• AUTOMATIC CHANGEOVER USING AUTOMATIC
CHANGEOVER THERMOSTAT
Head Pressure Control
. . . . . . . . . . . . . . . . . . . . . . 42
SERVICE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42-53
Service Access
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
• COMPRESSORS
• LIQUID SERVICE VALVES, FILTER DRIERS, AND
SIGHT GLASSES
• EVAPORATOR-FAN MOTORS, PULLEYS, AND
BELTS
• POWER EXHAUST MOTORS, PULLEYS, AND
BELTS
• UNIT CONTROL BOX
• GAS HEAT SECTION (48 Series Units Only)
• MAIN AND PILOT BURNERS (48 Series Units Only)
• FLUE GAS PASSAGEWAYS (48 Series Units Only)
• COMBUSTION AIR BLOWER (48 Series Units Only)
• ECONOMIZER DAMPER MOTOR
• ELECTRIC HEATER CONTROL BOX (50 Series
Units Only)
• HEATER BOX (50 Series Units Only)
• 25% OUTDOOR-AIR DAMPER
• MODULATING POWER EXHAUST DAMPER
MOTOR
• RETURN-AIR FILTERS
• CONDENSER FANS AND FAN MOTORS
• INLET GUIDE VANE MOTOR
Cleaning
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Lubrication
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
• COMPRESSORS
• FAN SHAFT BEARINGS
• INLET GUIDE VANE BEARINGS (Units With
Optional Inlet Guide Vanes)
• FAN MOTOR BEARINGS
• DOOR HINGES
Adjustments
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
• EVAPORATOR FAN AND POWER EXHAUST
MOTOR PLATE
• MODULATING POWER EXHAUST DIFFERENTIAL
PRESSURE SWITCH
• INLET GUIDE VANE DIFFERENTIAL PRESSURE
SWITCH (Units With Optional Inlet Guide Vanes and
Static Pressure Control)
• BELT INSTALLATION AND TENSIONING
• PULLEY ALIGNMENT
• INSTALLING ALTERNATE MOTOR PULLEY
(Evaporator Fan Only)
• CONDENSER FAN ADJUSTMENT
• 25% OUTDOOR-AIR DAMPER
• REFRIGERANT CHARGE
• PILOT LIGHT OFF (48 Series Units Only)
48DJ,DK,NP034-074
50DJ,DK,DW,DY,NB,NP034-074
Single Package Heating and Cooling Units
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
1
Tab
1a 1b
PC 111
Catalog No. 564-818
Printed in U.S.A.
Form 48/50D,N-9SI
Pg 1
3-96
Replaces: 48DJ,DK-3SI;
48/50NB,NP-1SI; 50DJ,DK-9SI
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Carrier NP034-074
Summary
If roof curb is not used, support unit with steel beams along its entire length and then support steel as required. As a mini-mum, unit must be supported across its width at each liftinglug location. Positioning — Provide clearance around and above unit for airflow, safety, and service access. Do no...
Table 2 — Operating Weights of Options and Accessories OPTION OR ACCESSORY UNIT SIZE 034 044 054 064 074 Roof Curb 48DJ,DK,NP 50DW,DY,NB 50DJ,DK,NP 450450380 480480465 515560515 515560515 515560515 Condenser Section Roof Curb — — 540 540 625 Economizer 300* 300* 530* 530* 530* Power Exhaust 600* 600...
034 UNITS 044-074 UNITS Fig. 5 — Drain Location Selection Fig. 6 — Condensate Drain Location Fig. 7 — Seal Plate Location ROOF MOUNT DRAIN SLAB MOUNT DRAIN Fig. 8 — Condensate Drain Piping Details Fig. 9 — Outdoor-Air Hood 15