Carrier DIRECT VENT 4 58HDV- User Manual
Carrier DIRECT VENT 4 58HDV– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Required Notice for Massachusetts Installations; IMPORTANT; 4 as adopted by the Board and
- Page 3 – SAFETY CONSIDERATIONS; CAUTION; SAFE INSTALLATION REQUIREMENTS; WARNING
- Page 4 – Installation”; Safety Rules; Frozen Water Pipe Hazard; Winter Shutdown
- Page 5 – INSTALLATION; CARBON MONOXIDE POISONING HAZARD; Venting and Combustion Air; Installation Positions; never; Location and Clearances; FROZEN AND BURST PIPE HAZARD; Installation Requirements; NOT; Vent and Combustion Air Piping
- Page 6 – Combustion & Ventilation Air; Furnace Installation Considerations; Condensate Trap and Drain Lines; Condensate Drain Trap”; Leveling; NOTE; Vent and Combustion Air Piping”; Horizontal Furnace Installation; Do not
- Page 8 – Knock Outs; COMBUSTION & VENTILATION; For Single Pipe Installation; “Venting and Combustion Air Check”; Outdoor Combustion Air Method
- Page 9 – This installation NOT approved in Canada
- Page 10 – cm; Standard; and
- Page 11 – Outdoor; Ventilation Air
- Page 12 – VENT AND COMBUSTION AIR; Dual Certified; INLET; Confined Space Installation; MUST; Contaminated Combustion Air
- Page 13 – Combustion Air and Vent Piping Insulation; or
- Page 14 – For venting table, see; in; Vent Termination Clearances; “Concentric Termination Kit”
- Page 17 – Condensate Drain Trap; Condensate Drain Trap Freeze Protection
- Page 18 – Upflow Installations Top Vent; Trap
- Page 19 – Upflow Installations Vent through Left -- Side; Both
- Page 21 – EXHAUS
- Page 23 – Horizontal Left through Top
- Page 25 – Horizontal Right through Top
- Page 27 – Drain Line; Connecting Vent and Combustion Air Piping; Combustion Air Pipe Connection (
- Page 28 – elbow is approved; Joining Pipe and Fittings; Connecting Vent Pipes and Termination; Maintain a minimum of 36; Horizontal Termination
- Page 29 – Above Snow Level or Grade Level; for Sustained Cold Weather
- Page 30 – OR; Roof Termination; with Exterior Risers
- Page 31 – Canadian Fuel Gas Code; Concentric Vent Termination; Vertical & Horizontal Termination
- Page 32 – Table 5
- Page 33 – GAS SUPPLY AND PIPING; Gas Supply Requirements; Table 6; Gas Piping Requirements
- Page 34 – Failure to properly install metal gas connector could; Use elbows and 3
- Page 35 – Additional Propane Connection Requirements; Propane Conversion; General Derating Rules; maintained; High Altitude Input Rate =; High Altitude Air Pressure Switch
- Page 36 – Table 7; Table 8; Orifice; Changing Orifices for High Altitude
- Page 37 – Final Gas Piping Check; ELECTRICAL WIRING; Turn OFF electrical power at fuse box or service panel; Power Supply Wiring
- Page 38 – Humidifier/Electronic Air Cleaner; Furnace Control Board; Furnace Control Fuse; Tap Select Interface Board
- Page 39 – DUCTWORK AND FILTER; Installation; Connections
- Page 40 – Filters; Circulation Air; Filter Installation using Filter Rack; Addition Of Air Conditioning
- Page 41 – Combustible Floor Installation; install unit on noncombustible subbase could; Subbase for Combustible Floor; Table 9
- Page 42 – CHECKS AND ADJUSTMENTS; Verify the input rate of the furnace.; Startup; User’s Information; Gas Supply Pressure
- Page 43 – Natural Gas Input Rating Check; Stable and blue flames. Dust may cause orange tips; MUST NOT; Flames extending directly from burner into heat ex-; touch sides of heat exchanger; Burner Face; Temperature Rise Check
- Page 44 – Blower Adjustments; Changing Blower Speed; Technical Support Manual”; Continuous- Fan using “G”; See; “User’s Information Manual” and the “Service
- Page 45 – Wiring
- Page 46 – SEQUENCE OF OPERATION & DIAGNOSTICS
- Page 47 – Heating Request with Gas Shut Off:
- Page 48 – WIRING DIAGRAM
- Page 49 – Thermostat Wiring Guide; HUM
- Page 50 – and Dehumidify Wiring
1
58HDV
Direct Vent 4 --- Way Multipoise
Condensing Gas Furnace
95% Downflow / Horizontal Orientations
93.5% Upflow Orientation
Installation Instructions
Special Venting Requirements for Installations in Canada
Installation in Canada must conform to the requirements of CSA
B149 code. Vent systems
must
be composed of pipe, fittings,
cements, and primers listed to ULC S636. The special vent fittings
and accessory concentric vent termination kits and accessory
external drain trap have been certified to ULC S636 for use with
those IPEX PVC vent components which have been certified to this
standard. In Canada, the primer and cement must be of the same
manufacturer as the vent system -- IPEX System 636, PVC/CPVC
Primer, Purple Violet for Flue Gas Venting and IPEX System 636,
PVC Cement for Flue Gas Venting, rated Class IIA, 65 deg C. must
be used with this venting system -- do not mix primers and cements
from one manufacturer with a vent system from a different
manufacturer. Follow the manufacturer’s instructions in the use of
primer and cement and never use primer or cement beyond its
expiration date.
The safe operation, as defined by ULC S636, of the vent system is
based on following these installation instructions, the vent system
manufacturer’s installation instructions, and proper use of primer
and cement. All fire stop and roof flashing used with this system
must be UL listed material. Acceptability under Canadian standard
CSA B149 is dependent upon full compliance with all installation
instructions. Under this standard, it is recommended that the vent
system be checked once a year by qualified service personnel.
The authority having jurisdiction (gas inspection authority,
municipal building department, fire department, etc) should be
consulted before installation to determine the need to obtain a
permit.
ama
CERTIFIED
Consignes spéciales pour l’installation de ventillation au Canada
L’installation faite au Canada doit se conformer aux exigences du
code CSA B149. Ce systême de ventillation
doit
se composer de
tuyaux, raccords, ciments et apprêts conformes au ULC S636. La
tuyauterie de ventillation des gaz, ses accessoires, le terminal
concentrique mural ainsi que l’ensemble du drain de condensat
extérieur ont été certifiés ULCS 636 pour l’application des
composantes IPEX PVC qui sont certifiées à ce standard. Au
Canada l’apprêt et le ciment doivent être du même manufacturier
que le systême de ventillation -- IPEX Système 636, Apprêt
PVC/CPVC. Mauve Violette pour conduit en évacuation des gaz et
IPEX Système 636, ciment pour PVC pour conduit en évacuation
des gaz, évalué CLASSE IIA, 65 deg. C. doit ëtre utilisé avec ce
systèeme d’évacuation -- ne pas mélanger l’apprêt et le ciment d’un
manufacturier avec le systême de ventillation d’un autre
manufacturier. Bien suivre les indications du manufacturier lors de
l’utilisation de l’apprêt et du ciment et ne pas utiliser ceux--ci si la
date d’expiration est atteinte.
L’opération sécuritaire, tel que définit par ULC S636, du système
de ventilation est basé sur les instructions d’installation suivantes,
ainsi que l’usage approprié de l’apprêt et ciment. Tout arrët feu et
solin de toit utilisés avec ce système doivent être des matériaux
listés UL. L’acceptation du standard Canadien CSA B419 est
directement relié à l’installation conforme aux instructions ci-- haut
mentionnées. Le standard Canadien recommande l’ inspection par
un personel qualifié et ce, une fois par année.
Les autoritées ayant juridiction (inspecteurs de gas, inspecteurs en
bâtiments, département des incendies, etc) devraient être consultées
avant l’installation afin de déterminer si un permis est requis.
TABLE OF CONTENTS
PAGE
IMPORTANT INFORMATION
2
. . . . . . . . . . . . . . . . . . . . . . . . .
SAFE INSTALLATION REQUIREMENTS
3
. . . . . . . . . . . . . . .
COMBUSTION & VENTILATION AIR
8
. . . . . . . . . . . . . . . . . .
CONCENTRIC TERMINATION
31
. . . . . . . . . . . . . . . . . . . . . . .
GAS SUPPLY & PIPING
33
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL WIRING
37
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DUCTWORK & FILTER
39
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHECKS & ADJUSTMENTS
42
. . . . . . . . . . . . . . . . . . . . . . . . .
FURNACE MAINTENANCE
44
. . . . . . . . . . . . . . . . . . . . . . . . .
SEQUENCE OF OPERATION & DIAGNOSTICS
46
. . . . . . . . .
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
2 Required Notice for Massachusetts Installations IMPORTANT The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:5.08: Modifications to NFPA--54, Chapter 102) Revise 10.8.3 by adding the following additional requirements: a. For all side wall horizontally vented g...
3 NOTE : Read the entire instruction manual before starting the installation. NOTE : Please retain these instructions with the furnace after installation for future reference. SAFETY CONSIDERATIONS FURNACE RELIABILITY HAZARD Improper installation or misapplication of furnace may require excessive se...
4 furnace, the return air shall also be handled by a duct(s) sealed tothe furnace casing and terminating outside the space containingthe furnace. S A gas--fired furnace for installation in a residential garage mustbe installed as specified in “ Installation” of these instructions. S This furnace is ...