Page 2 - CONTENTS
– 2 – CONTENTS ORIGINAL INSTRUCTION ..................................................................................................... 3WARNING INDICATIONS ON THE AIR CONDITIONER UNIT .............................................. 5PRECAUTION FOR SAFETY ..............................................
Page 3 - Original instruction; Generic Denomination: Air Conditioner; Agent
– 3 – Original instruction Please read carefully through these instructions that contain impor tant information which complies with the“Machinery” Directive (Directive 2006/42/EC), and ensure that you understand them. Some of the details provided in these instructions differ from the service manual,...
Page 4 - Definition of Protective Gear; Work undertaken; Indication; DANGER; Explanation; Indicates contents assumed that an injury or proper ty damage (; Mark; Indicates prohibited items (Forbidden items to do)
– 4 – Definition of Protective Gear When the air conditioner is to be transpor ted, installed, maintained, repaired or removed, wear protectivegloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when under taking thespecial work det...
Page 5 - Warning Indications on the Air Conditioner Unit; Confirm that labels are indicated on the specified positions; Warning indication; ELECTRICAL SHOCK HAZARD; WARNING; BURST HAZARD; Description
– 5 – Warning Indications on the Air Conditioner Unit [Confirmation of warning label on the main unit] Confirm that labels are indicated on the specified positions If removing the label during par ts replace, stick it as the original. Warning indication WARNING ELECTRICAL SHOCK HAZARD Disconnect all...
Page 6 - Precaution for Safety; General; DENGER; Turn off
– 6 – Precaution for Safety WARNING General Before star ting to repair the air conditioner, read carefully through the Service Manual, and repairthe air conditioner by following its instructions. Only qualified service person ( 1) is allowed to repair the air conditioner. Repair of the air condition...
Page 7 - ) Do not use a welder in the closed room.
– 7 – Execute discharge between terminals. Prohibition Stay on protection Even if the circuit breaker has been set to the OFF position before the service panel is removedand the electrical par ts are repaired, you will still risk receiving an electric shock.For this reason, shor t-circuit the high-v...
Page 10 - Disposal; DI series
– 10 – Explanations given to user • If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person to have the repairs done.Do not set the circuit breaker to the ON position until the rep...
Page 11 - Safety Caution Concerned to New Refrigerant
– 11 – New Refrigerant (R410A) This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer. 1. Safety Caution Concerned to New Refrigerant The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant...
Page 12 - Required Tools for R410A; Used tool; attaching vacuum pump adapter.
– 12 – 4. Tools 1. Required Tools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary,etc. Accordingly, the tools to be used are classified into the following three types. 1) Tools exclusive for R410A (Those which cannot be used for conv...
Page 31 - • Capacity variation ratio according to temperature
– 31 – • Capacity variation ratio according to temperature RAV-SP1104AT8 (Z) (ZG)-E, -TRRAV-SP1404AT8 (Z) (ZG)-E, -TRRAV-SP1604AT8 (Z) (ZG)-E, -TR RAV-SP1104AT7 (Z) (ZG)RAV-SP1404AT7 (Z) (ZG)RAV-SP1604AT7 (Z) (ZG) <Cooling> <Heating> 50 55 60 65 70 75 80 85 90 95 100 105 32 33 34 35 36 3...
Page 34 - Gas side socket; Inner
– 34 – RBC-TRP100E (Simultaneous Triple) <Gas side> Header assembly <Liquid side> Branch pipe assembly Gas side socket Liquid side socket Ø15.9 (External diameter) Ø9.5 (External diameter) Ø12.7 (External diameter) Inner diameter Ø25.4 Inner diameter Ø12.7 Inner diameter Ø15.9 Inner diam...
Page 35 - OUTDOOR UNIT REFRIGERATING CYCLE DIAGRAM
– 35 – In cooling operationIn heating operation Ø25 × L180 Ø25 × L210 TS sensor P Pressure switch TO sensor TE sensor TD sensor TL sensor Cooling: High pressureHeating: Low pressure Cooling: Low pressureHeating: High pressure Check joint Heat exchanger Ø8, 2 rows, 52 stages FP1.45, flat fin Accumula...
Page 37 - SPECIFICATIONS OF ELECTRICAL PARTS; Parts name
– 37 – 5. SPECIFICATIONS OF ELECTRICAL PARTS 5-1. Outdoor Unit No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 Parts name Compressor Outdoor fan motor 4-way valve coil PMV coil High pressure switch Reactor Reactor Reactor P.C. board (Compressor drive) P.C. board (Fan moto...
Page 38 - NOTE
– 38 – 6. REFRIGERANT R410A This air conditioner adopts the new refrigerant HFC(R410A) which does not damage the ozone layer. The working pressure of the new refrigerant R410Ais 1.6 times higher than conventional refrigerant(R22). The refrigerating oil is also changed inaccordance with change of ref...
Page 39 - Flare Processing Procedures and Precautions; b) Removing Burrs and Chips
– 39 – Table 6-2-1 Thicknesses of annealed copper pipes 1. Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds20 mm. In...
Page 40 - Table 6-2-3 Dimensions related to flare processing for R410A / R22; Table 6-2-4 Flare and flare nut dimensions for R410A
– 40 – c) Inser tion of Flare Nut d) Flare Processing Make cer tain that a clamp bar and copper pipe have been cleaned. By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R410A or conventional flare tool. Flare processing dimensions differ accordingto the ...
Page 41 - Flare Connecting Procedures and Precautions; b) Correctly align the processed flare surface with the union axis.
– 41 – 43˚to 45˚ 45˚to 46˚ A B C D Fig. 6-2-2 Relations between flare nut and flare seal surface 2. Flare Connecting Procedures and Precautions a) Make sure that the flare and union por tions do not have any scar or dust, etc. b) Correctly align the processed flare surface with the union axis. c) Ti...
Page 42 - Refer to the “; Connect the charge hose of the vacuum pump adapter.; bit by bit
– 42 – 6-3. Tools 6-3-1. Required Tools Refer to the “ 4. Tools ” 6-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to thefollowing steps. (INDOOR unit) (Liquid side) Refrigerant cylinder (With siphon pipe) Check val...
Page 43 - liquid; Silver brazing filler
– 43 – Gauge manifold [ Cylinder with siphon ] [ Cylinder without siphon ] OUTDOOR unit Gauge manifold OUTDOOR unit Refrigerant cylinder Electronic balance Refriger ant cylinder Electronic balance Siphon 1) Be sure to make setting so that liquid can be charged. 2) When using a cylinder equipped with...
Page 44 - Characteristics required for flux; • Noncorrosive flux; Piping materials for brazing and used; Piping material
– 44 – Nitrogen gas cylinder Pipe Flow meter M Stop valve From Nitrogen cylinder Nitrogen gas Rubber plug 2. Characteristics required for flux • Activated temperature of flux coincides with the brazing temperature. • Due to a wide effective temperature range, flux is hard to carbonize. • It is easy ...
Page 45 - Existing Pipe; Pipe outer diameter; Operation System; Place position
– 45 – 6-6. Instructions for Re-use Piping of R22 or R407C Instruction of Works:The existing R22 and R407C piping can bereused for our digital inverter R410A productsinstallations. NOTE) Confirmation of existence of scratch or dent of theformer pipes to be applied and also confir mation ofreliabilit...
Page 46 - Existing pipe SW; Piping necessary to change the flare nut/; Switch
– 46 – 6-6-5. Final Installation Checks Do not apply the refrigerator oil to the flare surface. Existing pipe: NO * Use a new pipes. Clean the pipes or use the new pipes. Trial run Is it possible to operate the existing air conditioner? Was not largely discolored oil or a large quantity of remains d...
Page 47 - Cautions for using existing pipe; Reference outside diameter; When shipped from factory; Procedure
– 47 – 6-6-6. Handling of Existing Pipe When using the existing pipe, carefully check it forthe following: • Wall thickness (within the specified range) • Scratches and dents • Water, oil, dir t, or dust in the pipe • Flare looseness and leakage from welds • Deterioration of copper pipe and heat ins...
Page 48 - CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS
– 48 – 7. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS 7-1. Outdoor Unit Control 7-1-1. Print Circuit Board, MCC-1596 (Compressor IPDU) CN851 (Red) Connector for MCC-1597 (CN505) CN101 (White) Connector for MCC-1597 (CN502) CN13 (Black) Terminal for power relay F02 Electric circuit protective fu...
Page 52 - REQUIREMENT; restar ts after 2 minutes 30 seconds.
– 52 – 7-2. Outline of Main Controls 1. PMV (Pulse Motor Valve) control 1) PMV is controlled between 30 and 500 pulses during operation. 2) In cooling operation, PMV is usually controlled with the temperature difference between TS sensor and TC sensor aiming 1 to 4K as the target value. 3) In heatin...
Page 53 - Outdoor fan control; Revolution frequency allocation of fan taps [rpm]; When TE
– 53 – 3. Outdoor fan control Revolution frequency allocation of fan taps [rpm] 3-1) Cooling fan control The outdoor fan is controlled by TL sensor, TO sensor and the operation frequency.The outdoor fan is controlled by every 1 tap of DC fan control (14 taps). Only for 60 seconds after the opera...
Page 54 - Coil heating control; otherwise a trouble of the compressor may be caused.
– 54 – 4. Coil heating control 1) This control function heats the compressor by turning on the stopped compressor instead of a case heater. It purposes to prevent stagnation of the refrigerant inside of the compressor. 2) As usual, turn on power of the compressor for the specified time before a test...
Page 55 - Current release value shift control; Current release control value (; Temperature range; To; HEAT
– 55 – 8. Over-current protective control 1) When the over-current protective circuit detected an abnormal current, stop the compressor. 2) The compressor restar ts after 2 minutes 30 seconds setting [1] as an error count. 3) When the error count [8] was found, determine an error and restar t operat...
Page 56 - ) The time of above d can be changed by; Start of heating operation; In normal To; compressor is terminated.
– 56 – 10. Defrost control 1) In heating operation, defrost operation is performed when TE sensor satisfies any condition in A zone to D zone. 2) During defrosting operation, it finishes if TE sensor continued 12°C or higher for 3 seconds or continued 7°C # TE < 12°C for 1 minute. The defrost ope...
Page 57 - Trouble
– 57 – 8. TROUBLESHOOTING 8-1. Summary of Troubleshooting <Wired remote controller type> 1. Before troubleshooting 1) Required tools/instruments • + and – screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch • Tester, thermometer, pressure gauge, etc. 2) Confirmati...
Page 62 - Returned to usual display; Calling of sensor temperature display; is; marks in the above table are displayed only
– 62 – <Operation procedure> 1 2 3 4 Returned to usual display 2 4 1 3 SET TIME TIMER SET TEST FILTER LL RESET TEMP. CL FAN SAVE A A SWING/FIX VENT MODE ON / OFF UNIT LOUVER T 8-2-3. Monitor Function of Remote Controller Switch n Calling of sensor temperature display <Contents> Each data...
Page 65 - Error mode detected by indoor unit
– 65 – Error mode detected by indoor unit Operation of diagnostic function Check code E03 E04 E08 L03 L07 L08 L09 L30 P10 P12 P19 P31 F01 F02 F10 F29 E10 E18 Cause of operation No communication from remotecontroller (including wireless) andcommunication adapter The serial signal is not output fromou...
Page 66 - Error mode detected by outdoor unit; The check code has been ramified from
– 66 – Error mode detected by outdoor unit The check code has been ramified from 4 series and after. The ramified check code is displayed only when both the indoor unit and the outdoor unit are 4 series and after. (Ex. Combination of RAV-SM140 4 UT-E with RAV-SP140 4 AT8-E) When the indoor unit is 3...
Page 68 - For the wireless models, an error is notified with indication lamp.
– 68 – Error mode detected by remote controller or central controller (TCC-LINK) 2 The check code cannot be displayed by the wired remote controller. (Usual operation of air conditioner becomes unavailable.) For the wireless models, an error is notified with indication lamp. 3 This trouble is relate...
Page 73 - Refer to
– 73 – Check code [H03] [H04] Outdoor LED display <Display 1> <Display 2> ¡ ¡ ¡ l l l ¡ l l ¥ l ¥ <Display 1> <Display 2> ¡ ¡ ¡ l l l ¡ ¥ ¡ l ¡ ¥ <Display 1> <Display 2> ¡ ¡ ¡ l l l ¡ ¥ l l l l Check and troubleshooting (Item without special mention Indicates part...
Page 80 - Output v; Temperature sensor; Representative value
– 80 – Resistance (k Ω ) (50˚C or lo w er) Resistance (k Ω ) (50˚C or higher) 0 0 50 100 150 200 0 5 10 15 20 10 20 30 40 50 60 70 80 90 100 Temperature (˚C) Resistance (k Ω ) 0 0 10 20 30 40 Output v oltage (V) 10 20 30 40 50 60 70 80 90 100 Temperature (˚C) Temperature sensor Temperature – Resista...
Page 81 - Table Inspection of outdoor unit main parts
– 81 – Red White Black Connector : White Red White Black Table Inspection of outdoor unit main parts No. 1 2 3 Parts name Compressor(Model : DA422A3F-27M) Outdoor fan motor(Model : ICF-280-A100-1) 4-way valve coil(Cooling/heating switching)(Model : STF-01AJ502E1) Checking procedure Measure the resis...
Page 82 - SETUP AT LOCAL SITE AND OTHERS
– 82 – 9. SETUP AT LOCAL SITE AND OTHERS 1. Display range on remote controller The setup range (Operation mode/Air volume select/Setup temp) of the indoor unit which was set to themaster unit is reflected on the remote controller. 2. Address setup Turn on power of the indoor unit to be controlled in...
Page 83 - Indoor unit power-ON sequence; Power ON
– 83 – n Indoor unit power-ON sequence <Cautions at test run> • Power supply/Indoor/Outdoor serial and Gr wiring: OK• Powers of all indoor units are turned on within 3 minutes.• Reception time for remote controller operation (After power supply was turned on) 1) When address is OK : Approx. 50...
Page 85 - All LED are colorless when it goes off.; Specifications; LED; Enlarged view of
– 85 – 9-3-2. Service Support Function (LED Display, Switch Operation) 1. Outline A various setup and operation check can be performed by DIP switches at 3 positions(SW802, SW803, SW804) and the pushdown button switches (SW800, SW801) at 2 positions. Operation part Display part All LED are colorless...
Page 86 - ) Display selection list
– 86 – ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 TC SW803 TL SW803 TE SW803 TA SW803 TO SW803 TD SW803 TCJ SW803 TH SW803 TS SW803 SW803 SW803 SW803 SW803 SW803 SW803 9-3-3. Oth...
Page 88 - Sensor error, unconnected
– 88 – 3) Sensor, current, compressor operation frequency, PMV opening display The values detected by the controller, such as temperature sensor or current value are simply confirmed. (Legend) l l ¥ l l ¡ D800 D801 D802 D803 D804 D805 (Yellow) (Yellow) (Yellow) (Yellow) (Yellow) (Green) l : Go off, ...
Page 90 - Operation when pushdown button switch SW801 is pushed; Forced star t command
– 90 – ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 ON 2 3 4 1 SW804 SW804 SW804 SW804 SW804 SW804 SW804 Operation when pushdown button switch SW801 is pushed 4-way valve relay operation (For RY700, CN70 check) Turn on 4-way valve power relay (RY700).When pushing SW801 again or when 2 minu...
Page 91 - Item code
– 91 – Setup of line address of outdoor unit, indoor unit address, and group address Completion of cabling work Turn on power of outdoor unit. Turn on power of outdoor unit. Connect one remote controller with one indoor unit (1 : 1) tentatively with communication cable. END Turn on power of outdoor ...
Page 92 - Outdoor; Indoor; Single group operation
– 92 – 10-2. Address Setup & Group Control <Terminology> Indoor unit No. : N - n = Outdoor unit line address N (Max. 30) - Indoor unit address n (Max. 64) Group address : 0 = Single (Not group control) 1 = Master unit in group control2 = Sub unit in group control Master unit (= 1) : The re...
Page 93 - Only turning on source power supply (Automatic completion); The follower unit sends own thermo ON/OFF demand to the header unit.
– 93 – 1-1 Individual (Master/Sub) 2-1 Sub/Header 1-1 Sub/Header 1-2 Sub/Follower 3-1 Master/Header 3-2 Sub/Follower 3-3 Sub/Follower 10-2-2. Automatic Address Example from Unset Address (No miswiring) 1. Standard (One outdoor unit) 1) Single 2) Group operation (Twin, Triple operation) (Multiple out...
Page 94 - Multiple groups operation; Change is necessary
– 94 – 2-1 Single Twin Triple 1-1 1-2 3-1 3-2 3-3 2-1 Sub/Header 1-1 Sub/Header 3-1 Master/Header 8-1 Sub/Header 2-1 Sub/Header 1-1 Sub/Header 2-3 Master/Follower 3-1 Sub/Header 3-3 Sub/Follower 1-2 Sub/Follower 1-2 Sub/Header (1-1) (1-2) (1-3) 1-3 Master/Follower 1-1 Sub/Follower 1-1 Individual (Ma...
Page 95 - Single system; Triple
– 95 – AB AB Terminal block for remote controller wiring of indoor unit Terminal block Remote controller unit Remote controller wire (Procured locally) 10-3. Remote Controller Wiring • Strip off approx. 9 mm the wire to be connected. • For single system, use non polarity, 2 core wire is used for wir...
Page 96 - END; • Set an indoor unit per a remote controller.
– 96 – (Example of 2-lines cabling)(Real line: Cabling, Broken line: Refrigerant pipe) For the above example, perform setting by connecting singly the wired remote controller without remote controller inter-unit cable. Group address Individual : 0000 Master unit : 0001 Sub unit : 0002 In case of gro...
Page 97 - Operation; To know the position of indoor unit body by address
– 97 – 1 2 END Operation <Operation procedure> 2 1 SET TIME TIMER SET TEST FILTER LL RESET TEMP. CL FAN SAVE A A SWING/FIX VENT MODE ON / OFF UNIT LOUVER T 1 2 3 END <Operation procedure> 3 1 2 SET TIME TIMER SET TEST FILTER LL RESET TEMP. CL FAN SAVE A A SWING/FIX VENT MODE ON / OFF UNI...
Page 99 - Setting the jumper wires and DIP switches; Part name
– 99 – 11. REPLACEMENT OF THE SERVICE P.C. BOARD (4316V417) MCC-1599 1. Setting the jumper wires and DIP switches Model switching (J800 to J803) Since this service P.C. board is available for several models, cut the jumper wires according to the following table. If they are not cut correctly, an err...
Page 100 - HOW TO EXCHANGE COMPRESSOR; For exchange of compressors, refer to (11) Compressor in Section
– 100 – 12. HOW TO EXCHANGE COMPRESSOR 12-1. Exchanging Procedure of Compressor (Outline) 12-2. Exchange of Compressor For exchange of compressors, refer to (11) Compressor in Section 14. Detachments . START Has refrigerant recovery work been done? YES Remove the defective compressor. Mount a servic...
Page 101 - ts; IO
– 101 – S u p e r D ig it a l In v e rt e r EN-i i C o n te n ts 1 P RECAUTIO NS FOR SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2 A C C E S S O R Y P A R T S A N D R E F R IG E R A N T . . . . . . . . . . . . . . . . . . . . . . . . . ....
Page 102 - dic
– 102 – E N -2 2 S u p e r D i g i ta l I n v e rt e r D efi n i t i on o f Prot ec t i v e G e ar W h e n th e a i r c o n d i t i o n e r i s to b e tr a n s p o rt e d , i n s ta ll e d , m a i n ta i n e d , re p a i re d o r re m o v e d , w e a r p ro te c t i v e g l o v e s a n d “ s a fe ty...
Page 103 - PRECAUTIONS FOR SAFETY
– 103 – E N -4 4 S u p e r D ig it a l In v e rt e r 1 PRECAUTIONS FOR SAFETY W A R N IN G General • B e fo re s ta rt in g t o i n s ta ll th e a ir c o n d it io n e r, r e a d c a re fu lly t h ro u g h t h e I n s ta lla ti o n M a n u a l, a n d f o llo w i ts i n s tr u c ti o n s t o in s ta ...
Page 105 - CC; IN
– 105 – EN-8 8 S u p e r D i g i ta l I n v e rt e r 2 A CC E SSOR Y P A R T S A N D R E F R I G E R A N T A c c e s s o ry P a rt s P a rt n a m e Q ’ ty S h a p e U s a g e O u td o o r u n i t i n s ta ll a t i o n m a n u a l 1 H a n d th i s d i re c t l y to th e c u s to m e r . ( F o r o t...
Page 108 - EF
– 108 – E N - 1 4 1 4 S u p e r D i g i ta l I n v e rt e r S e r i a l i n s ta ll a t i o n i n f ro n t a n d r e a r O p e n a b o v e a n d to th e r i g h t a n d l e ft o f th e u n i t . T h e h e i g h t o f a n o b s ta c l e i n b o th th e fr o n t a n d re a r o f th e u n i t s h o u l...
Page 113 - OC
– 113 – E N -2 4 2 4 S u p e r D ig it a l In v e rt e r 8 EARTHING C o n n e c t th e e a rt h l in e p ro p e rl y f o llo w in g a p p lic a b le t e c h n ic a l s ta n d a rd s . C o n n e c ti n g t h e e a rt h l in e i s e s s e n ti a l to p re v e n ti n g e le c tr ic s h o c k a n d t o ...
Page 115 - APPENDIX
– 115 – E N -2 8 2 8 S u p e r D ig it a l In v e rt e r 1 5 APPENDIX W o r k i n s tr u c ti o n s T h e e x is ti n g R 2 2 a n d R 4 0 7 C p ip in g c a n b e r e u s e d f o r o u r d ig it a l in v e rt e r R 4 1 0 A p ro d u c t in s ta lla ti o n s . W A R N IN G C o n fi rm in g t h e e x is...
Page 117 - la
– 117 – E N -3 2 3 2 S u p e r D ig it a l In v e rt e r D e c la ra ti o n o f C o n fo rm it y N o te : T h is d e c la ra ti o n b e c o m e s i n v a lid i f te c h n ic a l o r o p e ra ti o n a l m o d if i c a ti o n s a re i n tr o d u c e d w it h o u t th e m a n u fa c tu re r’ s c o n s ...
Page 118 - • Remove the screws and then pull service panel; Remarks
– 118 – 14. DETACHMENTS 14-1. Outdoor Unit RAV-SP1104AT8 (7), RAV-SP1404AT8 (7), RAV-SP1604AT8 (7) series No. 1 Part name Commonprocedure Procedure WARNING Stop operation of the air conditioner and turn offbreaker switch. CAUTION Ensure wearing of gloves when performing any workin order to avoid inj...
Page 122 - ) Remove lead wires and connectors to other
– 122 – Support (4 positions) Statue of control board when removed Interface board (Control board) No. 5 Part name Interface board(Control board) MCC-1599 Procedure 1. Detachment 1) Carry out the operation in 1. of , and 1. of above. 2) Remove lead wires and connectors to other components from t...
Page 124 - ) Remove the lead wires connector to other components from
– 124 – Interface board Fan-IPDU boardg Using the hook, it is possible to temporarily suspendthe inverter assembly (front). Screws (2 positions) Inverter assembly (front) Using Noize filter board State of noize filter board when removed State of noize filter board when removed No. 7 Part name Noise ...
Page 125 - ) Remove the lead wire and connector to other
– 125 – No. 8 Part name CompressorIPDU board MCC-1596 Procedure 1. Detachment 1) Carry out the operation in 1. of , 1. of , 1. of
, 1. of and 1. of . 2) Remove the screw (4 positions) fixing the inver ter assembly (IPDU). 3) Remove the lead wire and connector to other components from the c...
Page 127 - Removal of defective compressor
– 127 – No. 10 Part name Compressor Compressorlead Procedure 1. Removal of defective compressor 1) Recover the refrigerant gas. 2) Carry out work of item 1 of , 1 of and 1 of . 3) Remove the piping panel (Front). Remove the piping panel (Front) and screws of thebottom plate. (Hexagonal screw Ø...
Page 128 - Mounting of compressor; Refrigerant charge
– 128 – No. 10 Part name Compressor Compressor lead (Continued) Procedure 2. Mounting of compressor 1) Mount the compressor in the reverse procedure for removal. NOTE • After replacement of the compressor, be sure to replace the compressor lead. (Repair par tcode of compressor lead: 43160612)In this...
Page 130 - EXPLODED VIEWS AND PARTS LIST; Outdoor Unit
– 130 – 15. EXPLODED VIEWS AND PARTS LIST Outdoor Unit RAV-SP1104AT8-E, RAV-SP1104AT8Z-E, RAV-SP1104AT8ZG-ERAV-SP1104AT8-TR, RAV-SP1104AT8Z-TR, RAV-SP1104AT8ZG-TRRAV-SP1104AT7, RAV-SP1104AT7Z, RAV-SP1104AT7ZG 23 18 20 25 38, 39, 40 41, 42, 43 16 48 2 1 8 21 13 15 37 24 4, 10 32, 33 29, 30 44, 45 22 ...
Page 132 - Inverter Assembly
– 132 – 711 701 717 713 720 TETS TO TD TL 718, 719 708 709 715 706 707 721 710 718, 719 720 702 704 705 714 712 720 Inverter Assembly RAV-SP1104AT8-E, RAV-SP1104AT8Z-E, RAV-SP1104AT8ZG-ERAV-SP1104AT8-TR, RAV-SP1104AT8Z-TR, RAV-SP1104AT8ZG-TRRAV-SP1104AT7, RAV-SP1104AT7Z, RAV-SP1104AT7ZG
Page 133 - Bushing; Model name RAV-SP
– 133 – Location Part No. Description No. 701 43058288 Reactor, CH-56-4Z 702 43154177 Relay, 480V, 20A 704 43158207 Reactor, CH-68 705 43153006 PTC-Thermistor, ZPROYCE101A500 706 43050425 Sensor Ass’y, TC (F6) 707 43150319 Sensor Ass’y, TD (F4) 708 43160565 Terminal Block, 3P, 20A, AC250A 709 431605...
Page 136 - Inverter Unit
– 136 – 711 701 717 713 720 TETS TO TD TL 718, 719 708 709 715 706 707 721 710 718, 719 720 702 704 705 714 712 720 Inverter Unit RAV-SP1404AT8-E, RAV-SP1404AT8Z-E, RAV-SP1404AT8ZG-ERAV-SP1404AT8-TR, RAV-SP1404AT8Z-TR, RAV-SP1404AT8ZG-TRRAV-SP1404AT7, RAV-SP1404AT7Z, RAV-SP1404AT7ZG
Page 142 - WARNINGS ON REFRIGERANT LEAKAGE; (2) When there is an effective opening with the; Important; For the amount of charge in this example:
WARNINGS ON REFRIGERANT LEAKAGE (2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerantgas (opening without a door, or an opening 0.15%or larger than the respective floor spaces at the topor bottom of the door). (3) If an indoor unit is installed in each ...