Carrier 48TC**16- Manual
Carrier 48TC**16– Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – SAFETY CONSIDERATIONS; WARNING
- Page 4 – INSTALLATION; Jobsite Survey; Step 1 — Plan for Unit Location; NOTE
- Page 5 – COMPONENT; Step 2 — Plan for Sequence of Unit Installation; Ductwork must be attached to curb and
- Page 7 – Step 5 — Field Fabricate Ductwork; Do not connect ductwork to unit.; PROPERTY DAMAGE HAZARD; Step 6 — Rig and Place Unit; UNIT DAMAGE HAZARD; CAUTION; DETAIL “A”
- Page 8 – Step 7 — Convert to Horizontal and Connect; without
- Page 9 – Step 8 — Install Outside Air Hood; Factory Option —; Economizer Hood and Two–Position Hood; Two Position Damper Hood Removal and Setup --; Economizer Hood and Two–Position
- Page 10 – Be careful not; Step 9 — Install Flue Hood
- Page 11 – Step 10 — Install Gas Piping; UNIT; EQUIPMENT DAMAGE HAZARD
- Page 12 – Option
- Page 13 – Step 11 — Install External Condensate Trap and
- Page 14 – All units must have an external trap for condensate; Step 12 — Make Electrical Connections; ELECTRICAL SHOCK HAZARD; Do not use gas piping as an electrical ground.
- Page 15 – FIRE HAZARD; to be connected to a 208-v power supply, the control
- Page 16 – Convenience Outlets —; Convenience Outlet Utilization
- Page 17 – ELECTRICAL OPERATION HAZARD; Installing
- Page 19 – Heat Anticipator Settings —
- Page 20 – Control Connections
- Page 21 – Adaptive Dehumidification System Humidistat Wiring; with EDGE Pro Thermidistat Device
- Page 22 – PremierLink
- Page 25 – Temperature (SAT) Sensor on Small Rooftop Units; Field Connections; Table 3 – PremierLink Sensor Usage; NOTES
- Page 27 – Space Sensors —; Connect Thermostat —
- Page 28 – Economizer Controls; COVER REMOVED
- Page 29 – Sensor Connections; UNIT PERFORMANCE HAZARD; Io; Humidistat connections:
- Page 30 – Filter Status Switch —; Supply Fan Status Switch —; CTB; Connection; Connection
- Page 31 – CCN Bus
- Page 32 – RTU Open Control System
- Page 35 – Table 8 – RTU Open Controller Inputs and Outputs
- Page 36 – Indoor Air Quality (CO
- Page 38 – Relative Humidity Sensor
- Page 39 – RTU Open Controller Integration Guide; SW3 Protocol Selection; PROTOCOL; Baud Rate Selections; BAUD RATE
- Page 40 – Local Access —; BACview; Handheld Connections
- Page 41 – Table 9 – LEDs; Tx; RTU Open; Outdoor Air Enthalpy Control; Differential Enthalpy Control —
- Page 42 – Smoke Detectors
- Page 43 – Smoke Detector Locations
- Page 44 – Completing Installation of Return Air Smoke Sensor:; Sampling Tube; Additional Application Data —
- Page 45 – Table 10 – Unit Wire/Fuse or HACR Breaker Sizing Data; UN; Legend and Notes for Table 10
- Page 46 – IV Wiring; Step 13 — Adjust Factory--Installed Options; Smoke Detectors —; Step 14 — Install Accessories
48TC**16
Single Package Rooftop
Gas Heating/Electric Cooling Unit
with Puron
r
(R --- 410A) Refrigerant
Size 16
Installation Instructions
NOTE
: Read the entire instruction manual before starting
the installation
TABLE OF CONTENTS
SAFETY CONSIDERATIONS
2
. . . . . . . . . . . . . . . . . . . .
INSTALLATION
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Jobsite Survey
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 1 -- Plan for Unit Location
4
. . . . . . . . . . . . . . . . . .
Roof Mount
5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 2 -- Plan for Sequence of Unit Installation
5
. . . . . .
Curb--Mount Installation
5
. . . . . . . . . . . . . . . . . . . . .
Pad--Mount Installation
5
. . . . . . . . . . . . . . . . . . . . . .
Frame--Mount Installation
5
. . . . . . . . . . . . . . . . . . . .
Step 3 -- Inspect Unit
5
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 4 -- Provide Unit Support
5
. . . . . . . . . . . . . . . . . . .
Roof Curb Mount
5
. . . . . . . . . . . . . . . . . . . . . . . . . .
Slab Mount (Horizontal Units Only)
5
. . . . . . . . . . .
Alternate Unit Support
(In Lieu of Curb or Slab Mount)
5
. . . . . . . . . . . . . .
Step 5 -- Field Fabricate Ductwork
7
. . . . . . . . . . . . . . . .
Step 6 -- Rig and Place Unit
7
. . . . . . . . . . . . . . . . . . . . .
Positioning on Curb
8
. . . . . . . . . . . . . . . . . . . . . . . .
Step 7 -- Convert to Horizontal and Connect Ductwork
8
. . .
Step 8 -- Install Outside Air Hood
9
. . . . . . . . . . . . . . . .
Economizer Hood Removal and Setup —
Factory Option
9
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Two Position Damper Hood Removal and Setup —
Factory Option
9
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Economizer Hood and Two--Position Hood
10
. . . . .
Step 9 -- Install Flue Hood
10
. . . . . . . . . . . . . . . . . . . . .
Step 10 -- Install Gas Piping
11
. . . . . . . . . . . . . . . . . . . .
Factory--Option Thru--Base Connections
(Gas Connections)
11
. . . . . . . . . . . . . . . . . . . . . . . . .
Step 11 -- Install External Condensate Trap and Line
13
. .
Step 12 -- Make Electrical Connections
14
. . . . . . . . . . .
Field Power Supply
14
. . . . . . . . . . . . . . . . . . . . . . . .
All Units
15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Units without Factory--Installed Disconnect
15
. . . .
Units with Factory--Installed Disconnect
15
. . . . . . .
Convenience Outlets
16
. . . . . . . . . . . . . . . . . . . . . . .
Factory--Option Thru--Base Connections
(Electrical Connections)
18
. . . . . . . . . . . . . . . . . . . .
Units without Thru--Base Connections
18
. . . . . . . . .
Field Control Wiring
18
. . . . . . . . . . . . . . . . . . . . . . .
Thermostat
18
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit without Thru--Base Connection Kit
19
. . . . . . .
Heat Anticipator Settings
19
. . . . . . . . . . . . . . . . . . .
Humidi--MiZer
R
Control Connections
20
. . . . . . . . . .
Humidi--MiZer -- Space RH Controller
20
. . . . . . . .
PremierLink
t
(Factory Option)
21
. . . . . . . . . . . . . . . . .
Supply Air Temperature (SAT) Sensor
25
. . . . . . . . .
Outdoor Air Temperature (OAT) Sensor
25
. . . . . . .
EconoMi$er2
25
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Connections
25
. . . . . . . . . . . . . . . . . . . . . . . . . .
Space Sensors
27
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connect Thermostat
27
. . . . . . . . . . . . . . . . . . . . . . .
Configure the Unit for Thermostat Mode
27
. . . . . .
Economizer Controls
28
. . . . . . . . . . . . . . . . . . . . . . . .
Indoor Air Quality (CO
2
sensor)
28
. . . . . . . . . . . . .
Outdoor Air Quality Sensor
28
. . . . . . . . . . . . . . . . .
Space Relative Humidity Sensor or
Humidistat Connections
29
. . . . . . . . . . . . . . . . . . . .
Smoke Detector/Fire Shutdown (FSD)
30
. . . . . . . . .
Filter Status Switch
30
. . . . . . . . . . . . . . . . . . . . . . . .
Supply Fan Status Switch
30
. . . . . . . . . . . . . . . . . . .
Remote Occupied Switch
30
. . . . . . . . . . . . . . . . . . .
Power Exhaust (output)
30
. . . . . . . . . . . . . . . . . . . . .
CCN Communication Bus
31
. . . . . . . . . . . . . . . . . .
RTU Open Control System
32
. . . . . . . . . . . . . . . . . . . . .
Supply Air Temperature (SAT) Sensor
35
. . . . . . . . .
Outdoor Air Temperature (OAT) Sensor
35
. . . . . . .
EconoMi$er2
35
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Connections
35
. . . . . . . . . . . . . . . . . . . . . . . . . .
Space Temperature (SPT) Sensors
36
. . . . . . . . . . . .
Indoor Air Quality (CO
2
) Sensor
36
. . . . . . . . . . . . .
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Carrier 48TC**16
Summary
2 Outdoor Air Quality Sensor 37 . . . . . . . . . . . . . . . . . Space Relative Humidity Senor or Humidistat 37 . . Smoke Detector/Fire Shutdown (FSD) 38 . . . . . . . . . Connecting Discrete Inputs 38 . . . . . . . . . . . . . . . . . . Communication Wiring -- Protocols 39 . . . . . . . . . . . . ...
4 C10862A Fig. 1 -- Unit Dimensional Drawing – 16 Size Unit (cont.) INSTALLATION Jobsite Survey Complete the following checks before installation. 1. Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installa- tion requirements. 2. Determine unit location (...
5 Roof Mount — Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1. Table 1 – Operating Weights 48TC**16 COMPONENT UNITS LB (KG) Base Unit 1380 (627) Economizer Vertical 100 (45) Horizontal 115 (52) Humidi --- MiZer R System 62 (28) Powered Outlet 32 ...