Carrier 48MPD- Manual
Carrier 48MPD– Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 3 – Copy continues on page 14.
- Page 4 – Table 1 — Physical Data
- Page 14 – Branch circuit for power supply to unit must be protected; SLAB MOUNT DRAIN; Fig. 9 — Condensate Drain Piping Details
- Page 15 – — Ground; Fig. 12 — Field Power Wiring Connections
- Page 16 – Table 5 — Electrical Data
- Page 17 – Control Wiring; Table 6 — Recommended Sensor and
- Page 18 – — Switch; Fig. 13 — Space Temperature Sensor Wiring
- Page 19 – SPACE TEMPERATURE AVERAGING — 4 SENSOR APPLICATION; RED; SPACE TEMPERATURE AVERAGING — 9 SENSOR APPLICATION; Fig. 14 — Space Temperature Sensor Averaging; TB
- Page 20 – Fig. 15 — Heat Interlock Relay; DSIO — Relay Module; Fig. 17 — Remote Start; TB — Terminal Block; Fig. 18 — Accessory Humidity Control; TB — Terminal Block; Fig. 20 — Indoor Air Quality
- Page 22 – TRANSDUCER ACCESSORY; DPT — Duct Pressure; SPT — Suction Pressure; Fig. 28 — CCN Building Supervisor
- Page 23 – Carrier Comfort Network Interface; — The; Table 7 — CCN Connection Approved; VFD; Fig. 29 — Optional VFD — Wiring Connections
- Page 24 – Air Pressure Tubing —; Fig. 30 — Space Sensor to Communication Bus Wiring
- Page 25 – Fig. 33 — Air Pressure Tubing Locations
- Page 26 – Fig. 35 — Flue and Inlet Hood Locations; Fig. 36 — Inlet Hood Assembly
- Page 27 – Fan Isolator Adjustment —; Remove shipping hard-; Check Compressor Mounting; For applications requiring; Fig. 40 — Outer View, Compressor Mounting; Fig. 39 — Fan isolator Adjustment
- Page 28 – System Check; Fig. 41 — Compressor Mounting —; Fig. 43 — Rear View of Compressor Mounting
- Page 29 – Compressor Oil —; Fig. 44 — Operating Oil Levels
- Page 35 – Controls Configuration and Quick Test; The switch must be set prior to unit operation. To set the; Table 22 — Filter Switch Dirty Set Point
- Page 36 – Table 23 — HSIO Keypad Key Usage; Fig. 46 — Psychrometric Chart for; Fig. 47 — Wiring Connections for Solid-State
- Page 37 – Table 24 — Set Point Ranges and Defaults
- Page 38 – Table 25 — Basic Configuration Data; Gas Pressure Check —
- Page 39 – General; Operating
- Page 40 – Table 26 — IGC Control Board LED Alarms; IGC
- Page 41 – Control Loop Checkout; Table 27 — 48/50MP Units SMG, SCV and MLG Recommended Starting Values
- Page 42 – IAQ Control Loop Adjustment —; Table 29 — Index of Lead/Lag Circuits and; LEAD CIRCUIT; Final Checks —
- Page 43 – Default Set Points/Changing Set Points —
- Page 45 – Table 30 — Variable Frequency Drive (VFD) Display; SERVICE; All unit components can be reached; SEQ; DSPL; REMOTE; RUN; Fig. 49 — VFD Digital Operator
- Page 46 – Cleaning —
- Page 47 – Lubrication; Coil Cleaning —; Clean the coils with a vacuum cleaner,; Refrigerant Circuit; Schrader connection for charging liquid refrigerant.; Fig. 52 — Burner Section Detail; Fig. 53 — Removing Heat Exchanger Ceramic
- Page 49 – Moisture/Liquid Indicator —; ALL OUTDOOR FANS MUST BE OPERATING
- Page 50 – Table 31 — Pressure Switch Settings,; SWITCH; Low-Pressure Switch —
- Page 51 – Fig. 61 — Motor Plate Adjustment
- Page 52 – Fig. 62 — Pulley Alignment
- Page 53 – Control Modules —
- Page 54 – Refrigerant Feed Components —
- Page 55 – TORQUE; TROUBLESHOOTING; Fig. 64 — Condenser Fan Adjustment
- Page 56 – TROUBLESHOOTING AND DIAGNOSTICS
- Page 58 – Refer to Fig. 65 for IGC troubleshooting information.
- Page 60 – PACKAGED SERVICE TRAINING; ] Packaged Service Training
- Page 61 – II. PRELIMINARY CHECKLIST ITEMS; CONTROL SETTINGS FOR NON-NETWORKED, FREESTANDING UNIT
Installation, Start-Up and Service
Instructions
CONTENTS
Page
GENERAL
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
SAFETY CONSIDERATIONS
. . . . . . . . . . . . . . . . .
2
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-28
Jobsite Survey
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Unit Placement
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Roof Mount
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Slab Mount
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Field-Fabricated Ductwork
. . . . . . . . . . . . . . . . . .
3
Rigging
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Condensate Drains
. . . . . . . . . . . . . . . . . . . . . . . . .
3
Condensate Coil Shipping Covers
. . . . . . . . . .
3
Install Outdoor Hoods
. . . . . . . . . . . . . . . . . . . . . .
3
Make Electrical Connections
. . . . . . . . . . . . . . . . 14
• POWER SUPPLY
Field Electrical Connections
. . . . . . . . . . . . . . . . 14
• POWER WIRING
Control Wiring
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
• SENSORS
• HUMIDITY CONTROL AND HOT WATER
AND STEAM VALVES
• SPACE TEMPERATURE SENSOR (T55)
• SPACE TEMPERATURE SENSOR (T56)
(CV Applications Only)
• SPACE TEMPERATURE AVERAGING
• HEAT INTERLOCK RELAY (VAV Units Only
— Not Necessary For DAV Applications)
• OPTION AND ACCESSORY CONTROL WIRING
Carrier Comfort Network Interface
. . . . . . . . . . 23
Air Pressure Tubing
. . . . . . . . . . . . . . . . . . . . . . . . 24
Gas Piping (48 Series Units Only)
. . . . . . . . . . . . 26
Installing Flue/Inlet Hoods
(48MP Units Only)
. . . . . . . . . . . . . . . . . . . . . . . . . 26
Fan Isolator Adjustment
. . . . . . . . . . . . . . . . . . . . 27
Check Compressor Mounting
. . . . . . . . . . . . . . . 27
Install Accessories
. . . . . . . . . . . . . . . . . . . . . . . . . 27
PRE-START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-38
System Check
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Compressor Oil
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Evaporator-Fan Belts, Pulleys,
and Sheaves
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Controls Configuration and Quick Test
. . . . . . 35
• SUPPLY FAN STATUS SWITCH (FS)
• CHECK FILTER SWITCH (CFS)
• ENTHALPY CONTROL SET POINT
• KEYPAD AND DISPLAY MODULE (HSIO)
CONFIGURATION
• SET UNIT TYPE
• ENTER JOB SET POINT VALUES
• CONFIGURE UNIT CONTROLS AND
FUNCTIONS
• QUICK TEST FUNCTION
Page
Gas Pressure Check
. . . . . . . . . . . . . . . . . . . . . . . . 38
Check Supply Fan Rotation
. . . . . . . . . . . . . . . . . 38
START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-42
Initial Check
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Operating Sequences
. . . . . . . . . . . . . . . . . . . . . . 39
• SUPPLY FAN
• ECONOMIZER
• COOLING (All Units)
• OCCUPIED COOLING
• UNOCCUPIED COOLING
• OVERRIDES
• ADAPTIVE OPTIMAL START
• ADAPTIVE OPTIMAL STOP
(CV Applications Only)
• GAS HEATING, OPERATION
(48MP Units Only)
Control Loop Checkout
. . . . . . . . . . . . . . . . . . . . . 41
IAQ Control Loop Adjustment
. . . . . . . . . . . . . . . 42
Lead/Lag Circuits
. . . . . . . . . . . . . . . . . . . . . . . . . . 42
Final Checks
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
CONTROL SYSTEM
. . . . . . . . . . . . . . . . . . . . . . . . 42-45
General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Components
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
• PROCESSOR MODULE NO. 1
• PROCESSOR MODULE NO. 2
• HIGH-VOLTAGE RELAY MODULES (DSIO)
• KEYPAD AND DISPLAY MODULE (HSIO)
Default Set Points/Changing Set Points
. . . . . 43
Motor Protection
. . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Variable Frequency Drive (VFD)
. . . . . . . . . . . . . 43
• DISPLAY AND KEYPAD
SERVICE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45-55
Service Access
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
• UNIT CONTROL BOX
• COMPRESSORS
• LIQUID SERVICE VALVES, SOLENOID VALVES,
FILTER DRIERS, AND SIGHT GLASSES
• EVAPORATOR-FAN MOTORS, PULLEYS, AND
BELTS
• POWER EXHAUST MOTORS, PULLEYS, AND
BELTS
• GAS HEAT SECTION
• UNIT CONTROL BOX
• ECONOMIZER DAMPER MOTORS
• RETURN-AIR FILTERS
• CONDENSER FANS AND FAN MOTORS
Cleaning
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
46
48MPD,MPE62L-10R
50MP62L-10R
Single Package Electric Cooling Units
and Gas Heating/Electric Cooling Units
With Product Integrated Controls
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
1
Tab
1a 1b
PC 111
Catalog No. 534-893
Printed in U.S.A.
Form 48/50MP-1SI
Pg 1
12-98
Replaces: 50MP-1SI
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Carrier 48MPD
Summary
INSTALLATION Jobsite Survey — Complete the following checks be- fore installation.1. Consult local building codes and the NEC (National Electrical Code) (ANSI/NFPA [National Fire ProtectionAssociation] 70) for special installation requirements. 2. Determine unit location (from project plans) or sele...
Table 1 — Physical Data BASE UNIT 48/50MP 62L 70M 82N NOMINAL CAPACITY (tons) 80 90 105 OPERATING WEIGHT (lb) Base Unit (48MP/50MP) 16,810/16,550 18,060/17,800 22,660/22,400 Copper Condenser Coils 675 725 725 Exhaust Fan 1,675 1,775 2,375 COMPRESSORS Semi-Hermetic Number of Refrigerant Circuits 2 2 ...
Make Electrical Connections POWER SUPPLY — Electrical characteristics of availablepower supply must agree with unit nameplate rating. Supplyvoltage must be within the limits shown in Table 5. Field Wire Routing — Field wiring is brought into the unitthrough the bottom of the control box. A 3 5 ⁄ 8 -...