Carrier 42BH- User Manual
Carrier 42BH– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Table of contents; Model number nomenclature; Options and accessories; Coils —; Filters —
- Page 3 – Dimensions
- Page 4 – Selection procedure
- Page 5 – Example 3: Heating selection
- Page 6 – Performance data
- Page 23 – Electrical data
- Page 24 – HVAC Guide Specifications; Guide specifications
Copyright 2001 Carrier Corporation
Form 42BH-3PD
Satisfy All Your Design Requirements
with Carrier’s Versatile 42BH Fan Coil
Unit
• A selection of 6 sizes covers
capacities from 800 to 4000 cfm
• Choice of motors, from
1
/
4
to 3 hp,
eliminates oversizing
• Wide range of coil options for 2-pipe
or 4-pipe system
• Optional DX coils with expansion
valve and distributor
Features/Benefits
The 42BH fan coil unit
provides year-round comfort
air conditioning with central
station operating economy.
A variety of coil options
reduces first cost
Four- or 6-row cooling coils combine
the capacities you need with the most
efficient heat transfer surface. For
4-pipe systems, select either of two
split-coil options. Coils consist of
aluminum fins securely bonded to
1
/
2
-in. OD seamless copper tubes.
Each fin’s aluminum collar ensures
accurate control of the fin spacing,
while completely covering the tubes to
lengthen coil life. All coils also feature
manual air vents, with automatic air
vent available as an option.
Fan wheels are designed to
provide low operating costs
The forward-curved, centrifugal,
double-inlet fans are statically and
dynamically balanced at the factory to
minimize transmission of vibration
to the building structure.
The belt-driven motor has a variable-
pitch pulley which adjusts at the jobsite
to accommodate limited ranges of air
quantities and pressures.
42BH
System Fan Coil
Air Conditioner
800 to 4000 Cfm
Product
Data
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
2 Motors are bolted to an adjustable platform for easy belt adjustment. Single-phase motors are resiliently mounted to reduce noise and vibration. Complete factory assembly minimizes on-the-jobsite costs and problems Compact, lightweight units are designed for easy mounting. One-in. duct flanges on ...
3 Dimensions UNIT DIMENSIONS — INCHES QUANTITY/UNIT A B C D E F G H J K L M N P Filters Blower Motor 42BH08 35 14 1 / 2 20 1 / 2 18 1 / 4 10 9 / 16 6 7 / 16 16 8 1 / 2 13 1 / 2 28 24 31 20 32 1 / 2 1 1 1 42BH12 35 14 1 / 2 20 1 / 2 18 1 / 4 10 9 / 16 6 7 / 16 16 12 1 / 16 14 37 33 40 29 32 1 / 2 1 1...
4 Example 1: Selection for specified total cooling I Determine job requirements: Given:Total Cooling Load . . . . . . . . . . . . . . 67.0 MBtuhSensible Cooling Load . . . . . . . . . . . 41.0 MBtuhAir Delivery . . . . . . . . . . . . . . . . . . . . . 1800 cfmEntering Air Temperature . . 75.0 F db,...